Weight, approx:
Clearance Requirement:
Power Source:
Power Requirements:
Input Power Connector:
Circuit Breakers:
Fuses:
Operating Environment:
Shock:
Vibration:
Heat Transfer to Room:
Table 30-1 Ambient Temperature and Humidity Limits
Conditions
Operating Temperature
Recommended
Short-Term Temperature
Operating Relative Humidity
Short-Term Relative Humidity
1. Room temperature refers to conditions at a location 5 feet above the floor and 15 inches in front of the equipment.
Cisco BPX 8600 Series Installation and Configuration
30-2
73 lb. (33.2 kg.) empty BPX shelf, w/fans but no PS.
6 lb. (2.7 kg.) each card.
18 lb. (8.2 kg.) empty AC Power Supply Tray.
16 lb. (7.3 kg.) each AC Power Supply.
2 lb. (0.9 kg.) each DC Power Entry module.
At least 30 inches front and rear clearance; nominal 12 inch side
clearance.
AC system: 180 – 264 VAC, 47 to 63 Hz.
DC system: –42 to –56 VDC.
AC BPX-15: 13 A at 180 VAC (2300 VA).
DC BPX-15: 40 A at –42 VDC (1680W).
AC: 3-conductor IEC receptacle. 8 feet (2.4 m.) power cord
supplied.
DC: 3 Ring lug screw terminal connectors.
AC: 15 A on AC power supply assembly.
DC: 40A on power entry module.
Individual Backplane Card slot fuses, F1 through F3 for Fans 1
through 3, and F4 through F18 for card slots 1 through 15,
5A-120VAC rating.
Operating Conditions are listed in Table 30-1.
Withstands 10G, 10 ms. at 1/2 sine wave.
Withstands 1/4 G, 20–500 Hz.
Up to 7200 BTUs depending on node configuration.
Limits
Fahrenheit
+40 to +100 degrees
+68 to + 86 degrees
1
+35 to +120 degrees
20% to 55%
(noncondensing)
10% to 80%
(noncondensing)
Chapter 30
BPX Node Specifications
Centigrade
+4.5 to +38 degrees
+20 to +30 degrees
+1.7 to + 49 degrees
Release 9.3.30, Part Number 78-12907-01 Rev. E0, May 2005