R G M 4 0 M E T E R Q U I C K S TA R T G U I D E — Safety warnings Installation of the RGM40 meter must be Do not use the meter or any I/O device for performed only by qualified personnel who...
E L E C T R I C A L I N S TA L L AT I O N — Electrical installation — Select diagram for your IMPORTANT! 02 Wye/Delta*, 4-wire, no PTs, 3 CTs application; see user manual For Delta connections, do not exceed 480 V —...
R G M 4 0 M E T E R Q U I C K S TA R T G U I D E — Program settings Program settings using the faceplate buttons: 6. Press the ENTER button to go to the CT (MENU, ENTER, DOWN ARROW, RIGHT ARROW) scaling setting screen (CT-S).
Page 5
P R O G R A M S E T T I N G S 10. Press the ENTER button to go to the 13. Press the ENTER button to go to the meter connection setting screen (Cnct). The current protocol setting screen (Prot).
Page 6
10,000/5 amps: Set the Ct-n value as 1000, 345000/69 volts: Set the Pt-n value as 0345, Ct-S value as 10. Pt-d value as 69, Pt-S value as 1000. For additional programming instructions for the faceplate buttons, see chapter 5 in the RGM40 meter user manual.
Page 8
— — ABB Inc. has made every attempt to ensure disclaimed. ABB Inc. may change or modify ABB Inc. the accuracy and reliability of the contents the contents at any time, without prior 305 Gregson Drive of this document. However, all content is notice.