Error
Error Type
No.
01
Indoor unit air sensor error
02
Indoor unit pipe inlet sensor error
06
Indoor unit pipe outlet sensor error
I Error diagnosis and countermeasure flow chart
Is sensor properly
connected to PCB?
Yes
Is the resistance value
of sensor normal?*
Yes
Change the PCB
** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs
Refer: Resistance value maybe change according to temperature of temp sensor,
It shows according to criteria of current temperature(±5% margin) ➔ Normal
Air temp sensor: 10°C(50°F) = 20.7 kΩ, 25°C(76°F) = 10 kΩ, 50°C(122°F) = 3.4 kΩ
Pipe temp sensor: 10°C(50°F) = 10 kΩ, 25°C(76°F) = 5 kΩ, 50°C(122°F) = 1.8 kΩ
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Indoor unit sensor is
No
Connect properly to PCB
No
Change the sensor
- 77 -
Error Point
1. Indoor unit PCB wrong connection
2. Indoor unit PCB failure
open/short
3. Sensor problem (main reason)
CN-ROOM : Indoor air temp sensor
CN-PIPE2 : Pipe outlet temp sensor
CN-PIPE1 : Pipe inlet temp sensor
Measure the resistance of outlet pipe temp sensor.
Troubleshooting Guide
Main Reasons