hit counter script

Cisco VG224 - Analog Phone Gateway Hardware Installation Manual page 44

Voice gateway
Hide thumbs Also See for VG224 - Analog Phone Gateway:
Table of Contents

Advertisement

Installing the Ground Connection
For EN/IEC 60950-compliant grounding, use size AWG 18 (1 mm
appropriate user-supplied ring terminal.
To ground the chassis, follow this procedure:
Locate a suitable ground location.
Step 1
Use a multimeter to measure the resistance between various ground locations, such as the following:
Tip
Between the ground of a junction box (outlet) and the ground of a power tap
Between the ground of a junction box and a metal water pipe
Between the Cisco VG224 voice gateway chassis and the ground of a power tap
Between the Cisco VG224 voice gateway chassis and the ground of a junction box
A good ground connection should read between 0.0 and 0.5 ohms.
Strip one end of the ground wire to the length required for the ground lug or terminal.
Step 2
For the NEBS ground lug—approximately 0.75 in. (20 mm)
For user-provided ring terminal—as required
Crimp the ground wire to the ground lug or ring terminal, using a crimp tool of the appropriate size. (See
Step 3
Figure
Figure 3-9
Attach the ground lug or ring terminal to the chassis as shown in
Step 4
ground lug, use the two screws with captive locking washers provided. For a ring terminal, use one of
the screws provided. Use a number 2 Phillips screwdriver, and tighten the screws to a torque of 8 to 10
in-lb (0.9 to 1.1 N-m).
Note
You can orient the crimped end of the ground lug in either direction (right or left).
Connect the other end of the ground wire to a grounding point at your site.
Step 5
Cisco VG224 Voice Gateway Hardware Installation Guide
3-12
3-9.)
Crimping a Ground Lug onto the Ground Wire
Chapter 3
Installing the Cisco VG224 Voice Gateway
2
) or larger wire and an
Figure 3-10
or
Figure
3-11. For the
OL-5006-04

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents