hit counter script

Power Connection - GE Zoneline 6100 Series Technical Service Manual

Hide thumbs Also See for Zoneline 6100 Series:
Table of Contents

Advertisement

Power Connection

230/208-Volt Line Cord Connected Units
Line cord kits consist of a self-aligning nine-
pin molded connector, that plugs into a mating
connector on the Zoneline chassis, and an insulated
line cord with an electrical plug on the end. The
confi guration of the electrical plug conforms to NEC
standards for the circuit amperage, and the position
of the wires in the nine-pin connector determines
the heater wattage and current requirements when
it is plugged into the Zoneline chassis.
The power connection kit is selected by the
amperage of the circuit, where it will be installed.
Each line cord kit has an integral Leakage Current
Detection and Interruption (LCDI) or Arc Fault
Current Interrupter (AFCI) device as required by the
National Electrical Code (NEC) and Underwriters
Laboratory (UL) for line cord connected air
conditioners manufactured on or after August 1,
2004. The line cord power connection kits are shown
in the table below.
230/208-Volt Line Cord Connected Units
Line Cord
Electric Heat
Kit
(BTU/hr)
RAK3153A
8100/7900
RAK3203A
11200/10900
RAK3303*
16000/15400
*Not approved for use on 7000 BTU models.
Electric heat amps include electric heater and fan motor current draw.
230/208-Volt ― Permanently Connected Units
Permanently connected units do not require
the LCDI or AFCI device. Permanent connection
is usually made through the use of a sub-base.
Each 230/208-volt sub-base consists of a sub-
base with an appropriate receptacle for minimum
circuit amperage, a chaseway to route the power
connector from the sub-base to the chassis,
wiring to connect the sub-base to building wiring,
and a short line cord with a self-aligning nine-pin
connector to connect to the chassis and plug into
the receptacle in the sub-base.
230/208-Volt Sub-Base Connected Units
Sub-Base
Electric Heat
(BTU/hr)
RAK204D15P
8100/7900
RAK204D20P
11200/10900
RAK204D30P*
16000/15400
*Not approved for use on 7000 BTU models.
Electric heat amps include electric heater and fan motor current draw.
Electric
Electric
Min. Circuit
Heater
Heat
Protection
(KW)
(Amps)
(Amps)
2.40/2.32
11.0/11.6
15
3.30/3.20
15.1/16.0
20
4.70/4.53
21.2/22.4
30
Electric
Electric
Min. Circuit
Heater
Heat
Protection
(KW)
(Amps)
(Amps)
2.40/2.32
11.0/11.6
15
3.30/3.20
15.1/16.0
20
4.70/4.53
21.2/22.4
30
Permanent, or direct-wired, installation of a
230/208-volt unit requires a junction box kit,
RAK4002A, that attaches to the chassis to form
an enclosed junction box. The short sub-base line
cord may not be used without the sub-base. For
6100 Series 230/208-volt units, where a permanent
installation using fl exible conduit is desired, the
RAK4002A forms an enclosed junction box on the
chassis.
The RAK4002A has a 7/8-in. diameter hole to allow
conduit to be connected to the junction box. A
line cord kit (See
Receptacles/Sub-Bases
purchased and modifi ed to allow direct connection
to the building wiring.
The line cord kit should be cut about 8 inches away
from the 9-pin connector. Strip the insulation off
the end of each conductor to expose wires for fi eld
connection. These wires are then connected to the
building wiring by fi eld-supplied connectors.
230/208-Volt ― Direct Connection Kits
Branch Circuit and Unit
Amperage Rating
15
20
30
*Not approved for use on 7000 BTU models.
– 16 –
) must be
Power Supply
Power Supply
Accessory
Kit
RAK4002A
RAK4157
RAK4002A
RAK4207
RAK4002A
RAK4307*
(Continued next page)

Advertisement

Table of Contents
loading

Table of Contents