Detailed Commissioning; System Handover; Shutting Down/Switching Off - Bosch RC35 Installation And Service Instructions Manual

Logamatic ems programming unit room controller
Table of Contents

Advertisement

Commissioning
5

5.4 Detailed commissioning

B Check whether the basic settings in the SERVICE\SETTINGS menu match the heating system.
B Note down modified settings if needed.

5.5 System handover

B Ensure that no temperature limits for central heating and DHW have been set at the boiler
programming unit, so DHW and flow temperature can be regulated via the RC35 programming
unit.
B Explain to the customer how the appliance works and how to operate it.
B Inform customer about the selected settings.
We recommend that you hand over these installation and maintenance instructions to
the customer for safe keeping at the heating system.

5.6 Shutting down/switching off

The RC35 programming unit is powered via the heating system and remains permanently on. The
heating system is only switched off for maintenance work, for example.
B For switching the heating system on or off: switch the On/Off switch on the boiler programming
unit to position 1 (ON) or 0 (OFF).
B With hybrid systems with HM10: shut off power to the hybrid module.
After shutting down or in the event of a power failure, the date and time are retained for
up to 8 hours. All other settings are retained permanently.
24
Logamatic EMS – 6 720 801 387 (2011/05)