UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual Issue Date 2022-01-19 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
About This Document About This Document Purpose This document describes the high-frequency tower-mounted UPS5000-A-30 kVA & 40 kVA & 80 kVA in terms of features, appearance, structure, working principle, technical specifications, installation, operation, and maintenance. UPS is short for uninterruptible power system. Unless otherwise specified, UPS refers to all the models described in this document.
Page 4
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual About This Document Symbol Description Indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury. Indicates a potentially hazardous situation which,...
Page 5
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual About This Document Updated the Monitoring screen image. Issue 08 (2017-06-09) This issue is the eighth official release, which incorporates the following changes: Updated the Monitoring screen image. Issue 07 (2016-12-03) This issue is the seventh official release, which incorporates the following changes: Updated the UPS front space reservation in section 3.1.1 "Site".
Page 6
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual About This Document Issue 02 (2013-11-18) This is the second official release, which incorporates the following changes: Added figures of OT and DT terminals for the UPS5000-A and tables that list their specifications in section 3.1.3.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual Contents Contents About This Document........................ ii 1 Safety Information........................1 1.1 General Safety..................................1 1.2 Personnel Requirements............................... 4 1.3 Electrical Safety..................................4 1.4 Installation Environment Requirements.......................... 6 1.5 Mechanical Safety................................... 8 1.6 Device Running Safety................................
Page 8
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual Contents 3.1 Installation Preparations..............................36 3.1.1 Site......................................36 3.1.2 Tools and Instruments..............................39 3.1.3 Power Cables..................................41 3.1.4 Unpacking and Checking..............................47 3.1.4.1 30 kVA/40 kVA UPS............................... 47 3.1.4.2 80 kVA UPS..................................48 3.2 Installing a Single UPS................................
Page 9
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual Contents 4.3.3.1 Historical Alarms Page...............................134 4.3.3.2 Logs Page..................................134 4.3.4 Config. Page..................................135 4.3.4.1 User Management...............................135 4.3.4.2 Site Config..................................135 4.3.4.3 RCCMD.................................... 137 4.3.4.4 Managing the UPS by Using the NMS Complying with RFC1628 Standard........... 145 4.3.5 Protecting the Server by Using the RCCMD Software..................146...
Page 10
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual Contents 8.4 Safety Regulations and EMC............................180 8.5 Mains Input Electrical Specifications........................... 180 8.6 Bypass Input Electrical Specifications.......................... 181 8.7 Battery Specifications................................ 181 8.8 Output Electrical Specifications............................. 182 8.9 System Electrical Specifications............................. 183 A Menu Hierarchy........................184...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information Safety Information 1.1 General Safety Statement Before installing, operating, and maintaining the equipment, carefully read this document and observe all safety instructions provided herein and written on the equipment itself.
Page 12
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information ● Damage caused during transportation by the customer ● Storage conditions that do not meet the requirements specified in this document General Requirements ● Do not install, use, or operate outdoor equipment and cables (including but...
Page 13
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information ● All cable holes should be sealed. Seal the used cable holes with firestop putty. Seal the unused cable holes with the caps delivered with the cabinet. The following figure shows the criteria for correct sealing with firestop putty.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information Personal Safety ● If there is a likelihood of personal injury or equipment damage during operations, immediately stop, report the case to the supervisor, and take feasible protective measures.
Page 15
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information General Requirements Use dedicated insulated tools when performing high-voltage operations. AC and DC Power D ANGER Do not connect or disconnect power cables with power on. Transient contact between the core of the power cable and the conductor will generate electric arcs or sparks, which may cause fire or personal injury.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information ● Do not perform any improper operations, for example, dropping cables directly from a vehicle. ● When selecting, connecting, and routing cables, follow local safety regulations and rules.
Page 17
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information vents, or feeder windows of the equipment room. Ensure that no liquid enters the equipment to prevent faults or short circuits. ● If any liquid is detected inside the equipment, immediately disconnect the power supply and contact the administrator.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information 1.5 Mechanical Safety Hoisting ● Do not walk under hoisted objects. ● Only trained and qualified personnel should perform hoisting operations. ● Check that hoisting tools are available and in good condition.
Page 19
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information ● When climbing a ladder, take the following precautions to reduce risks and ensure safety: – Keep your body steady. – Do not climb higher than the fourth rung of the ladder from the top.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information ● When moving the equipment by hand, wear protective gloves to prevent injuries. ● Move or lift the equipment by holding its handles or lower edges. Do not hold...
Page 21
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information NO TICE ● This is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information Do not use the UPS in the following places: ● Environments that are close to flammable or explosive materials, dust, corrosive gases or dust, conductive or magnetic dust, abnormal vibration, or collision ●...
Page 23
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information ● The site must be equipped with qualified fire extinguishing facilities, such as firefighting sands and powder fire extinguishers. NO TICE To ensure battery safety and battery management accuracy, use batteries provided by the Company.
Page 24
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information Battery Leakage NO TICE Battery overheating causes deformation, damage, and electrolyte overflow. WARNING When the electrolyte overflows, absorb and neutralize the electrolyte immediately. When moving or handling a battery whose electrolyte leaks, note that the leaking electrolyte may cause damage.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 1 Safety Information 1.8 Others ● Exercise caution when manually shutting down the UPS inverter for transferring to bypass mode, or when adjusting the UPS output voltage level or frequency. Doing so may affect the power supply to equipment.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview Overview 2.1 Model Description This document describes the following UPS models: ● UPS5000-A-30KTTL ● UPS5000-A-40KTTL ● UPS5000-A-80KTTL Figure 2-1 Model number 2.2 Working Principles NO TE ● indicates an input mode.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview Figure 2-2 UPS conceptual diagram 2.2.2 Working Modes 2.2.2.1 Normal Mode When the UPS works in normal mode, the rectifier converts the AC input voltage into the DC voltage, which is then raised to the bus voltage by the power factor correction (PFC) circuit.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview 2.2.2.2 Bypass Mode If the inverter does not start or is manually shut down after the UPS is powered on, the bypass supplies power to loads. The UPS automatically transfers from normal mode to bypass mode if it detects power unit overtemperature, overload, or other faults that may cause the inverter to shut down.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview 2.2.2.4 Maintenance Bypass Mode The current flows through the maintenance bypass, instead of the power unit or bypass unit. UPS maintenance can be performed in this mode. Figure 2-6 UPS conceptual diagram in maintenance bypass mode 2.2.2.5 ECO Mode...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview Figure 2-9 UPS5000-A-80 kVA (1) Front panel 1 (2) MDU (3) Front panel 2 (4) Leveling foot (5) Castor (6) Chassis 2.3.2 Product Structure 2.3.2.1 30 kVA/40 kVA UPS...
Page 32
(5) MDU reset button (6) Dual in-line (7) MDU port (8) Cold-start button package (DIP) switch Figure 2-11 UPS5000-A-30 kVA/40 kVA product structure (rear view and enlarged view of certain parts) (1) Ventilation panel (2) Dry contacts (3) Battery (4) Ambient...
Page 33
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview (9) UPS mains input (10) UPS bypass input (11) Battery wiring (12) UPS output terminals (under the terminals (under the terminals (under the terminals (under the cover) cover) cover)
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview DIP1 DIP2 DIP3 LCD Operation Function Remarks Switch Status 3 Hold down the Restores the After restoring the preset Up and Down user name user name and password, buttons at the and password.
Page 35
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview Figure 2-12 UPS5000-A-80 kVA product structure (front view) (1) Bypass unit indicators (2) MDU port (3) Bypass unit ready switch (4) MDU reset button (5) DIP switch (6) Power unit indicators...
(7) Slot for dry contact (8) PDU card (optional) NO TE ● UPS5000-A-80 kVA functional components have the same functions as UPS5000-A-30 kVA/40 kVA functional components. For details, see section 2.3.2.1 30 kVA/40 kVA UPS. ● Connect the BMU by using a 04080298 transfer cable, which is delivered with the BMU.
Page 37
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview Table 2-2 Functions of the parallel port and BSC port Silk Screen Description PARALLEL The PARALLEL port transmits parallel signals. To connect multiple UPSs in parallel, use parallel cables to connect the parallel ports on the UPSs.
Page 38
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview Silk Screen Description Status BCB_OL Detects the battery circuit Status: breaker (BCB) box. ● Grounded: BCB box connected ● Floated: BCB box not connected The initial status is Grounded.
Page 39
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview Silk Screen Description Status SWITCH STATUS_BP Monitors the bypass input Status: circuit breaker on the ● Open: circuit breaker input PDC. ● Closed: circuit breaker The initial status is Closed.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview Description RS485_R+ RS485_R- NO TE If cables are prepared onsite, follow the three methods below: ● Connect pin 1 and pin 2. Pin 1 connects to RS485+ and pin 2 connects to RS485–.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview 2.4.1 Single UPS The UPS5000-A is a high frequency tower-mounted UPS. It uses a unit-level design to handle power functionality, and provides an embedded maintenance bypass switch to ensure maintenance with power on.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview Figure 2-17 Conceptual diagram of a dual-bus system 2.5 Optional Components The UPS5000-A provides a variety of optional components to address various customer requirements. Table 2-8 Optional components Componen...
Page 44
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview Componen Model Function Reference Document PDU8000-(0630, 1250, 2000) DCV8-BGA001 Battery bus ● PDU8000-063 Converges the BBB Box User Manual bar (BBB) 0DCV8- energy of BGA001 multiple battery strings. ● PDU8000-125...
Page 45
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 2 Overview Componen Model Function Reference Document BSC cable 10 m, 15 m Transmits bus synchronizatio n signals in a dual-bus system. NO TE ● Antiseismic kits can be equipped only on the UPS5000-A-80 kVA.
Page 48
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-2 UPS5000-A-80 kVA installation dimensions (unit: mm) Installation Environment ● Do not install the UPS in high temperature, low temperature, and damp areas. For details about environmental specifications.
Keep a clearance of at least 300 mm at the rear of the cabinet. If you need to perform operations at the rear of the cabinet, keep a clearance of at least 800 Figure 3-3 takes the UPS5000-A-30 kVA/40 kVA as an example to show the installation clearance. Figure 3-3 Installation clearances (unit: mm) 3.1.2 Tools and Instruments...
Page 50
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Tools and Meters Hammer drill and Hand-held Alloy hole saw Heat gun drill bit Φ16 electric drill Diagonal pliers Crimping tools Wire stripper Electric hydraulic pliers Clamp meter Multimeter...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Tools and Meters Phillips Insulated torque Heat shrink Insulated screwdriver wrench tubing adjustable wrench (M3/M4/M5/M6/ (M6/M8/M12/ M16) NO TE Table 3-1 lists only the common tools for installation and cable connection. For more dedicated tools required, see the corresponding component manuals.
Page 52
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Item 30 kVA 40 kVA 80 kVA Bypass input Bypass input current (A) Recommended 4 x 10 4 x 16 4 x 35 cross-sectional area Output Output current (A)
Page 53
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation NO TE When the mains input and bypass input share a power source, configure input power cables as mains input power cables. The cables listed in Table 3-2 are used only when the following requirements are met: ●...
Page 54
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Model Connector Connection Mode Bolt Bolt Hole Torque Specifications Diameter 30 kVA-40 Output Crimped OT 6.5 mm 4.5 N·m connectors terminal 80 kVA Crimped DT 9 mm 13 N·m...
Page 55
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-5 DT terminal for the UPS5000-A Table 3-5 DT terminal specifications for the UPS5000-A Nominal Bolt ΦH d(mm) D(mm) W(mm L(mm) conduct diam (mm) or cross- eter Nomin...
Page 56
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation NO TICE The UPS can generate large leakage currents. A circuit breaker that provides leakage current protection is not recommended. Table 3-7 Recommended input front-end and output back-end circuit breakers...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation 3.1.4 Unpacking and Checking NO TICE ● Only trained personnel are allowed to move the UPS. Use a pallet truck to transport the UPS box secured to a wooden support to the installation position.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-7 Removing packing materials Step 5 Remove the foam and moisture-proof bag, and take out the UPS. Step 6 Check that the UPS is intact. Visually inspect the UPS appearance for shipping damage. If it is damaged, notify the carrier immediately.
Page 59
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-8 Removing binding tape Step 4 Remove the packing materials and foam, as shown in Figure 3-9. Figure 3-9 Removing packing materials Step 5 Remove the moisture-proof bag.
Page 60
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Step 6 Check that the UPS is intact. Visually inspect the UPS appearance for shipping damage. If any damage is founded, notify the carrier immediately. Check that the fittings comply with the packing list. If some fittings are missing or do not comply with the packing list, record the information and contact your local Huawei office immediately.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Step 8 Remove the L-shaped bracket that secures the chassis to the pallet, as shown in Figure 3-11. Figure 3-11 Removing the L-shaped bracket NO TE Store the removed L-shaped bracket, which will be used to secure the UPS.
Page 62
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-12 Assembling support bases Step 2 Pull the back-end handle out of the UPS, as shown in Figure 3-13. Figure 3-13 Pulling the back-end handle Loosen the back-end handle screws anticlockwise.
Page 63
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-14 Placing the UPS on support bases (unit: mm) Step 4 Push the back-end handle into the groove, as shown in Figure 3-15. For details, see the instructions on the chassis.
Page 64
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-16 Installing the front panel Insert the bottom half of the panel into the UPS. Push the top half of the panel until it is securely fastened in place.
Page 65
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Rack-mounting the UPS Step 1 Remove the left and right side panels, handles, and MDU from the UPS chassis, as shown in Figure 3-18. Before you remove the MDU, remove the cables that are connected to the chassis.
Page 66
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-19 Removing the power unit and bypass unit Step 3 Install guide rails (2 U) on the cabinet. Align the lower edge of a guide rail with the lower edge of a U scale, and...
Page 67
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-20 Engaging the mounting brackets (rear view) (1) Scale (2) Mounting bracket (3) Lower edge of a U scale NO TICE Ensure that the lower edge of the guide rail is aligned with the lower edge of a U scale.
Page 68
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-22 Installing floating nuts NO TE Install floating nuts by using a flat-head screwdriver. Secure the back end of the guide rail with panel screws, as shown in Figure 3-23.
Page 69
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-24 The position of the subrack Step 5 Replace the left and right mounting brackets for the power unit, as shown in Figure 3-25. Figure 3-25 Replacing a mounting bracket...
Page 70
1) clockwise 90 degrees, install it along with the support, and connect cables, as shown in Figure 3-27. Figure 3-27 Installing the MDU Step 8 Install the front panel and rotate the Huawei logo on it clockwise 90 degrees, as shown in Figure 3-28. Issue 13 (2022-01-19)
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-28 Installing the front panel Step 9 (Recommended) Install a lock for the maintenance bypass switch, as shown in Figure 3-17. ----End 3.2.2 Installing the UPS5000-A-80 kVA Installing a UPS by Using Leveling Feet...
Page 72
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Step 2 Check the cabinet levelness using a level. If the cabinet is not leveled, adjust the leveling feet. Step 3 Reinstall the upper and lower front panels. Step 4 (Recommended) Install a lock for the maintenance bypass switch to prevent...
Page 73
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation NO TE Pay attention to the front and back edge lines of the cabinet, preventing incorrect location. Step 2 Use a hammer drill to drill holes for installing the expansion bolts and then install the four expansion bolts in the holes.
Page 74
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Partially tighten the expansion bolt and vertically insert it into the hole. Knock the expansion bolt using a rubber mallet until the expansion sleeve is fully inserted into the hole.
Page 75
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Step 1 Install guide rails at the bottom of the rack. The guide rail is 2 U high. The methods for installing guide rails on the left and right sides are the same.
Page 76
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-36 Securing a guide rail (front view) Step 2 Install one reinforced beam on the front and at the rear of the rack, as shown in Figure 3-37. Then tighten the panel screws.
Page 78
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-39 Installation positions of floating nuts Step 4 Remove the UPS front panels, MDU (with its support), power units, and bypass unit, as shown in Figure 3-40. Before you move the power unit and bypass unit,...
Page 79
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Remove UPS front panel 1. Remove UPS front panel 2. Remove the MDU. Remove the power units and bypass unit. Step 5 Install mounting brackets on the chassis, two on the left and two on the right, as...
Page 80
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-42 Placing the chassis into the rack Step 7 Adjust the four leveling feet using an adjustable wrench until the bottom of the chassis is level with the Edge of cabinet line on the scale plate, as shown in Figure 3-43.
Page 81
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-43 Adjusting the leveling feet (1) Bottom of the chassis (2) Edge of cabinet line on the scale plate Step 8 Check the cabinet levelness using a level. If the cabinet is not leveled, adjust the leveling feet.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-44 Securing the chassis to the rack Step 10 Reinstall the power units, bypass unit, MDU (with its support), and UPS font panels. NO TICE After you insert the power unit and bypass unit, rotate the ready switches to...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-45 Securing antiseismic kits to the cabinet Step 6 Adjust the cabinet position so that the expansion bolt holes are aligned with the four holes at the bottom of the cabinet.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-47 Connecting the UPS and BMU (with ambient temperature and humidity sensor) 3.2.5 Installing Batteries Context NO TICE ● Before installing batteries, read through the battery safety precautions, obtain the delivered battery installation guide, and install batteries as instructed.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation NO TICE After you install the BCB box, adjust the end of discharge (EOD) threshold based on backup time, which prevents overcurrent disconnection. The default values are as follows: ●...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation NO TE Choose an appropriate cabling route based on the actual situation. The figure is for reference only. Step 4 Connect the cable with a crimped terminal to the corresponding copper bar.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-50 Removing small covers from the bottom of the cabinet Figure 3-51 shows the power cables routed from the bottom of the cabinet. Figure 3-51 Routing power cables from the bottom of the cabinet...
Page 89
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation CA UTION If you do not ground the UPS as required, electromagnetic interference, electric shocks, or fire disasters may occur. NO TICE ● Before cable connections, ensure that all UPS input switches are OFF. Paste warning labels to prevent operation on the switches.
Step 1 If the mains input and bypass input share a power source, connect AC input power cables to mains input terminals N, and 1L1, 1L2, 1L3 on the UPS. Figure 3-54 Connecting AC input power cables to the UPS5000-A-30 kVA/40 kVA (1) Input N...
Page 91
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-55 Connecting AC input power cables to the UPS5000-A-80 kVA (1) Input N (2) Input 1L1 (3) Input 1L2 (4) Input 1L3 NO TE ● Mains and bypass input of the delivered UPSs by default share one power source. The neutral terminals of the mains and the bypass are interconnected internally.
Page 92
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-56 Removing copper bars from the UPS5000-A-30 kVA/40 kVA NO TE Install the copper bars from within outwards based on the ascending order of their numbers. Figure 3-57 Removing copper bars from the UPS5000-A-80 kVA Step 2 Connect mains input cables to mains input terminals N, and 1L1, 1L2, 1L3 on the UPS cabinet.
Page 93
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-58 Connecting AC input power cables to the UPS5000-A-30 kVA/40 kVA (1) Bypass input N (2) Bypass input 2L1 (3) Bypass input 2L2 (4) Bypass input 2L3 (5) Mains input N...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-61 Connecting AC output power cables to the UPS5000-A-80 kVA (1) Output N (2) Output U (3) Output V (4) Output W 3.2.7.5 Connecting Battery Cables D ANGER The battery voltage may result in serious injury.
Page 96
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-62 Connecting battery cables to the UPS5000-A-30 kVA/40 kVA (1) Battery input + (2) Battery input N (3) Battery input – Figure 3-63 Connecting battery cables to the UPS5000-A-80 kVA...
Figure 3-64 Neutral wire 3.2.8 Remote EPO NO TICE ● Huawei does not provide the EPO switch or cable. Prepare them by yourself. The recommended cable is 22 AWG. ● Equip the EPO switch with a protective cover to prevent misoperations, and cover the cable with protective tubing.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation 3.2.9 Connecting Communications Cables Procedure Step 1 Connect the external network management device to the RS485 port of the monitoring interface card. Step 2 Connect the network port on a PC to the FE port of the monitoring interface card.
Page 99
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-67 Cable connections for a UPS5000-A-30 kVA/40 kVA 1+1 parallel system (1) Mains input power (2) Bypass input power (3) Battery cable (4) Output power cable cable cable...
Page 100
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation NO TICE The specifications of power cables on each UPS should be the same to achieve current equalization in bypass mode. The power cables include bypass input power cables and UPS output power cables.
Page 101
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-70 Cable connections for a UPS5000-A-30 kVA/40 kVA dual-bus system (1) Mains input power (2) Bypass input power (3) Battery cable (4) Output power cable cable cable Issue 13 (2022-01-19)
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-71 Cable connections for a UPS5000-A-80 kVA dual-bus system (1) Mains input power (2) Bypass input power (3) Battery cable (4) Output power cable cable cable ----End 3.3.2 Connecting Signal Cables...
Page 103
Figure 3-72 Connecting signal cables in an N+X parallel system Figure 3-73 shows how to connect signal cables to four UPSs in parallel. Figure 3-73 Connecting signal cables in a UPS5000-A-30 kVA/40 kVA N+X parallel system ● Dual-bus system, Connect cables to BSC ports on the master and slave UPS systems.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Figure 3-74 Connecting signal cables in a UPS5000-A-30 kVA/40 kVA dual- bus system Connecting Other Signal Cables Connect the signal cables for each single UPS in a parallel system.
Page 105
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Item Acceptance Criteria Marks for tightened screws Tightened screws are marked. Serial port connection Signal cables are connected properly and (security protection securely. mechanism supported) Marks for tightened screws Both ends of a cable are labeled.
Page 106
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 3 Installation Item Acceptance Criteria Operating environment The inside and outside of the cabinet, and other operating components, are free from conductive dust. ● 30 kVA/40 kVA UPS – Ensure that there is no foreign...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI LCD and WebUI 4.1 MDU The MDU is located on the front panel of the UPS. The MDU allows you to control the UPS operation, set parameters, and view running status and alarms.
Page 110
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Indicators Table 4-1 Indicator description Indicator Color Status Meaning Mains indicator Green The UPS is in normal mode. The UPS is not in normal mode. Battery indicator Yellow The UPS is in battery mode.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Button Meaning Description ▲ Press ▲ or ▼ to scroll upward or downward. Set parameters by using the list or step ▼ Down increase or decrease. Startup/Enter/Mute On the default screen, hold down more than 5s.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI 4.2.1 Overview Symbol Meaning Table 4-3 Symbol conventions Symbol Meaning Press A. Press A and then B. NO TE The symbol conventions apply to all chapters in this document.
Page 113
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Table 4-4 Mains Input Item Description Van, Vbn, and Vcn Mains input phase voltages Ia, Ib, and Ic Mains input phase currents Frequency Mains input frequency Vab, Vbc, and Vca...
Page 114
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Table 4-7 UPS Output Item Description Van, Vbn, and Vcn UPS output phase voltage Ia, Ib, and Ic UPS output phase current Power factor_A, Power Proportion of passive power to apparent power for...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Table 4-10 Environment Monitoring Item Description Ambient temp. Temperature measured by the ambient temperature and humidity sensor. An ambient temperature and humidity sensor is required. If there is no such sensor, the data uploaded by the bypass unit is displayed.
Page 116
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-5 Sort Alarms screen ● Generate (latest first) Active alarms are displayed by occurrence time. The latest alarms are listed first. ● Severity (highest first) Active alarms are displayed by severity. The most critical alarms are listed first.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI 4.2.4 Settings Screen On the Main Menu screen, select Settings, and press . On the login screen displayed, enter the password (preset password: 000001), and press . The Settings screen is displayed.
Page 118
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Communication Settings Figure 4-8 Comm Settings screen Figure 4-9 IP settings IP address allocation ● Manual: After the MDU connects to the PC over a network cable, check that their IP addresses are two different values on the same network segment.
Page 119
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-10 RS485 communication settings Item Description Default Value Value Range Comm. This serial port address is 1–254 address allocated by the user. Baud rate Select a baud rate to match...
Page 120
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Value Range Quantity Number of cascaded ambient 0–4 temperature and humidity sensors Figure 4-12 Battery temperature sensor Item Description Default Value Value Range Start address 16–28...
Page 121
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI System Settings NO TICE ● Single/Parallel, Outp volt lev., and Outp. freq. must be set according to the system configuration. Otherwise, alarms may be generated or serious faults may occur.
Page 122
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Value Range BSC mode ● Set this parameter to Non-BSC Non-BSC, Standard BSC mode for Standard BSC a dual-bus system. ● After setting this...
Page 123
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-15 Input Settings screen Item Description Default Value Value Range Inp. Input adaptability mode 1: It Mode 2 Mode 1, Mode adaptabil. is applicable to the normal...
Page 124
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Value Range Outp. freq. Specifies the system output 50 Hz 50 Hz, 60 Hz frequency level. Output The specific voltage range The default 380 V: 209.0–...
Page 125
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Value Range Max. voltage When the difference between ● When the voltage level is the bypass voltage and the 380 V, the value range is...
Page 126
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-18 Battery Settings Screen ● Basic Parameters Figure 4-19 Basic Parameters screen Item Description Default Value Range Value Single batt. Specifies the voltage of 12 V 2, 6, 12 volt.
Page 127
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Range Value Maint. Specifies the interval for 0–365 period reminding users of battery maintenance. Cur. limit The charging current limit 0.1C10 0.05C10 to...
Page 128
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Range Value Cell float Indicates the battery float 2.25 V/cell 2.23 V/cell– volt. charging voltage. The 2.30 V/cell parameter is configurable in any mode.
Page 129
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-23 Shallow Discharge Test screen Item Description Default Value Range Value Scheduled When certain conditions Disabled Disabled, test are met, the charger shuts Enabled down, the UPS transfers...
Page 130
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI – Warning thresh. parameter If the warning function is enabled, a warning is generated when the backup time reaches the specified value. ● Remaining cap. Figure 4-25 Remaining cap. screen –...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Enable or disable PDC maintenance circuit breaker status detection. BP/SYSMT If the BP/SYSMT switch is set to Enable, the port has dry contact signal access. Using the port depends on the status of the BP/SYSMT switch.
Page 132
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Shutting Down the Inverter You can shut down the inverter manually by pressing Shutdown. Maintaining Batteries Figure 4-28 Maintain Batteries screen Item Description Update Installation Date You can update the battery installation time to the current system time.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI 4.2.6 About Screen Figure 4-29 shows the About screen. Figure 4-29 About screen On the About screen, you can view the model, manufacturer, monitoring version, and power version.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Table 4-12 User description Default User Preset User Rights Password admin (system Changeme Performs all operations on the LCD and WebUI, administrator) including system running information browsing, system information exporting,...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-30 Monitoring page NO TE If NA is displayed for load ratio, the value is invalid or outside the range. Table 4-13 Monitoring page details Number...
Page 136
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI System Settings Item Description Default Value Value Range High ambient An alarm is generated when 40–60 temperature the ambient temperature alarm reaches or exceeds the threshold (°C) threshold specified by this parameter.
Page 137
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Value Range Collect real- If this parameter is set to Disable Disable, time site Enable, one waveform can Enable waveform be stored manually.
Page 138
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Value Range Output The interruption for the UPS 0 ms, 40 ms, interruption to transfer from normal 60 ms, 80 ms, transfer time mode to bypass mode is 1–2...
Page 139
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Value Range Specifies whether to Enable Disable, overvoltage automatically clear the alarm Enable recovery and restart the rack when the rectifier or inverter shuts down due to a bus overvoltage alarm.
Page 140
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Bypass Setting Item Description Default Value Value Range BPM mode Specifies whether to start Enable Disable, upon BPM bypass mode when Enable overtemp. overtemperature occurs. Lightload Enable or disable the light...
Page 141
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Value Range Float volt. If this parameter is set to Enable, the Enable Disable, temp. float voltage is calibrated based on the Enable comp.
Page 142
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Value Range Forced When batteries are continuously under 12–24 equalized float charging or hibernation, enable charging forced equalized charging. When the protection forced equalized charging time reaches...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Item Description Default Value Value Range The calculation formula is (Charge/ Single batt. 10–30 Discharge voltage – Average voltage)/ dis. voltage Average voltage x 100%. deviation alarm thres.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-33 Control page 4.3.3 Query Page 4.3.3.1 Historical Alarms Page On the homepage, click the Query tab to open the Historical Alarms page for querying historical alarms based on severity, generation time, and clear time.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI 4.3.4 Config. Page 4.3.4.1 User Management On the home page, choose Config. > User Mgmt. Figure 4-36 User management NO TE ● On the User Mgmt. page, you can add, modify, delete, lock, or unlock users and change user passwords.
Page 146
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-37 Site configuration ● The NTP parameters are used to set the NTP server address, port number, and synchronization interval. ● The default SNMP version is SNMPv3, and the preset MD5/SHA password is Changeme1, and the preset DES/AES password is Changeme2.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI is used to configure a server for receiving alarm emails from the monitoring system. ● Set Email and Alarm Severity and simulate an alarm. Check that the alarm email can be received.
Page 148
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-39 RCCMD function enabled SSL Encrypted Transmission NO TICE The SSL encrypted transmission set on the page of the UPS5000 monitor display module (MDU) must be the same as the setting on the RCCMD client.
Page 149
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-40 SSL encrypted transmission enabled by default Figure 4-41 SSL encrypted transmission disabled Event Configuration The MDU supports 17 alarm events, and a maximum of 50 jobs can be added for...
Page 150
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI NO TE Number of jobs = Number of RCCMD Shutdown jobs + Number of RCCMD Message jobs + Number of RCCMD Execute jobs + Number of RCCMD TRAP jobs.
Page 151
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Table 4-15 Buttons after one event is expanded Name Description Button for modifying A dialog box for modifying a job is displayed after you click this button.
Page 152
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-45 RCCMD message ● RCCMD Execute: Specify the RCCMD client IP address, port, and command to be executed. For example, enter SHUTDOWN, and the RCCMD client will shut down the computer after receiving the command.
Page 153
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-47 RCCMD TRAP Table 4-16 RCCMD TRAP signal Signal Name Description Unit in the UPS #MODEL Device name #OUTPOWER Active power #OUTVOLT Output voltage #OUTCURR Output current...
Page 154
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Signal Name Description Unit in the UPS #CNT_PF Power supply failure times #CNT_BL Low battery voltage times #INPHASES Input phases #OUTPHASES Output phases When you add a job, five sending methods are available. The latter three methods can take effect only when the event condition is still true after the specified seconds.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-48 RCCMD certificate management NO TE If the RCCMD certificate key has been encrypted, enable and enter the key password. 4.3.4.4 Managing the UPS by Using the NMS Complying with RFC1628...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Managing the UPS by Using the NMS ● Applying for Access Rights To manage the UPS by using the UNMS II of Generex over the MDU, apply to the system administrator of the MDU for access rights and add the NMS information to the NMS access list of the MDU.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI 4.3.5.2 RCCMD Event Shutdown and Message Sending Procedure Step 1 On the RCCMD client, choose Connections, add the server IP address, and set the encryption mode to encryption.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Step 6 On the RCCMD client, you can view messages through the View Event Log at the upper left corner. ----End 4.3.5.3 UPS Alive Check Function Context...
Page 159
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 4 LCD and WebUI Figure 4-52 Heartbeat detecting mode on the RCCMD client You can also manually detect heartbeat by clicking Run alive check now..Figure 4-53 Detecting heartbeat manually Issue 13 (2022-01-19)
Procedure Step 1 Close the upstream bypass and mains input switches. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar. Step 2 After the LCD starts properly, perform the following operations: ●...
Page 162
UPS (when no battery string is shared). High or low charging power shortens the battery lifespan, or even promptly damages batteries. To determine the battery capacity, contact Huawei technical support. Figure 5-1 Settings wizard Step 3 After the quick settings, if no alarm is displayed on the LCD, go to the next step. If any abnormal alarm is displayed, clear the abnormal alarm.
Page 163
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations Step 4 View the system running diagram on the LCD to check whether the parallel system has transferred to bypass mode. Step 5 Start the inverter. ● Start the inverter on the LCD.
Page 164
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations Figure 5-3 WebUI login On the home page, choose Monitoring > Control. Click Inv. ON. In the displayed dialog box, click OK to start the inverter. Figure 5-4 Starting the inverter...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations Ph. B output volt., and Ph. C output volt. under Actual Value and click Submit at the end of each row to commission the voltages. NO TE Commission the voltages on other power uints one by one.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations ● Shut down the inverter on the WebUI. On the homepage, choose Monitoring > Control. Click Inv. OFF. In the displayed dialog box, click OK to shut down the inverter, as shown in Figure 5-7.
Step 4 Press and hold down the BATT START button on the bypass unit for at least 2 seconds. The system automatically enters the battery cold start status. The LCD displays the Huawei logo and an initialization progress bar. Step 5 After LCD initialization, start the inverter on the LCD.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations Step 2 Select a value (±5%, ±6%, ±7%, ±8%, ±9%, or ±10%) from the ECO volt. range drop-down list box, as shown in Figure 5-8. Click to select ECO volt. range, press ▲...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations Procedure Step 1 Log in to the WebUI. Step 2 On the Monitoring > Control > System Commands and Tests page, click Start next to Forced equalized charging to start a forced equalized charging test.
Page 170
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations Step 2 On the home screen of the WEBUI, choose Monitoring > Param. Settings > Battery Setting, and set Sched. shallow dis. test to Enable. Step 3 Set Sched. shallow dis. test time, Sched. shallow dis. test interval and Shallow dis.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations 5.6.3 Capacity Test Context NO TICE Before conducting a capacity test, check whether the requirements of a capacity test are met. If the requirements are met, the button for starting a capacity test is available.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations NO TE Click Stop next to Capacity test in any of the following cases: ● The battery discharge voltage reaches the end of discharge (EOD) voltage plus 0.01 V.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations Figure 5-15 Turning on the maintenance bypass switch on the UPS5000-A-80 kVA The UPS transfers to maintenance bypass mode. The Maint. Breaker closed alarm is displayed on the LCD and WebUI, as shown in...
Page 175
5-19. The Maint. breaker closed alarm disappears on the LCD and WebUI. View the system running diagram on the LCD or WebUI to check that the UPS has transferred to bypass mode. Figure 5-18 Turning off the maintenance bypass switch on the UPS5000-A-30 kVA/40 kVA Issue 13 (2022-01-19)
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations Figure 5-19 Turning off the maintenance bypass switch on the UPS5000-A-80 kVA Step 2 Start the inverter. ----End 5.9 Performing EPO Context NO TICE ● On the WebUI, EPO can be performed only when Monitoring > Param.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations Figure 5-20 EPO alarm on the LCD Figure 5-21 EPO alarm on the WebUI ----End 5.10 Clearing the EPO State Procedure Step 1 Turn off the external EPO switch that connects to the dry contact. Ensure that the EPO switch is not in the EPO state.
Page 178
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 5 Operations ● WebUI On the WebUI, choose Monitoring > Control and click Clear Fault to clear the EPO alarm, as shown in Figure 5-24. Figure 5-24 Clearing the alarm on the WebUI Step 3 Check that the EPO alarm has disappeared from the alarm list.
Customers are not allowed to maintain components behind protective covers that can be removed only using tools. If the components are to be maintained, contact Huawei technical support. ● Only maintenance engineers can maintain power units and bypass units.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 6 Routine Maintenance 6.1.1 Monthly Maintenance Table 6-1 Monthly maintenance Check Item Expected Result Troubleshooting Operating ● Ambient temperature: 0– ● If the humidity or environment 40°C temperature is abnormal, check the air conditioner ●...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 6 Routine Maintenance Check Item Expected Result Troubleshooting Parameter The configuration of the Reset the parameters. configuration output voltage grade, frequency, number of batteries, and battery capacity meets requirements. Status record...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 6 Routine Maintenance Table 6-4 Service life parameters for replaceable components and recommended replacement intervals Key Component Design Service Life Recommended Replacement Interval Power unit 15 years 10 years Bypass unit...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 6 Routine Maintenance 6.2.2 Monthly Maintenance Table 6-5 Monthly maintenance Item Expected Result Troubleshooting Battery No battery management Identify the cause of an alarm management alarm is generated. based on the alarm alarm information.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 6 Routine Maintenance 6.2.3 Quarterly Maintenance Table 6-6 Quarterly maintenance Item Expected Result Troubleshooting Battery temperature The difference between 1. Install the temperature sensor measurement the temperature sensor in the correct...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 6 Routine Maintenance Item Expected Result Troubleshooting Shallow discharge test Conduct a shallow 1. If the batteries cannot (recommended) discharge test when the discharge normally, UPS is backed up to verify...
Page 187
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 7 Troubleshooting Table 7-1 Solutions to common faults Case Symptom Possible Cause Measure The rectifier is not The mains voltage exceeds Check whether the mains rectifier working, and the bus the upper threshold 280 V...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 8 Technical Specifications Technical Specifications 8.1 Physical Specifications Item 30 kVA 40 kVA 80 kVA Cabling mode Cables are routed from the bottom. Protection level IP20 Communication Optional card slot, RS485 port, and FE port; SNMP and...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 8 Technical Specifications Item 30 kVA 40 kVA 80 kVA Storage temperature –40°C to +70°C Humidity 0–95% RH (non-condensing) Altitude 0–1000 m When the altitude is above 1000 m (maximum 4000 m), see IEC62040-3 to check how the load power is derated.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 8 Technical Specifications Item 30 kVA 40 kVA 80 kVA Input voltage 80–280 V AC (phase voltage) ● At 30–40°C: The UPS works at full load when the voltage is 187–280 V AC and is derated to 40% load when the voltage is 187–80 V AC.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual 8 Technical Specifications Item 30 kVA 40 kVA 80 kVA Battery string No battery string is shared by default. Battery string sharing sharing is supported in a parallel system. Charge voltage ●...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual A Menu Hierarchy Menu Hierarchy A.1 LCD Menus Level-1 Menu Level-2 Menu Level-3 Menu Main Menu Status Mains Input Bypass Input Battery Status UPS Output Local-UPS Load Parallel-System Load Environment Monitoring...
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual A Menu Hierarchy Level-1 Menu Level-2 Menu Level-3 Menu Bypass Settings Battery Settings Dry Contact Set Settings Wizard Restore Default Settings Control Inv. ON Inv. OFF Parallel Inv. ON (available in parallel UPS mode) Parallel Inv.
Page 196
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual A Menu Hierarchy Level-1 Menu Level-2 Menu Level-3 Menu Battery Settings Dry Contacts Comm. Config. IP Settings RS485 Settings ModbusTCP Settings Amb T/H Sensor Batt Temp Sensor WiFi Settings Control System Commands and...
Page 197
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual A Menu Hierarchy Level-1 Menu Level-2 Menu Level-3 Menu ModbusTCP CA Certificate Management ModbusTCP Authentication eUPS Certificate Management RCCMD RCCMD SSL Encrypted Transmission Event Configuration RCCMD Certificate Management Maint. Calib Module Commissioning Var.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0001-1 Mains Minor ● Cable 1. Check whether cables to mains are voltage connections disconnected, loose, or incorrectly abnormal connected.
Page 199
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0005-1 Mains Minor Cable 1. Secure or connect the neutral wire to neutral connections the cabinet if it is loose or absent are incorrect.
Page 200
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0020-1 Battery Critical Batteries are 1. Check whether battery polarities are connected not properly correctly installed by using a reversely installed.
Page 201
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0026-1 Low battery Minor ● Battery 1. If the low battery voltage alarm is voltage discharge generated in battery mode, check results in whether the mains voltage recovers.
Page 202
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0032-1 Battery Critical ● The battery 1. Check the battery voltage. overvoltage voltage is 2. Check that the configured number of...
Page 203
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0043-1 Critical ● The fan for Replace the faulty power unit. abnormal the power unit is abnormal. ● The fan...
Page 204
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0564-1 Overload Critical ● The load is 1. Check that there is no overload. timeout excessive. 2. Check that the unit power is not ●...
Page 205
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0570-4 BPM unit Critical ● The bypass 1. Check the bypass fan and air abnormal fan is not channel. If the fan is faulty, replace...
Page 206
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0583-6 ● The intra- rack INVBYP cable is broken. ● The parallel CAN bus is broken. 0584-2 Inter-rack Minor The inter-rack Replace the parallel cable.
Page 207
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0090-2 Replace the dry contact board MUE06A. communicatio n with the dry contact board MUE06A fails. 0356 Battery Minor The UPS is The running status is displayed.
Page 208
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0096-1 ECO volt. Minor ● The ECO 1. Check the bypass input voltage and Abnormal bypass frequency. voltage or 2.
Page 209
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual B Alarm List Alarm ID Alarm Severity Cause Solution (Alarm Name ID-Cause 0150-1 Inverter Minor ● The bypass 1. Check that the bypass output asynchronou frequency frequency does not change fast.
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual C Acronyms and Abbreviations Acronyms and Abbreviations Alternating Current American Wire Gauge Battery Circuit Breaker Bus Sync Controller Controller Area Network Conformite Europeenne Direct Current D.G. Diesel Generator Dual In-Line Package...
Page 211
UPS5000-A-30 kVA, 40 kVA and 80 kVA User Manual C Acronyms and Abbreviations Fast Ethernet Internet Data Center International Electrotechnical Comission Internet Protocol Liquid Crystal Display Monitor Display Unit Printed Circuit Board Power Distribution Cabinet Protective Earthing RS485 Recommend Standard 485...