CHAPTER 5: SETTINGS
XSWI1 INTERLOCK CLS
Range: any FlexLogic operand
Default: On
This setting is used to select a FlexLogic operand that declares to IEC 61850 services that interlocking conditions are not
acceptable for closing disconnect switch 1. While the selected operand is asserted, the value of DiscCILO.EnaCls.stVal is
false. If a SelectWithValue or Operate service with ctlVal true and with Check.Interlock-check true is requested of
DiscCSWI1.Pos or Disc0XSWI1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with
the REASON CODE of Blocked-by-interlocking.
XSWI1 Pos ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: sbo-with-enhanced-security
This setting selects the control model that clients must use to successfully control the disconnect switch 1 signals
marked Disc0XCBR1.PosOpn.ctlVal and Disc0XCBR1.PosCls.ctlVal on the Disconnect Switch Logic diagram in the Settings
> System Setup section later. These signals force a disconnect switch trip or close control while the operand selected by
setting XSWI1 ST.LOC OPERAND is not active.
"sbo" here is select-before-operate. Enhanced security means that the C60 reports to the client the disconnect switch 1
position the end of the command sequence.
XSWI1 Pos sboTimeout
Range: 2.000 to 60.000 s in steps of 0.001s
Default: 30.000 s
This setting specifies the maximum time between a select and an operate command to disconnect switch 1 signals
marked Disc0XCBR1.PosOpn.ctlVal and Disc0XCBR1.PosCls.ctlVal in order for the operand to be successful. This setting is
only relevant when XSWI1 Pos ctlModel is sbo-with-normal-security or sbo-with-enhanced-security.
XSWI1 BlkOpn ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: sbo-with-normal-security
This setting selects the control model clients must use to successfully control the disconnect switch 1 signal marked
DiscCSWI1.BlkOpn.ctlVal signal on the Disconnect Switch Logic diagram in the Settings > System Setup section later. This
signal when true blocks disconnect switch 1 trip control while the operand selected by setting XSWI1 ST.LOC OPERAND is
not active.
XSWI1 BlkCls ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: sbo-with-normal-security
This setting selects the control model clients must use to successfully control the disconnect switch 1 signal marked
DiscCSWI1.BlkCls.ctlVal signal on the Disconnect Switch Logic diagram in the Settings > System Setup section later. This
signal when true blocks disconnect switch 1 close control while the operand selected by setting XSWI1 ST.LOC OPERAND
is not active.
CSWI1 Pos ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: sbo-with-normal-security
This setting selects the control model clients must use to successfully control the disconnect switch 1 signals marked
DiscCSWI1.PosOpn.ctlVal and DiscCSWI1.PosCls.ctlVal on the Disconnect Switch Logic diagram in the Settings > System
Setup section later. These signals force a disconnect switch trip or close control while the operand selected by setting
XSWI1 ST.LOC OPERAND is not active.
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
5
5-67