Figure 14
Cisco ASR 1006 Router DC Input Power Cable Lug
Note
To avoid hazardous conditions, all components in the area where DC input power is accessible must be
properly insulated. Therefore, before installing the DC cable lugs, be sure to insulate the lugs according to the
manufacturer's instructions.
Before you connect DC-input power, you must install the DC power ground leads to the DC power supply.
Caution
Obtain these necessary tools and equipment:
• Number 2 Phillips screwdriver
• A 3/16-inch flat-blade screwdriver
Installing the Cisco ASR 1006 Router DC Ground Lugs
To install the grounding lugs on the DC power supply, follow these instructions.
DC power supply grounding stud.
Make certain that the chassis ground is connected before you begin installing the DC power supply.
Step 1
Locate the stud on the DC power supply for the GND connection which must be connected first and follow these steps:
Step 2
a. Using the grounding lug, replace the washers and Kepnut screw in the following order.
- Flat washer
- Grounding cable lug
- Kepnut screw
b. Tighten the Kepnut screws on the power supply studs.
Tighten the Kepnut screw
Step 3
20+/–2 in-lbs / 2 per.) to complete the installation.
See
Figure 15
if you are using the ASR1006-PWR-DC power supply.
End View
Ø 0.267
0.48
2 holes
0.25
0.63
0.08
(use the screwdriver to tighten the ground screw in the terminal block to a torque of
All measurements in inches
2.24
Crimp area
0.37
Figure 12
(item #6) shows the location of the
19