CHAPTER 5: SETTINGS
support paired control points, with each paired control point operating two virtual inputs. The
setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired
CONTROL POINTS
operate on a one-to-one basis.
The
DNP TCP CONNECTION TIMEOUT
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection is
aborted by the C60. This frees up the connection to be re-used by a client. Any change takes effect after cycling power to
the relay.
5.3.4.11 DNP / IEC 60870-5-104 point lists
SETTINGS PRODUCT SETUP SECURITY COMMUNICATIONS DNP / IEC104 POINT LISTS
DNP / IEC104
POINT LISTS
Up to 256 binary and up to 256 analog input points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104
protocol, can be configured. The value for each point is user-programmable and can be configured by assigning FlexLogic
operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) follows.
SETTINGS PRODUCT SETUP SECURITY COMMUNICATIONS DNP / IEC104 POINT LISTS BINARY INPUT /
MSP POINTS
BINARY INPUT / MSP
POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. See the Introduction to FlexLogic section in this chapter for the range of
assignable operands.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the C60 is restarted.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) follows.
SETTINGS PRODUCT SETUP SECURITY COMMUNICATIONS DNP / IEC104 POINT LISTS ANALOG INPUT
/ MME POINTS
ANALOG INPUT / MME
POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is
configured by assigning an appropriate FlexAnalog parameter to each point. See the FlexAnalog Parameters section in
Appendix A for the range of assignable parameters.
Changes to the DNP / IEC 60870-5-104 point lists take effect when the C60 is restarted.
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
setting specifies a time delay for the detection of dead network TCP connections. If
BINARY INPUT / MSP
POINTS
ANALOG INPUT / MME
POINTS
Point: 0
Off
Point: 1
Off
Point: 255
Off
Point: 0
Off
Point: 1
Off
Point: 255
Off
DNP NUMBER OF PAIRED
See below
See below
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
Range: any FlexAnalog parameter
PRODUCT SETUP
5
5-41