Technical Specifications
in a standard 23-inch (584.2 mm) cabinet or rack. The chassis mounting brackets may be repositioned to
support flush and mid-mount installations.
The chassis footprint is approximately 19-inch (48.26 cm) wide by 26.75 in. (67.9 cm) long.
Important
Two ASR 5500 chassis fit in 42 RU (73.5 in.) of space within an equipment rack or cabinet.
Important
Power Requirements
Power Specifications
The table below lists the power requirements for individual components of the ASR 5500 chassis.
Table 6: ASR 5500 Power Requirements
Component
Chassis
Cards
FSC
SSC
MIO or UMIO
DPC or UDPC
DPC2 or UDPC2
Fan Tray Unit
Front
Rear
This footprint does not include the rear-mounted cable management tray.
Rack mounting requires the use of industry-standard equipment racks or cabinets with
supplier-recommended fasteners. The rack should be rated to accommodate the weight of one or two
chassis and any auxiliary equipment.
Parameter
Input voltage per feed circuit (nominal)
Input voltage per feed circuit (maximum)
Power feed circuits per each PFU
TUV rated peak current load per feed
Maximum power load per chassis
Maximum power
Maximum power
Maximum power
Maximum power
Maximum power
Maximum power
Maximum power
Power Requirements
Values
-48VDC
-40VDC to -60VDC
4
80 amps @ -40 VDC
12,800 watts
150 watts
10 watts
650 watts
630 watts
760 watts
60 watts each (2 per chassis
940 watts each (2 per chassis)
ASR 5500 Installation Guide
Notes
—
—
1
2
3
—
—
—
—
—
—
—
21