Wall Mount refrigerant pipe system. Refer to the figure for maximum length and elevation of piping. Outdoor unit Indoor unit Table 6: Single Zone Extended Pipe Refrigerant Piping System Limitations LS243HLV LS303HLV LS363HLV Pipe Length Longest total equivalent piping length (ELF = Equivalent Length of 164.0...
Always follow local codes when selecting and installing copper pipe and piping system components. Approved piping for use with LG Single Zone products will be marked “R410 RATED” along the length of the pipe. Piping wall thickness must meet local code requirements and be approved for a maximum operating pressure of 551 psi. When bending piping, try to keep the number of bends to a minimum, and use the largest radii possible to reduce the equivalent length of installed piping;...
COPPER EXPANSION AND CONTRACTION Copper Expansion and Contraction Under normal operating conditions, the vapor pipe temperature of 1. From Table 10 find the row corresponding with the actual length a Duct Free System can vary as much as 280°F. With this large of the straight pipe segment.
PIPING HANDLING Piping Materials and Handling Keep Pipes Capped While Storing. Pipes used for the refrigerant piping system must include the specified thickness, and the interior must be clean. While handling and storing, do not bend or damage the pipes, and take care not to contaminate the interior with dust, moisture, etc.
Failure to do so will cause significant performance degradation. Proper leak checks must be performed. Using isolation valves does not automatically void any LG product warranty, however, a limited warranty will be voided in whole or part if any field supplied accessory fail in any way that causes product failure.
Page 27
REFRIGERANT SYSTEM ENGINEERING Figure 21: Installing Piping Above and Below an Obstacle. Obstacles When an obstacle, such as an I-beam or concrete T, is in the path of the planned refrigerant pipe run, it is best practice to route the MINIMUM pipe over the obstacle.
Page 28
Pipe Sleeves at Penetrations LG requires that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the sleeve.
FLARING AND BRAZING PROCEDURES Flaring and Brazing Procedures One of the main causes of refrigerant leaks is a defective connection. For LG HVAC systems, the installer needs to know how perform both flared and brazed connections successfully. • During installation, it is imperative to keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust.
No cables were spliced and no wire caps are present. LG-supplied cable was used between the indoor unit and its zone controller. No cables were spliced and no wire caps are present. Appropriate crimping tool was used to attach ring or spade terminals at all power wiring and control cable terminations.
Page 66
ISO 9001: 2008 LG ELECTRONICS INC. For further technical materials such as submittals, engineering manuals, service manuals, and catalogs, visit www.lghvac.com. LG Customer Information Center, Commercial Products 1-888-865-3026 USA Follow the prompts for commercial A/C products. LG Electronics, U.S.A., Inc.