Table 4: 208-230V, 60Hz, 1-Phase Single-Zone Mega Inverter System Electrical Data Table.
Model Number Nominal Tons
LS090HEV1
3/4
LS120HEV1
1
LS180HEV1
1-1/2
LS240HEV1
2
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Table 5: 115V, 60Hz, 1-Phase Single Zone Single-Zone Mega 115V System Electrical Data Table.
Model Number Nominal Tons
LS090HXV
3/4
LS120HXV
1
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Compressor
Compressor(A)
Qty
Cool/Heat
1
7.0/7.0
1
7.0/7.0
1
8.81/8.61
1
10.72/10.28
Compressor
Compressor(A)
Qty
Cool/Heat
1
10/10
1
10/10
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.

ELECTRICAL DATA

Mega Inverter and Mega 115V Outdoor Units
Fan Qty
ODU Fan (A)
IDU Fan (A)
1
0.5
1
0.5
1
0.4
1
0.4
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
Fan Qty
ODU Fan(A)
IDU Fan (A)
1
0.4
1
0.4
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
MCA(A)
MOP(A)
0.5
10
0.5
10
0.4
12
0.4
15
MCA(A)
MOP(A)
0.5
13.5
0.5
13.5
PRODUCT DATA | 13
15
15
20
20
20