4
Timer operation
Select a timer type from the following three: (Max. 168 hours)
OFF timer :
Stops running after the specifi ed period.
Repeat-OFF timer :
Stops running after the specifi ed period every time you use the air conditioner.
ON timer :
Starts running after the specifi ed period.
■
Setting the timer
1
3
1
Push the
button.
Each time you push the button, the timer mode
and indication change in the following order
Off
Off
On
(Off timer)
(Repeat Off timer)
(On timer)
No indication (Timer
function is deactivated)
•
and the time indicator blink.
2
Push the
buttons to set the period of
time until the timer actions.
• The time setting increases in 0.5-hour
(30- minute) increments each time you push
The setting increases in 1-hour increments if
it is over 1d (24 hours). The maximum is 7d
(168 hours). On the remote controller, settings
between 0.5h and 23.5h (*1) are displayed as
is. If it is over 24 hours (*2), the days and hours
appear.
• The time setting decreases in 0.5-hour
(30- minute) decrements (0.5 hours to 23.5
hours) or 1-hour decrements (24 hours to 168
hours) each time you push
.
Example of remote controller display
• 23.5 hours (*
1
)
2
• 34 hours (*2)
indicates 1 day
(24 hours).
indicates 10 hours.
(Total: 34 hours)
3
Push the
button.
•
disappears, the time indication is
displayed, and
or
display fl ashes.
(When using the ON timer, all indications other
than the time and
turn off.)
■
Cancelling the timer
.
1
Push the
button.
The timer indicator disappears.
NOTE
• When using Repeat OFF timer, pushing the
button after stopping by the timer starts running again
and the timer will stop the running again after the
specifi ed period.
• When using OFF timer, the timer indication temporarily
disappears for about 5 seconds by pushing the
button. This occurs due to the processing in the remote
controller, and is not a malfunction.
5
Installation
Ask the installation company about important points of
general instruction.
■
Location
• Avoid installing near machines emitting high
frequency waves.
• Not suitable for chemical plants such as liquefi ed
carbon dioxide refrigerant plants.
• Do not install the air conditioner in locations where
iron or other metal dust is present. If iron or other
metal dust adheres to or collects on the interior of the
air conditioner, it may spontaneously combust and
start a fi re.
• A failure may occur in certain locations such as the
following:
• Areas with large amount of oil droplets (including
machine oil) or vapors.
• Salty areas near oceans, etc.
• Hot springs emitting sulfi dizing gas, etc.
• Heavily acidic or alkaline places.
Special maintenance or parts are required for use
Days
Hours
in the above places. For details, contact the dealer
where you purchased the product.
• Leave an enough space around the air intake and
discharge of the outdoor unit so that the ventilation is
not restricted.
• Avoid places where strong wind may blow against
the air intake and discharge of the outdoor unit.
• Attach a snow stand, snow hood, etc. to the outdoor
unit for use in snowfall areas. For details, contact the
dealer where you purchased the product.
• Make sure drain water from the outdoor unit is
emitted into places with good drainage.
• Make sure the air fi lter is attached to the indoor unit.
If not, dust may accumulate on the heat exchanger
or other parts in the air conditioner and cause a
water leak.
• Keep a distance of at least 1 m between the air
conditioner/remote controller and a TV or radio.
Failure to observe this precaution may cause visual
disturbance or noise.
• Leave a distance of at least 1.5 m between the air
discharge and a fi re alarm. If this precaution is not
observed, the alarm may not work properly or detect
fi re in case of fi re.
– 8 –
■
Be careful of operation sounds
• Locate the unit in a place secure enough so that the
sounds and vibrations do not increase.
• If something is placed near the air discharge of the
outdoor unit, noise may increase.
• Be careful not to disturb your neighbors with cool/
warm air or noise coming from the air discharge of
the outdoor unit.