6.4 Heating circuit data
This chapter explains the settings for all heating circuits using heating circuit 1 as an example.
B Turn the
rotary selector to the left until heating circuit 1 is selected.
B Press
to select heating circuit 1.
The menu for SETTING\HEATING CIRCUIT 1 is opened.
Menu item
Do you want to enable
heating circuit 1?
Which programming unit
is assigned to heating
circuit 1?
How should heating
circuit 1 be controlled?
Which heating system
does heating circuit 1
have?
Table 14 Navigator for service menu of SETTING\HEATING CIRCUIT 1
Logamatic EMS – 6 720 801 387 (2011/05)
System settings (Service menu – Settings)
Input range
Yes, No
RC2x/RC20/RF,
RC35, none
Outside
temperature
compensated,
room temperature
compensated
Radiator,
convector, floor
Standard
setting
Other information
Yes
RC35
See page 35. With UBA1.xyou can
not select RC2x.
With selection of"None"the control
mode is switched to"Outside
temperature" compensatedand it is
hidden.
Outside
"Room temperature compensated"
temperature
can only be set if RC2x or RC35 has
compen-
been allocated. If "room temperature
sated
compensated" is selected, room
flow is used.
Radiator
With HK1 "underfloor" setting only if
it is a case of a oil/gas condensing
boiler. Additional heating circuits
can then be installed.
Use a safety thermostat with
underfloor heating systems.
SERVICE\SETTINGS
plant data
boiler data
domestic hot water
B
heating circuit 1
6
31