8-1. Indoor Unit

8-1-1. Test Run Setup on Remote Controller
<Wired remote controller>
1. Push [TIME] and [▲] buttons and hold for more than 10 seconds. [TEST] is displayed on the display screen,
and mode selection in Test mode is allowed.
2. Push [ON/OFF] button to start the air conditioner.
3. Using [MENU] button to change the cooling or heating mode
• Do not use [MENU] button to change modes other than cooling and heating modes.
• Under heating and cooling operations, a command for fixing test running frequency will be output.
• The temperature cannot be adjusted during the test run, but the air volume can be selected.
• Fault detection is operating normally, but do not use this function in "test run" as this will cause load on the
equipment.
4. Push [ON/OFF] button to stop the operation after the test run.
5. Push [TIME] button to clear the TEST mode, [TEST] display in the display part disappears and the status
returns to the normal stop status.
(To prevent a continuous test run operation, it will be automatically shut down after 60 minutes by the remote
controller.)

8. SETUP AT LOCAL SITE AND OTHERS

– 58 –