INSTALLATION MANUAL Free Joint Fixed MH18VF1X MH040FX MH19VF1X MH050FX MH060FX MH070FX MH080FX Free Joint Multi & Multi-Split Type Room Air Conditioner (Cooling and Heating) F I P D G DB98-28896A(2)
Store the operation and installation manual in a safe location and remember to hand it over to the new owner if the air conditioner is sold or transferred. This manual explains how to install an indoor unit with a split system with two SAMSUNG units. The use of other types of ...
PREPARING THE INSTALLATION Deciding on Where to Install the Air Conditioner When deciding on the location of the air conditioner with the owner, the following restrictions must be taken into account. General Do NOT install the air conditioner in a location where it will come into contact with the following elements: Combustible gases ...
Page 5
PREPARING THE INSTALLATION MH040FXA2B Piping outside diameter Power supply Outside diameter Indoor unit Outdoor unit Unit Ø, V, Hz Liquid MH040FX 1,220-240, 50 020/023/026/035 1/4" 3/8" 020/023/026/035 A2B outdoor unit cannot be connected to the following indoor unit combination. MH040FX ...
Page 6
PREPARING THE INSTALLATION Deciding on Where to Install the Air Conditioner (Continued) MH050FXA2B Piping outside diameter Power supply Outside diameter Indoor unit Outdoor unit Unit Ø, V, Hz Liquid 3/8" 020/023/026/035 MH050FX 1,220-240, 50 020/023/026/035/052 1/4" 1/2" 052 A2B outdoor unit cannot be connected to the following indoor unit combination.
Page 7
PREPARING THE INSTALLATION MH060FXA3B Piping outside diameter Power supply Outside diameter Indoor unit Outdoor unit Unit Ø, V, Hz Liquid 3/8" 020/023/026/030/035 MH060FX 1,220-240, 50 020/023/026/030/035/052 1/4" 1/2" 052 200 mm or more 100 mm 160 mm or more or more CAUTION: (h) (H)
Page 8
PREPARING THE INSTALLATION Deciding on Where to Install the Air Conditioner (Continued) MH070FXA4B / MH080FXA4B Piping outside diameter Power supply Outside diameter Indoor unit Outdoor unit Unit Ø, V, Hz Liquid MH070FXA4B 1/4" 3/8" 020/023/026/030/035 1,220-240, 50 020/023/026/030/035/052 1/4" 1/2"...
Page 9
PREPARING THE INSTALLATION Piping outside diameter MH18VF1X/MH19VF1X Power supply Outer Diameter Indoor unit Outdoor unit Unit Ø, V, Hz Liquid MH18VF1-09 MH18VF1X MH18VF1-09 MH19VF1-07 1/4" 3/8" MH19VF1-07 1,220-240~, 50 MH19VF1X MH19VF1-12 MH19VF1-12 Respect the clearances and maximum lengths indicated in the diagram below when installing the unit. CAUTION: B-unit MH18VF1-09...
Page 10
PREPARING THE INSTALLATION Deciding on Where to Install the Air Conditioner (Continued) Space Requirements for Outdoor Unit When installing 1 outdoor unit Unit : mm W hen the air outlet is opposite the wall W hen the air outlet is towards the wall ...
Page 11
PREPARING THE INSTALLATION When installing more than 1 outdoor unit Unit : mm When the air outlet is towards the wall 300 or more 600 or more 600 or more 600 or more When 3 sides of the outdoor unit are blocked by the wall 600 or more 600 or more ...
PREPARING THE INSTALLATION Air Conditioner and Accessories The following accessories are supplied with the air conditioner. Accessories in the Outdoor Unit Case MH040FXA2B/MH050FXA2B/MH060FXA3B/MH18VF1X/MH19VF1X 3-wire 2-wire Drain Plug Transmitter power Energy Label Power Cable Assembly Cable cable (option) (option) Rubber Leg Flare Bolt Installation Manual (Nut 1/2”, Bolt 3//8”)
INSTALLING THE INDOOR UNIT Installing and Connecting the Drain Hose of the Outdoor Unit While heating, ice may accumulate. During the process of defrosting, check if condensation draining is adequate. For adequate draining, do the following: Insert the drain plug into the drain hole on the underside of the outdoor unit. Connect the drain hose to the drain plug.
INSTALLING THE INDOOR UNIT Cutting/Extending the Piping Make sure that you have the required tools available (pipe cutter, reamer, flaring tool and pipe holder). If you wish to shorten the piping, cut it using a pipe cutter, taking care to ensure that the cut edge remains at a 90°...
INSTALLING THE OUTDOOR UNIT Connecting the Cables to the Outdoor Unit When you install the unit, make first refrigerant connections and then elec- trical connections.Connect the air conditioner to grounding system before performing the electrical connection.If unit is uninstalled first disconnect electrical cables, then refrigerant connections.
Page 16
INSTALLING THE OUTDOOR UNIT Connecting the Cables to the Outdoor Unit(Continued) MH060FXA3B B-unit C-unit A-unit Indoor unit 1(L) 2(N) 1(L) 2(N) 1(L) 2(N) Assembly cable F1 F2 F1 F2 F1 F2 Earth Earth Earth terminal terminal terminal F1 F2 F1 F2 F1 F2 Earth Earth...
Page 17
INSTALLING THE OUTDOOR UNIT MH070FXA4B / MH080FXA4B A-unit B-unit Indoor unit C-unit D-unit 1(L) 2(N) 1(L) 2(N) 1(L) 2(N) 1(L) 2(N) Assembly cable F1 F2 F1 F2 F1 F2 F1 F2 Earth Earth Earth Earth terminal terminal terminal terminal F1 F2 F1 F2 F1 F2 F1 F2...
Page 18
INSTALLING THE OUTDOOR UNIT Connecting the Cables to the Outdoor Unit (Continued) Preparation of cables for outdoor unit terminal block Main power supply cable: L(mm) Cable of indoor unit Main Power L(mm) Power cable to indoor units: L(mm) Cable of Remark indoor unit...
INSTALLING THE OUTDOOR UNIT Transmitter Installation (Optional) MH040FXA2B/MH18VF1X/MH19VF1X Accessories (Transmitter: MIM-B13) Transmitter Transmitter power Transmitter Installation Manual Case Cable-tie cable communication cable Bolts spec. 7seg. LED Fix the case at with bolts on the side of the control box in the outdoor unit. Display side (See the picture) Attach the transmitter PCB to the case in the control box in the outdoor...
Page 20
INSTALLING THE OUTDOOR UNIT Transmitter Installation (Optional) (Continued) MH050FXA2B/MH060FXA3B/MH070FXA4B / MH080FXA4B Accessories (Transmitter: MIM-B13) Transmitter Transmitter power Transmitter Installation Manual Case Cable-tie cable communication cable MH050FXA2B Terminal side Transmitter 7seg. LED Display side Bolts spec. Fix the case with bolts on the control box in the outdoor unit. (See the picture) Attach the transmitter PCB to the case in the control box in the outdoor unit, then connect the power and the communication cable between the...
Page 21
INSTALLING THE OUTDOOR UNIT Transmitter power cable CN01 (Accessory in the outdoor unit) (Whit) Transmitter CN03 (Blue) CN01 MH040FXA2B MH050FXA2B/MH060FXA3B (Whit) MH18VF1X/MH19VF1X MH070FXA4B/MH080FXA4B Center Controller Outdoor unit PCB Transmitter communication One housing is used for connection cable (Accessory in the although there are 2 housings on the transmitter) communication cable.
INSTALLING THE OUTDOOR UNIT Checking Correct Earthing If the power distribution circuit does not have an earth or the earth does not comply with specifications, an earthing electrode must be installed. The corresponding accessories are not supplied with the air conditioner. Select an earthing electrode that complies with the specifications given in the illustration opposite.
COMPLETING THE INSTALLATION Connecting Up and Purging the Circuit The outdoor unit is loaded with sufficient R410A refrigerant.Do not vent R-410A into atmosphere: it is a fluorinated greenhouse gas, covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 1975. You should purge the air in the indoor unit and in the pipe.
COMPLETING THE INSTALLATION Connecting Up and Purging the Circuit(Cont.) MH060FXA3B/MH070FXA4B / MH080FXA4B Check the piping connections. Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port (5/8” Packed valve) as shown at the figure (Value stem: 1/2”...
COMPLETING THE INSTALLATION Important information regulation regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere. Refrigerant type GWP value CAUTION R410A 1975 Inform user if system contains 3 kg or more of fluorinated greenhouse gases. In this ...
COMPLETING THE INSTALLATION Pipe Installation with Indoor Units MH070FXA4B / MH080FXA4AB Follow different orders depending on the capacity of indoor units. MH020/023/026/030/035FEA OUTDOOR UNIT Install pipes between indoor and outdoor units orderly as[AB CD]. MH052FEA Install pipes between indoor and outdoor units orderly as [ CD]. Examples ...
COMPLETING THE INSTALLATION Switch Setting and Testing Operation To complete the installation, perform the following checks and tests to ensure that the air conditioner is operating correctly. Step 1 Review all the following elements in the installation: Installation site strength ...
Page 28
COMPLETING THE INSTALLATION Switch Setting and Testing Operation(Cont.) TO SET ADDRESSING MANUALLY BY TYPE PICTURE MODEL ROTARY SWITCH “SW02” Same for: MH020FV(N)EA MH023FBEA MH026FB(V/N)EA MH035FB(V/N)EA MH052FB(V/N)EA MH026FKEA 1 WAY CASSETTE MH035FKEA MH030FMEA MINI 4 WAY MH035FMEA MH052FMEA MH026FEEA SLIM DUCT MH035FEEA MSP-DUCT MH052FUEA...
Page 29
COMPLETING THE INSTALLATION ROTARY SWITCH “SW02” POSITION ACCORDING TO REFRIGERANT CIRCUIT CONNECTED ( 0=A; 1=B; 2=C; 3=D ) OUTDOOR UNIT Indoor Unit SW02 A unit B unit Indoor Unit OUTDOOR UNIT SW02 A unit B unit C unit Indoor Unit SW02 OUTDOOR UNIT A unit...
Page 30
COMPLETING THE INSTALLATION Switch Setting and Testing Operation (Cont.) It could take maximum 60 minutes to operate for the protection of the compressor if the outdoor temperature is below -5°C. Ampere Limit Setting & Changing Procedure WARNING Do not adjust the “Ampere Limit Switch”, if it’s not necessary: before modifying it, evaluate the total number of electric and electronics loads consumption and use “Ampere limits switch”...
Page 31
COMPLETING THE INSTALLATION Pipe Checking Operation (Auto Addressing Mode) Automated checking of pipe connection (Auto addressing option) Turn on the outdoor unit and wait for one minute. During these 60 seconds, the left dispaly DIS01 will show sequentially 00-01-02-03-...15-00. E199 is showed on the display PCB of outdoor unit. - It means you didn’t do “Pipe check operation“...
Page 32
COMPLETING THE INSTALLATION Switch Setting and Testing Operation (Cont.) Settings of PCB Display of the Outdoor unit Key Options of PCB Display - K1 : pipe checking operation button - K2 : Function button - K3 : Reset button - K4 : View mode change button SW02 SW01 Push...
COMPLETING THE INSTALLATION Troubleshooting The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for Authorise Service Center. The error indicated on the PCB display of outdoor unit DISPLAY EXPLANATION (The error indicated on the PCB display of outdoor unit) REMARK Check electrical connection Communiaction error(indoor unable to receive data)
COMPLETING THE INSTALLATION Troubleshooting (Cont.) The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for Authorise Service Center. The error indicated on the PCB display of outdoor unit DISPLAY EXPLANATION (The error indicated on the PCB display of outdoor unit) REMARK check pipe lenght, indoor Outdoor unit freezing(Compressor stop)