Indoor Unit Condensed Water
Drainage
The indoor unit condensed water drainage is
fundamental for the success of the installation.
1
Place the drain hose below the piping, taking
care not to create siphons.
2
The drain hose must slant downwards to aid
drainage.
3
Do not bend the drain hose or leave it protruding
or twisted and do not put the end of it in water.
If an extension is connected to the drain hose,
ensure that it is lagged when it passes into the
indoor unit.
4
If the piping is installed to the right, the pipes,
power cable and drain hose must be lagged
and secured onto the rear of the unit with a pipe
connection.
1) Insert the pipe connection into the relative
slot.
2) Press to join the pipe connection to the base.
YES
NO
NO

Installation of the Indoor Unit

After having connected the pipe according to the
instructions, install the connection cables. Now install
the drain pipe. After connection, lag the pipe, cables
and drain pipe with the insulating material.
1
Arrange the pipes, cables and drain hose well.
2
Lag the pipe joints with insulating material,
securing it with vinyl tape.
Covered by vinyl tape
Connection cable
Connection cable 1
(for heat-pump)
Probe cable
(for heat-pump)
3
Run the bound pipe, cables and drain pipe
through the wall hole and mount the indoor
unit onto the upper part of the mounting plate
securely.
4
Press and push the lower part of the indoor unit
tightly against the mounting plate.
Mounting plate
Refrigerant pipe
Insulation sleeve
Refrigerant pipe
Condensed water
drain pipe
EN