2.3

Technical Data

Type rating
PROTECT D.1000
PROTECT D.1500
PROTECT D.2000
PROTECT D.3000
UPS input
Nominal input voltage
Rectifier voltage range
(without battery operation
100% load, pf = 0.9 lag.)
Rectifier voltage range
(without battery operation
100% load, pf = 0.8 lag.)
Rectifier voltage range
(without battery operation
100% load, pf = 0.7 lag.)
Bypass voltage range
Frequency
Frequency tolerance range
Charging rate at full load and battery charging (max.)
PROTECT D.1000
PROTECT D.1500
PROTECT D.2000
PROTECT D.3000
Circuit feedback factor
1000 VA (pf = 0.9 lag.)
900 W
1500 VA (pf = 0.9 lag.)
1350 W
2000 VA (pf = 0.9 lag.)
1800 W
3000 VA (pf = 0.9 lag.)
2700 W
1ph~ / N / PE
230 Vac
190 Vac – 276 Vac
(PROTECT D.1000 & D.1500)
200 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
180 Vac – 276 Vac
(PROTECT D.1000 & D.1500)
190 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
160 Vac – 276 Vac
(PROTECT D.1000 & D.1500)
180 Vac – 276 Vac
(PROTECT D.2000 & D.3000)
195.5 Vac – 253 Vac
50 Hz / 60 Hz
(autom. recognition or manual)
± 5 Hz
4.8 A
7.2 A
9.6 A
13.7 A
 > 0.99
11
EN