hit counter script

Siemens SITOP PSU8600 Manual page 128

Psu8600power supply systems
Hide thumbs Also See for SITOP PSU8600:
Table of Contents

Advertisement

Engineering and remote access
7.3 SIMATIC STEP 7 in the TIA Portal
Navigation area
Web server
A detailed description of the individual parameters is provided in Sections Parameterizing the
basic unit (Page 130) and Parameterizing outputs (Page 136).
Note
In addition, under "Device configuration > Outputs 1...4" by activating item "The
configuration of the output can differ during runtime because it is controlled remotely" a note
can be saved as to whether the parameters for the output are controlled from a PLC program
during the runtime. For a download, this information is not written to the device, it is only
saved in the STEP 7 project file.
128
Description
Outputs 1 ... 4
Make the following settings for the individual outputs:
Switch-on and switch-off output.
Setpoint output voltage
Response threshold value of the output current
Define a threshold to issue an alarm.
An alarm is output if this threshold is continually exceeded for
5 ms.
Define the on delay.
Define the ELECTRONIC SHUTDOWN or CONSTANT
CURRENT operating modes
PROFIenergy
Here, you can activate and configure energy management based
on PROFIenergy
General
Make the following settings:
Possibility of accessing via a web server (yes / no)
Automatic logoff when closing the web server (yes / no)
Permit access only via HTTPS (yes/no)
Automatic up-
Make the following settings:
date
Activate automatic update (yes / no)
Time interval for the update
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitop cnx8600Sitop buf8600

Table of Contents