Summary of Contents for Honeywell FIRE-LITE MS-10UD Series
Page 1
Fire Alarm Control Panels MS-5UD & MS-10UD Series Manual Document 52626 Rev: C7 6/12/2018 ECN:18-253...
Page 2
Fire Alarm & Emergency Communication System Limitations While a life safety system may lower insurance rates, it is not a substitute for life and property insurance! An automatic fire alarm system—typically made up of smoke Heat detectors do not sense particles of combustion and alarm detectors, heat detectors, manual pull stations, audible warning only when heat on their sensors increases at a predetermined rate devices, and a fire alarm control panel (FACP) with remote notifica-...
Page 3
LiteSpeed™ and Lite-Connect™ are trademarks; and Fire-Lite® Alarms, Honeywell®, and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
Page 4
• Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services. MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018...
Table of Contents Section 1: Product Description ............................12 1.1: Product Features ......................................12 1.2: Specifications........................................13 1.3: Controls and Indicators....................................17 1.4: Digital Alarm Communicator/Transmitter...............................17 1.5: Components ........................................18 1.6: Optional Modules and Accessories..................................18 1.7: Telephone Requirements and Warnings................................19 1.7.1: Telephone Circuitry ....................................19 1.7.2: Digital Communicator ..................................19 1.7.3: Telephone Company Rights and Warnings ............................19 1.7.4: For Canadian Applications ...................................20...
Page 7
Table of Contents 4.17: Special System Timers....................................100 4.17.1: Silence Inhibit Timer ..................................100 4.17.2: Autosilence Timer ....................................101 4.17.3: Trouble Reminder .....................................101 4.17.4: Waterflow Retard Timer...................................101 4.17.5: Alarm Verification (None or One Minute) ............................101 4.18: Walktest........................................101 4.19: Read Status ........................................102 4.19.1: Input Zones .......................................102 4.19.2: NAC ........................................102 4.19.3: Relays .......................................103 4.19.4: System Settings....................................103...
Page 8
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the stan- dards set forth by the following regulatory agencies: • Underwriters Laboratories/Underwriters Laboratories Canada • National Fire Protection Association Before proceeding, the installer should be familiar with the following documents. NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards: NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an...
Page 9
MS-5UD Series Main Circuit Board ms-5udlayout.wmf MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018...
Page 10
MS-10UD Series Main Circuit Board ms-10udlayout.wmf MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018...
Section 1: Product Description The MS-5UD is a five zone FACP (Fire Alarm Control Panel) and the MS-10UD is a ten zone FACP. The information in this manual refers to both the MS-5UD and MS-10UD unless otherwise specified. The combination control and digital communicator panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings.
Specifications Product Description • 80-character LCD display (backlit) • Real-time clock/calendar with daylight savings time control • History log with 256 event storage • Control Buttons ACK (Acknowledge) Alarm Silence System Reset/Lamp Test Drill • LED Indicators ...
Page 14
Product Description Specifications Normal Operating Voltage: Nominal 20 VDC Alarm Current: 15 mA minimum Short Circuit Current: 40 mA max. Maximum Loop Resistance: 100 ohms (700 ohms per zone for linear heat detection - See Section 2.3, “Input Circuits” for more informa- tion.) End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252) Standby Current: 2 mA...
Page 15
Specifications Product Description The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP with the FLPS-3 power supply. This applies to the MS-5UD-3, MS-10UD-3, MS-5UD-3E, and MS-10UD-3E. Special Application 0.5 amp max Nonresettable or...
Page 16
Product Description Specifications The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available from the FACP with the FLPS-7 power supply. This applies to the MS-5UD-7, MS-5UD-7C, MS-10UD-7, MS-10UD-7C, MS-5UD-7E, and MS-10UD-7E.
Controls and Indicators Product Description 1.3 Controls and Indicators LCD Display The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost SYSTEM ALL NORMAL and the system is not in alarm, the LED backlight will turn off to conserve batteries.
Product Description Components 1.5 Components Main Circuit Board The main circuit board contains the system’s CPU, DACT and other primary components and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board. Power Supply One power supply is provided standard with each FACP, mounted to a chassis. •...
Telephone Requirements and Warnings Product Description Battery Charger CHG-75 Battery Charger The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the FACP. The FACP battery charger must be disabled, through software programming, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel.
Product Description Telephone Requirements and Warnings If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible.
Section 2: Installation The cabinet can be surface mounted or semi-flush mounted. The door is removable during the installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional securing holes located at the bot- tom.
Page 22
Installation Backbox Mounting Semi-Flush Mounting Do not recess box more than 3.875” into wall to avoid covering venting Hinge Slot for optional holes on top of box. Dress Panel Mounting slots for optional Trim Ring Semi- Flush mounting hole Hinge Slot for optional Dress Panel Figure 2.2 Cabinet Dimensions MS-5UD &...
Operating Power Installation Depth = 5.207” (13.23 cm) Depth = 5.257” Door = 16.821” (42.73 cm) (13.353 cm) Backbox = 16.65” (42.29 cm) Door = 19.26” (48.92 cm) Backbox = 19.0” (48.26) Left Side Right Side Bottom Figure 2.3 Backbox and Battery Box 2.2 Operating Power WARNING: RISK OF ELECTRICAL SHOCK AND/OR EQUIPMENT DAMAGE SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL.
Installation Input Circuits MS-5UDC-7(C)(E) MS-5UD-3(E) MS-10UD-7(C)(E) MS-10UD-3(E) FLPS-3 FLPS-7 Power Supply Power Supply AC Power AC Power AC Hot Hot (L1) AC Neutral Earth Earth Neutral (L2) Ground Stud Ground Stud to batteries to batteries Figure 2.4 Operating Power Connections 2.3 Input Circuits The MS-5UD has five IDCs (Initiating Device Circuits) and the MS-10UD has ten IDCs.
Page 25
Input Circuits Installation Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A Converter module. Refer to “CAC-5X Class A Converter Module” on page 31. Class B Initiating Device Circuits (supervised and power-limited) 4.7 KΩ, ½ watt resistor P/N:71252 UL listed Power Supervision Relay (refer to Device Compatibility Document for list of compatible relays) UL listed compatible...
Installation Output Circuits Combination Waterflow/Supervisory Zone A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm switch (waterflow device) and a Super- visory switch (tamper) installed on the same circuit. Any circuit can be programmed as a Combo Type zone. The following figure illus- trates the wiring of Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.
Output Circuits Installation For FCC compliance with Class B wiring, a ferrite bead (supplied) is required for NAC 1 and for NAC 2. If using both NAC 1 and NAC 2 with Class B wiring, a single ferrite may be used with wiring as shown in Figure 2.7. Class B Notification Appliance Circuits (supervised and power-limited) 4.7 KΩ, ½...
Installation Output Circuits 2.4.3 Relays - Programmable The MS-5UD and MS-10UD control panels provide a factory default programmed alarm relay, fail-safe trouble relay and supervisory relay. Each relay can be programmed to activate for other conditions (refer to “Relays” on page 67). Each Form-C relay is rated for 2 amps @ 30VDC (resistive) and 0.5 amps @ 30 VAC (resistive).
Power-limited Wiring Requirements Installation 2.5 Power-limited Wiring Requirements Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wir- ing must enter and exit the cabinet through different knockouts and/or conduits.
Installation Digital Communicator 2.6 Digital Communicator Two independent telephone lines can be connected to the control panel. Telephone line control/command is made possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is critical that the panel's digital communicator be located as the first device on the incoming telephone circuit to properly function.
Installation of Optional Modules Installation 2.7 Installation of Optional Modules WARNING: RISK OF ELECTRICAL SHOCK REMOVE ALL POWER (AC AND DC) BEFORE INSTALLING OR REMOVING MODULES OR WIRING. 2.7.1 CAC-5X Class A Converter Module Installation The CAC-5X Module can be used to convert five Style B (Class B) Initiating Device Circuits to Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z (Class A).
Installation Installation of Optional Modules not wire to the corresponding A+ and A- terminals on the CAC-5X module. For FCC compliance with Class A wiring, a ferrite bead (supplied with the CAC-5X board) is required for NAC 1 and for NAC 2. If using NAC 1 and/or NAC 2 with Class A wiring, a ferrite must be used for each NAC with wiring as shown in Figure 2.15.
Installation of Optional Modules Installation Standoffs Note: This illustration shows the installation of the Option Module on the 5-zone panel. The module is installed in the same location on the 10-zone panel. Figure 2.16 4XTMF Option Module Connection to MS-5UD 4XTMF Transmitter Module Installation The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity.
Installation Installation of Optional Modules Before installing the module, place the disconnect switch to the down (disconnect) position to prevent accidental activation of the munic- ipal box. Note that a Disconnect LED will illuminate after the module is installed in the FACP. In addition, the System Trouble LED will turn on to indicate the Disconnect condition.
ANN-BUS Devices Installation 2.8 ANN-BUS Devices WARNING: RISK OF ELECTRICAL SHOCK DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY MODULES OR WIRING. Guidelines • A variety of optional annunciation devices can be connected to an ANN-BUS communication circuit. ANN Series devices can be connected to the primary communication circuit (EIA-485) terminals on TB3.
Page 36
Installation ANN-BUS Devices The following formulas were used to generate the wire distance chart: Maximum Resistance (Ohms) 6.0 Volts Total Worst Case Current Draw (amps) Maximum Wire Length (feet) Maximum Resistance (Ohms) *500 (6,000 feet maximum) where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below) Wire Gauge Ohms per 1,000 feet (Rpu) 16.2...
ANN-BUS Devices Installation Wiring Configuration Figure 2.19 illustrates the wiring between the FACP’s Primary ANN-BUS and ANN-BUS devices. FACP Primary ANN-BUS ANN-BUS and power wiring are supervised and power-limited ANN-80 Figure 2.19 FACP wiring to ANN-BUS Device on Primary ANN-BUS illustrates the wiring between the FACP’s Secondary ANN-BUS, via the ANN-SEC option card, and ANN-BUS devices.
Installation ANN-BUS Devices Powering ANN-BUS Devices from Auxiliary Power Supply Figure 2.21 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as the FCPS-24FS6/8, when the maxi- mum number of ANN-BUS devices exceeds the ANN-BUS power requirements. Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults) MS-5UD/MS-10UD ANN-BUS...
ANN-BUS Devices Installation these buttons. Communication between the ANN-80(C) and FACP is accomplished over a two wire serial interface employing the ANN-BUS communication format. The devices are powered, via two additional wires, from either the host FACP or remote UL-listed, filtered, power supply.
Installation ANN-BUS Devices Wiring ANN-80 to FACP The following steps can be used as a guide to wire the annunciator. Make certain all power has been removed from the FACP prior to annunciator installation. Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal block TB1. wiring channel wires Remove appropriate amount of wire insulation.
ANN-BUS Devices Installation Programming Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator must be added to the system via FACP programming. Refer to the programming section titled “ANN-BUS” on page 71 in this manual for detailed programming information. Select the LCD option for programming.
ANN-BUS Devices Installation 2.8.5 ANN-I/O LED Driver Module The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40 LEDs. The following sections describe hardware installation. Refer to the section titled“ANN-BUS”...
Installation ANN-BUS Devices ANN-I/O Connection to FACP The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.25. After the ANN-I/O is connected to the panel, it must be added to the system via FACP programming. Primary ANN-BUS ANN-I/O Module ANN-BUS and power wiring are supervised and power-limited...
ANN-BUS Devices Installation The LEDs are wired as illustrated in Figure 2.26. Note that the illustration depicts only connectors P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40). Figure 2.26 ANN-I/O Board Layout 2.8.6 ANN-LED Annunciator Module The ANN-LED annunciator module provides LED annunciation of general system faults and input zones when used with a compatible FACP.
ANN-BUS Devices Installation Mounting/Installation The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis or inside the ROME Series enclosure. Refer to the ANN-RLY Installation Document #53033 for instructions on chassis mounting or to the ROME Series Installation Document #53530 for mounting in the separate backbox.
Installation ANN-BUS Audio Panel ANN-RLY Board Layout and Connection to FACP Figure 2.29 illustrates the ANN-RLY board wiring connections to the FACP. ANN-BUS (ID#) Address DIP switch ANN-RLY FACP -24 VDC +24 VDC Primary ANN-BUS Figure 2.29 ANN-RLY Board Layout and Connection to FACP 2.9 ANN-BUS Audio Panel WARNING: RISK OF ELECTRICAL SHOCK DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY WIRING.
Page 49
ANN-BUS Audio Panel Installation The only connection between the MS-5UD/10UD and the ACC-25/50ZS/T audio panel is a pair of communication wires connected between the A/B terminals on TB3 of the FACP and TB1 terminals 2 & 3 of the ACC-ZPMK module on the ACC-25/50ZS/T. FACP A (+) B (-)
Section 3: Programming NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below: Permitted in UL Program feature or option...
Page 51
User Programming Programming Exit Programming and Read Status Mode The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the display reads System All Normal. Ten minutes of inactivity will also cause the panel to exit Programming Mode Note that the data which is entered during Programming mode is not saved until the programmer exits this mode by repeatedly pressing the ‘ESC’...
Programming Initial Power-up User Programming Levels There are two user programming levels: • User Master Program Level 1 is used for programming panel specific data relating to device types, zoning, messages, control panel functions, etc. • User Maintenance Program Level 2 is used by a qualified operator to access features such as Disable/Enable, View and Clear History, Walktest and System Time Change.
Master Programming Level Programming Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key. 3.5 Master Programming Level When the Master Program Level password is entered, the control panel will enter user Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and the system Trouble LED flashes until Programming mode is exited.
Page 54
Programming Master Programming Level Enable/Disable Zone To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2. Each press of INPUT ZONE the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the zone will 1=ENABLED 2=TYPE be disabled by the control panel, preventing the circuit from reporting alarms and troubles to the panel.
Page 55
Master Programming Level Programming Type To select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone Screen #2. This will cause the control panel to display the following Zone Type Screen: ZONE TYPE 1=PULL STATION 2=WATERFLOW 3=WATERFLOW NS...
Page 56
Programming Master Programming Level Verification Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and not a INPUT ZONE false alarm. This feature is selected by pressing 3 while viewing the Edit Zone Screen #2 so that the display 1=ENABLED 2=TYPE reads Verification On.
Page 57
Master Programming Level Programming PAS/Pre-Signal Delay Pressing 1 while viewing Edit Input Zone Screen #3 will display the following screen: INPUT ZONE # 1=PAS/PRE-SIG DELAY PAS/PRE-SIG DELAY NO DELAY 1=NO DELAY Edit Input Zone Screen #3 2=PRE-SIGNAL DELAY 3=PAS DELAY PAS/Pre-Signal Delay Screen MS-5UD &...
Page 58
Programming Master Programming Level Pre-signal The Pre-signal option programs the zone to delay panel activation for a preprogrammed time delay of up to three minutes while allowing for visual verification by a person. Note that the alarm relay and communicator will respond to the initial alarm immediately. To enable the Pre-signal feature, press 2 while viewing PAS/Pre-Signal Screen.
Page 59
Master Programming Level Programming The PAS (Positive Alarm Sequence) option will program the zone to delay panel activation (including alarm relay and communicator) for a period of 15 seconds plus a programmable time of up to 3 minutes. To enable the PAS feature, press 3 while viewing the PAS/Pre- Signal Screen.
Page 60
Programming Master Programming Level Freeze Supervision Pressing 1 for Freeze Supv. while viewing Edit Input Zone Screen #4 programs the FACP to supervise the INPUT ZONE # devices connected to the selected zone for freeze conditions. Each press of the 1 key will toggle the display 1=FREEZE SUPV.
Page 61
Master Programming Level Programming ACC Message Pressing 2 for ACC MSG # while viewing Edit Input Zone Screen #4 will cause the following screens to be displayed: ACC MSG NUMBER ACC MSG NUMBER ACC MSG NUMBER 1=NO MSG-ACTIVE 1=MESSAGE 2 1=MESSAGE 5 2=MESSAGE 3 2=NO MSG-INACTIVE...
Page 62
Programming Master Programming Level Adjective/Noun The Adjective/Noun selection allows the programmer to enter specific descriptors about the detector cur- INPUT ZONE # rently being programmed. Pressing 1 while viewing Edit Input Zone Screen #4 will cause the following 1=ADJECTIVE/NOUN 2=DESCRIPTION screen to be displayed: ...
Page 63
Master Programming Level Programming Description The Description selection allows the programmer to enter additional information about the zone currently INPUT ZONE # being programmed. This information will be displayed as part of the device label on the display. Pressing 2 1=ADJECTIVE/NOUN 2=DESCRIPTION while viewing Edit Input Zone Screen #4 will cause the following screen to be displayed:...
Programming Master Programming Level Recall/Increment Function In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Description, Adjective or Noun field as follows: • If the zero key is pressed, a 0 is placed in the first letter position •...
Page 65
Master Programming Level Programming Selection of one of the above options will cause the control panel to store the information in memory and return the display to NAC Screen #1, which will display the new coding choice. Two Stage Operation ...
Programming Master Programming Level Maximum Number of Strobes for Synchronization The maximum current draw for a Notification Appliance Circuit cannot exceed 2.5 amps for models with the FLPS-3 power supply or 3.0 amps for models with the FLPS-7 power supply (refer to the AC Power section under“Specifications” on page 13). Refer to the man- ufacturer’s documentation supplied with the Strobes to determine the maximum current draw for each strobe and ensure that the circuit maximum is not exceeded.
Master Programming Level Programming 3.5.3 Relays Pressing 3 while viewing Programming Screen #1 will allow the programmer to configure the three main PROGRAMMING circuit board Form-C relays. The following screen will be displayed: 1=INPUT ZONES 2=NACS 3=RELAYS RELAYS Programming Screen #1 1=RELAY 1 ALARM 2=RELAY 2...
Page 68
Programming Master Programming Level PAS (Positive Alarm Sequence) Delay The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds for all TIMERS devices programmed for PAS, press 1 while viewing Timer Screen #1. The following display will appear: 1=PAS DELAY 2=PRE SIGNAL 3=WATERFLW DELAY...
Master Programming Level Programming Banner STEM SETUP The top line of the display, which appears when the control panel is in normal mode, can be changed by using the Banner option. Press- NNER ME-DATE ing 2 while viewing System Setup Screen #1 will cause the following to be displayed: m Setup Screen #1 SELECT BANNER 1=FACTORY BANNER...
Programming Master Programming Level Date To change the date, press 2 while viewing the Time-Date Screen. The following screen will be displayed: ENTER DATE -- MONTH DAY YEAR 06-07-2018 Date Screen A flashing cursor is located toward the top left of the display. Below the cursor is the current date. To change the date, enter the two-digit month followed by the two-digit day and then the two-digit year (18 for 2018, 19 for 2019 etc.).
Master Programming Level Programming medical alert combo autoresettable • The auto-silence feature can be enabled or disabled. If this feature is enabled, the alarm signals will be turned off after 20 minutes of activation • The installer must write in the Date of Final Assembly on the Master Marking and Warranty label, located on the FACP backbox door Charger Disable Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or disable the onboard battery charger.
Page 72
Programming Master Programming Level Auto-Configure The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed ANN-BUS modules online. The software will search for all ANN-BUS modules and automatically program the device type and address into the system. Pressing 3 while viewing ANN-BUS Screen #1 will begin the Auto-Configure process and cause the following screen to be displayed: ANN-BUS AUTO-CONGFIGURE...
Page 73
Master Programming Level Programming Zone 5 Alarm Zone 6 Alarm Zone 7 Alarm Zone 8 Alarm Zone 9 Alarm Zone 10 Alarm Zone 1 Trouble Zone 2 Trouble Zone 3 Trouble Zone 4 Trouble Zone 5 Trouble Zone 6 Trouble Zone 7 Trouble Zone 8 Trouble Zone 9 Trouble...
Programming Master Programming Level ANN-RLY Options Screen Pressing 3 for ANN-RLY Options while viewing ANN-BUS Screen #2 will cause the following screen to be PROGRAMMING displayed: 1=ANN-S/PG OPTIONS 2=ANN-80 OPTIONS 3=ANN-RLY OPTIONS ANN-RLY OPTIONS ANN-BUS Screen #2 1=RELAY 1 IN ZONE 1 2=RELAY 2 IN ZONE 2 3=RELAY 3...
Master Programming Level Programming Onboard DACT The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a central sta- ANN-BUS tion. Pressing 2 while viewing the Option Module Screen will cause the following screens to be displayed: 1=ANN-AUDIO OPTIONS 2=ANN-SEC ENABLE ON BOARD DACT ON BOARD DACT ANN-BUS Screen #3...
Page 76
Programming Master Programming Level Reporting To enable the DACT for reporting FACP activity to the central station, press 1 while viewing Central Station Screen #1 so the display reads Reporting Yes. Each press of the 1 key will toggle the display between Reporting Yes and Reporting No. MS-5UD &...
Page 77
Master Programming Level Programming Report Style The DACT can be programmed to transmit reports to primary and/or secondary central station phone numbers as a backup. Press 2 while viewing Central Station Screen #1 to display the following screen: REPORT STYLE 1=BACKUP ONLY 2=BOTH 3=FIRST AVAILABLE...
Page 78
Programming Master Programming Level Central Station Primary and Secondary Phone Numbers Pressing 1 for Primary or 2 for Secondary, while viewing Central Station Screen #2, will display the fol- CENTRAL STATION lowing screens. 1=PRIMARY 2=SECONDARY Note that the following information must be entered for both the Primary and Secondary Central Station 3=CALL LIMIT Phone Numbers.
Page 79
Master Programming Level Programming Test Time Interval Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following screens to be displayed: CENTRAL STATION 1=TEST TIME INT TEST TIME INTERVAL TEST TIME INTERVAL 2=ACCOUNT CODE 1=24 HOURS 1=6 HOURS 3=24HR TST TIME Primary/Secondary Screen #1 2=12 HOURS 3=8 HOURS...
Page 80
Programming Master Programming Level Account Code Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following screen to be displayed: ACCOUNT CODE RANGE 0000-FFFF Account Codes Screen The Account Code, which is assigned by a Central Station, depends on the communication format being used. The Account Code screen will have a flashing cursor in the lower left corner.
Page 81
Master Programming Level Programming 24 Hour Test Time Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be displayed: CENTRAL STATION 1=TEST TIME INT 2=ACCOUNT CODE 24 HOUR TEST TIME 3=24HR T TIME ENTR USING 24HR TIME Primary/Secondary Screen #1 RANGE 0000-2359 24 Hour Test Time Screen...
Page 82
Programming Master Programming Level Phone Number Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following screen to be displayed: CENTRAL STATION 1=PHONE NUMBER PHONE NUMBER Primary/Secondary Screen #2 20 NUMBERS MAXIMUM Phone Number Screen The Phone Number screen is used to enter the Central Station phone number that the DACT will be contacting. A maximum of 20 char- acters can be entered with valid entries being 0 - 9 and A - C where A = *, B = # and C = look for secondary dial tone for up to 2 seconds (then dial anyway).
Page 83
Master Programming Level Programming Communication Format Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following screen to be displayed: CENTRAL STATION 1=COMM FORMAT COMM FORMAT 2=EVENT CODES 1=ADEMCO CONTACT ID Primary/Secondary Screen #3 2=SIA-DCS-8 3=SIA-DCS-20 The Communication Format is determined by the type of receiver that the DACT is transmitting to. Consult your Central Station for proper selection or consult our factory representatives.
Page 84
Programming Master Programming Level Event Codes Pressing 2 while viewing Primary/Secondary Screen #3 will cause the following screen to be displayed: EVENT CODES 1=ZONE 1 ALARM 2=ZONE 2 ALARM 3=ZONE 3 ALARM Event Code Screen Pressing the down arrow key allows viewing of all Events associated with the selected Communication Format. Pressing the number cor- responding to the event displayed in each screen will display its default active and restoral event codes which can be customized by the programmer.
Page 85
Master Programming Level Programming Ademco Contact ID Format - Primary Central Station Phone Number The information shown in Table 3.4 is automatically programmed for the Primary Central Station phone number Event Codes when Ademco Contact ID Format is selected. To disable event reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to disable it.
Page 86
Programming Master Programming Level Ademco Contact ID Format - Secondary Central Station Phone Number The information shown in Table 3.5 is automatically programmed for the Secondary Central Station phone number Event Codes when Ademco Contact ID Format is selected. To disable event reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to disable it.
Page 87
Master Programming Level Programming SIA-DCS Format - Primary Central Station Phone Number The information shown in Table 3.6 is automatically programmed for the Primary Central Station phone number Event Codes when SIA-DCS Format is selected. To disable event reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to disable it.
Page 89
Master Programming Level Programming SIA-DCS Format - Secondary Central Station Phone Number The information shown in Table 3.7 is automatically programmed for the Secondary Central Station phone number Event Codes when SIA-DCS Format is selected. To disable event reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to disable it.
Master Programming Level Programming Pressing 1 while viewing Onboard DACT Screen #2 will cause the following screens to appear: SERVICE TERMINAL 1=RING COUNT Service Terminal Screen Ring Count The ring count designates the number of rings allowed on the phone line prior to answering an incoming SERVICE TERMINAL call from a service terminal.
Programming Master Programming Level Erase History The Erase History option allows a user to erase all events from the history file. This will provide a clean slate in order to use the history file to track future events. Pressing 2 while viewing the History Screen will display the following screen: ERASE HISTORY PROCEED? 1=YES...
Master Programming Level Programming Printer/PC A Printer or a PC can be connected to the control panel. Pressing 3 while viewing the Option Module OPTION MODULES Screen will cause the following screen to appear: 1=ANNUNCIATORS/UDACT 2=ON BOARD DACT PRINTER-PC 3=PRINTER/PC 1=PRINTER NO SU Option Module Screen 2=PRINTER SU...
Programming Maintenance Programming Level 3.6 Maintenance Programming Level To access Maintenance Programming mode, press the Enter key. The LCD will display the following: 1=READ STATUS 2=PROGRAMMING 3=REMOTE DOWNLOAD To enter the Maintenance Programming mode, press 2. The display will read as follows: PROGRAMMING ENTER PASSWORD When the Maintenance level password (default 11111) is entered, the following screen will appear:...
Maintenance Programming Level Programming To view all the events which have occurred in the control panel since the history file was last erased, press 1 while viewing the Events screen. To view only alarms/active events which have occurred, press 2 while viewing the Events screen. To view events other than alarms, press 3.
Section 4: Operating Instructions 4.1 Panel Control Buttons 4.1.1 Acknowledge/Step The first press of the Acknowledge/Step key silences the piezo sounder, changes flashing LEDs to steady and also changes the status field on the LCD display from capital letters to small letters (TROUBL to Troubl). When the piezo is silenced, an acknowledge message is sent to the printer and the history file.
Trouble Operation Operating Instructions The FACP performs the following functions at regular intervals in Normal mode: Monitors AC input voltage and battery voltage Monitors and reports status option cards and control panel Refreshes LCD display and updates time ...
Operating Instructions Supervisory Operation • Communicate the alarm to the Central Station • Alarms latch and are not allowed to clear automatically • Timers for Silence Inhibit, Autosilence and Trouble Reminder are started • Alarms activate the alarm relay • Silenced alarms are resounded •...
Hazard/Tornado Condition Operation Operating Instructions • The alarm relay is not activated • Silenced alarms are not resounded • Timers are not started • Store event in history buffer • Activate appropriate LED on the ANN-LED annunciator (required for this application) Note that, like supervisories, process monitor signals latch, except when programmed for process monitor autoresettable.
Operating Instructions Time Functions: Real-Time Clock System Alarm Verification The control panel may be programmed to perform alarm verification to help eliminate the nuisance of false alarms. Alarm verification applies to smoke detectors only. 4.13 Time Functions: Real-Time Clock The FACP includes a crystal-based clock that provides time of day, date and day of week. Time is displayed as 12 or 24 hour time with month/day/year and is stored in RAM.
Walktest Operating Instructions 4.17.2 Autosilence Timer If Autosilence is selected, the notification appliances, programmed as silenceable, will automatically be silenced after a programmable duration of from 5 to 30 minutes. Pressing the Drill key will restart the timer. Autosilence operation requires the approval of the local Authority Having Jurisdiction.
Operating Instructions Read Status While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of the Program and status change opera- tions). The alarm relay is not activated. NOTE: In Walktest, a NAC open or short fault will not cause the NACs to activate. 4.19 Read Status Read Status functions do not require a password.
Read Status Operating Instructions The operator can press 1 to view the programmed options for NAC 1, 2 to view the programmed options for NAC 2, 3 to view the pro- grammed options for NAC 3, or 4 to view the programmed options for NAC 4. The resulting screens will display the following information: •...
Operating Instructions Read Status Pressing 1 while viewing the Print Screen allows the user to print the History file which will detail all of the system activities since the file was last cleared from memory. Pressing 2 while viewing the Print Screen allows the user to print the Walktest log which will detail all of the system activations during walktest since the log was last cleared.
Read Status Operating Instructions Pressing 1 for Superv Phone Line will cause the following screen to be displayed: SUPERVISE PHONE LINE PHONE LINE 2 This screen indicates whether or not Phone Line 2 is being supervised by the DACT. The factory default setting is Phone Line 2 super- vised (Yes).
Section 5: Central Station Communications The control panel transmits zone and system status reports to Central Stations via the public switched telephone network. Two super- vised telephone line connections are made to interface the control panel to the telephone lines. Two optional 7 foot telephone cords are available for this purpose and can be purchased separately.
Page 107
Transmittal Priorities Central Station Communications The table below shows UL listed receivers which are compatible with the MS-5UD and MS-10UD. Format SIA-DCS-8 SIA-DCS-20 Ademco Contact ID ...
Section 6: Local/Remote Site Upload/Download The control panel may be programmed or interrogated off-site via the public switched telephone network or locally using a USB cable. ® Any personal computer with Windows XP or later, with a 2400 baud compatible modem or USB port and Upload/Download software PS-Tools, available for download from www.firelite.com, may serve as a Service Terminal.
Transferring a Program Local/Remote Site Upload/Download While the control panel is communicating with the remote Service Terminal, one of the DACT’s red phone line active LEDs and the green Kissoff LED will remain on steady. In order to download the panel (whether initiated at the jobsite or remotely), the following must be true: ...
Section 7: Power Supply Calculations 7.1 Overview This section contains instructions and tables for calculating power supply currents in alarm and standby conditions. This is a four-step process, consisting of the following: Calculating the total amount of AC branch circuit current required to operate the system Calculating the power supply load current for non-fire and fire alarm conditions and calculating the secondary (battery) load Calculating the size of batteries required to support the system if an AC power loss occurs Selecting the proper batteries for your system...
Page 111
Calculating the System Current Draw Power Supply Calculations Calculation Column 1 - The primary supply current load that the control panel must support during a non-fire alarm condition, with AC power applied. Calculation Column 2 - The primary supply current load that the control panel must support during a fire alarm condition, with AC power applied.
Power Supply Calculations Calculating the Battery Size 7.4 Calculating the Battery Size Use Table 7.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in AH), required to support the control panel under the loss of AC power. Complete Table 7.4 as follows: Enter the totals from Table 7.3 on page 111, Calculation Columns 2 and 3 where shown Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’...
Appendix A: Ademco Contact ID Format Event Code Descriptions This appendix describes the various Event Codes and their messages which are available for the Ademco Contact ID Format. A.1 Transmission Format Between DACT and Receiver The transmission string for the Ademco Contact ID Format is as follows: where SSSS 18 QXYZ GG CCC SSSS= Four digit Subscriber ID Account Code...
Page 114
Ademco Contact ID Format Event Code Descriptions Ademco Contact ID Typical Printout EVENT MESSAGE 102 Fail to report in EMERG - Fail to Check-in - # Fire Alarm - 110 110 Fire Alarm FIRE - Fire Alarm - # 111 Smoke FIRE - Smoke Detector - # 112 Combustion FIRE - Combustion - #...
Page 115
Ademco Contact ID Typical Printout Ademco Contact ID Format Event Code Descriptions EVENT MESSAGE 158 High temp ALARM - High Temperature - # 159 Low temp ALARM - Low Temperature - # 161 Loss of air flow ALARM - Air Flow - # Fire Supervisory - 200 and 210 200 Fire supervisory SUPER.
Page 116
Ademco Contact ID Format Event Code Descriptions Ademco Contact ID Typical Printout EVENT MESSAGE 350 Communication TROUBLE - Communication Trouble 351 Telco 1 fault TROUBLE - Phone Line #1 352 Telco 2 fault TROUBLE - Phone Line #2 353 Long range radio xmitter fault TROUBLE - Radio Transmitter 354 Fail to communicate TROUBLE - Fail to Communicate...
Appendix B: NFPA Standard-Specific Requirements The MS-5UD/MS-10UD has been designed for use in commercial, industrial and institutional applications and meets the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this Appendix. The minimum system compo- nents required for compliance with the appropriate NFPA standard are listed below: MS-5UD/MS-10UD Control Panel Contains the main control board, cabinet (backbox and door), main power supply and transformer.
Page 119
NFPA Standard-Specific Requirements The following figure illustrates an example of Central Station/Remote Station Reporting using a 411UD. The relay contacts from the MS-5UD/MS-10UD may be used to trip any dialer UL listed for Central Station/Remote Station Reporting Services. 411UD Channel1 Channel 2 Channel 3 Channel 4 (2.2K ELR)
Page 120
NFPA Standard-Specific Requirements Notes: Reference the 411UD Manual for additional information Program the 411UD for slave operation The MS-5UD/MS-10UD must be programmed for AC Loss Reporting Delay This prevents the immediate transmission of a trouble on the loss of AC power All connections between the control panel and the 411UD must be in conduit, less than 20 feet (610 cm) in length, in the same room Any zone of the 411UD can be wired to function as alarm, trouble or supervisory.
Page 121
NFPA Standard-Specific Requirements NFPA 72 Remote Station Protective Signaling System Notes: Cut Jumper JP30 on the MS-5UD/MS-10UD main circuit board to supervise placement of the 4XTMF module. Refer to“4XTMF Transmitter Module Installation” on page 33 for detailed information. RS82 Remote Station Receiver UL listed. Refer to Instruction Manual for Remote Station Receiver Model RS82.
Page 122
NFPA Standard-Specific Requirements NFPA 72 Proprietary Protective Signaling Systems Fire Alarm Control Panel FACP Main Board Form-C Alarm contact programmed to activate on General Alarm. Form-C Trouble contact which will automatically activate on any Trouble condition. Form-C relay contact programmed to activate on Supervisory condition.
Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts NFPA Standard-Specific Requirements B.1 Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value determined by the Transmitter manufacturer.
Appendix C: FACP with Keltron The following figure illustrates the connections between the FACP and Keltron Receiver/Transmitter. CAUTION: POSSIBLE EQUIPMENT DAMAGE FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON MODULES ARE NOT SHOWN IN ACTUAL ORDER. FOLLOW KELTRON MANUAL AND MODULE MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE DAMAGE! IMPORTANT! All connections between the FACP and Keltron modules must be made within 20 feet and enclosed within conduit or equivalently protected against mechanical injury.
Appendix D: Wire Requirements Connecting external system accessories to the main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, gauge and run length for each circuit. Reference the chart below to specify wire requirements and limitations for each circuit.
Appendix E: Default Programming The following table provides a list of the programming options and their factory default settings. Program Option Factory Default Program Option Factory Default Zone #1-10 Enabled ANN-80 Lock Enabled Zone #1-10 Type Pull Station ANN-80 Acknowledge Button Enabled Zone #1-10 PAS Pre-Signal Enabled No Delay ANN-80 Silence Button Enabled...
Appendix F: Canadian Applications F.1 ANN-LED Annunciator Installation for Canadian Applications • The FACP is supplied with a modified dress panel and one ANN-LED annunciator. • When installing and programming the FACP, the Canadian Option must be set to ON prior to any other panel programming (refer to “Canadian Option”...
Page 129
ANN-LED Annunciator Installation for Canadian Applications Canadian Applications To Remote Station Receiver Relay 1 ALARM Relay 2 Relay 3 TROUBLE Relay 4 Relay 5 SUPERVISORY Relay 6 ANN-RLY Non-resettable Aux Power FACP Figure F.2 Alternate Transmission for Alarm, Trouble, and Supervisory Signals Notes: Relays 1 and 2 on the ANN-RLY must be programmed for latching alarm activation.
Index Numerics BB-55F Digital Communicator 19 see also battery box 18 dimensions 10 Zone Main Circuit Board 10 buttons backbox 18 24 Hour Test Time 81 see also control buttons 13 Downloading 108 4XTMF 121 dress panel 12 installation 33 Drill 13 see also Transmitter module 18 5 Zone Main Circuit Board 9...
Page 131
Index Class A 31 coding 64 trouble 17 In-Line resistor current 26 polarity reversal circuit IDC combination circuit 26 enable/disable 64 see also Transmitter module 33 Input Zones 53 End-of-Line resistor 14 Positive Alarm Sequence 59 installation 21 maximum current 14 power 14 CAC-5X 31 silence inhibit 66...
Page 132
Index see also Ringer Equivalence Number 19 operation 33 Reporting Enable 76 specifications 33 Reset 13 Transmitter option module resettable power 12 placement supervision 32 current 27 Trouble 97 maximum current 14 trouble reverse polarity circuit piezo pulse rate 17 see also Transmitter module 18 trouble call limit 50 Ring Count 91...
MS-5UD-3, MS-5UD-3E, MS-5UD-7, MS-5UD-7E, MS-5UD-7C, MS-10UD-3, MS-10UD-3E, MS-10UD-7, MS-10UD-7E, MS-10UD-7C Fire Alarm Control Panel Operating Instructions NORMAL - Only AC POWER is illuminated green. PANEL KEY - The key to open the panel can be found at the following All other indicators are off. LCD display will read SYSTEM ALL location: NORMAL.
Page 135
Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan.
Page 136
One Fire-Lite Place, Northford, CT 06472-1601 USA USA - Phone: (203) 484-7161 Canada - Phone: (905) 856-8733 www.firelite.com...