hit counter script

Backing Up The System Configuration; Synchronize File System; Preparing A Card For Replacement - Cisco ASR 5500 Installation Manual

Hide thumbs Also See for ASR 5500:
Table of Contents

Advertisement

Backing Up the System Configuration

Important
Backing Up the System Configuration
Prior to replacing a failed card of any type, it is good practice to save the current configuration to an external
USB device or remote network location.
Refer to Verifying and Saving Your Configuration in the System Administration Guide for detailed instructions

Synchronize File System

To assure that the configuration files on both MIO/UMIOs are identical, run the Exec mode filesystem
synchronize all command.
[local]

Preparing a Card for Replacement

To minimize service disruptions, traffic currently being processed by a failing or failed circuit card should be
switched to another card. You have the following options based on the type of card being replaced:
• MIO/UMIO – If the active MIO/UMIO fails, a switchover to the standby MIO/UMIO is automatic. In
• DPC/UDPC and DPC2/UDPC2 – An Exec mode card busy-out slot_number command moves processes
• DPC/UDPC and DPC2/UDPC2 – In the event of the critical failure of a DPCx/UDPCx, tasks will be
• FSC – The FSCs are configured for n+1 redundancy. When an active FSC fails, an automatic switchover
Important
ASR 5500 Installation Guide
140
Data processing cards must all be of the same type – DPC, UDPC, DPC2 or UDPC2 – in a chassis.
host_name
filesystem synchronize all
#
the event that an issue arises that is not severe enough for the system to perform an automatic switchover,
a manual switchover can be invoked by executing the Exec mode card switch from <5 or 6> to <6 or
5> command.
from the source DPC/UDPC to the destination DPC/UDPC, or disables the DPC/UDPC from accepting
any new calls. When busy-out is enabled, the DPC/UDPC stops receiving new calls but continues to
process calls until they are completed. The busy-out procedure is completed in background.
automatically be migrated from the active card to a redundant card in standby mode. In the event that
an issue arises that is not severe enough for the system to perform an automatic migration, a manual
migration can be initiated using the Exec mode card migration from original_slot# to final_slot#
is made to the standby FSC. At least one FSC must be in standby mode prior to initiating a switchover.
In the event that an issue arises that is not severe enough for the system to perform an automatic
switchover, a manual switchover can be invoked by executing the Exec mode card switch from
slot_number to slot_number command.
An FSC-200GB (equipped with two 200GB SSDs) can be replaced with an FSC-400GB (equipped with
a single 400GB SSD) only if the StarOS release supports the non-RAID 0 configuration of the FSC-400GB.
Replaceable Components

Advertisement

Table of Contents
loading

Table of Contents