Hardware manual ACS880-104 inverter modules Table of contents 4. Cabinet construction 5. Electrical installation 7. Start-up 2017 ABB Oy. All Rights Reserved. 3AUA0000104271 Rev G EFFECTIVE: 2017-01-16...
Target audience This manual is intended for people who plan the installation, install, commission, use and service ACS880-104 inverter modules. Read the manual before working on the modules. The reader is expected to know the standard electrical wiring practices, electronic...
You can find all documentation related to ACS880 multidrive modules on the Internet at https://sites-apps.abb.com/sites/lvacdrivesengineeringsupport/content. For other manuals, see the inside of the front cover. If needed, contact your local ABB representative. Categorization by frame size, option code and...
Introduction 19 Terms and abbreviations Term/abbreviation Explanation BCON Type of control board. See BCU. Type of control unit. The BCU is used to control inverter units of frame sizes R8i and up. It is connected to the inverter modules using fiber optic cables. The external I/O control signals of the inverter unit are mostly connected to the BCU, or optional I/O extensions mounted onto it.
Page 21
Introduction 21 Term/abbreviation Explanation Inverter unit Inverter module(s) under control of one control board, and related components. One inverter unit typically controls one motor. See Inverter module. Main circuit breaker Electrically-controlled main switching and protecting device. A withdrawable breaker can also be used as the main disconnector. Main contactor Electrically-controlled main switching device Main switch/disconnector...
Hardware description 23 Hardware description Contents of this chapter This chapter describes a typical drive system and the hardware of ACS880-104 inverter modules.
The supply unit connects to the AC supply network and converts the AC voltage into DC. The DC voltage is distributed through the DC bus to all inverter units. The inverter unit, consisting of one or more ACS880-104 inverter modules, converts the DC back to AC that rotates the motor.
ACS880-104 inverter modules can be used to construct inverter units with a power rating from 2.5 kW up to several megawatts. Up to approximately 500 kW, inverter units consist of one module only;...
Slots for optional I/O modules I/O terminal blocks Grounding/clamping plate for control cables Memory unit Control panel connector Air temperature sensor Cover with control panel holder (can optionally be left out) Varistor board connecting screw (VAR). Should not be present in an ACS880-104.
Slots for optional I/O modules I/O terminal blocks Grounding/clamping plate for control cables Memory unit Control panel connector Air temperature sensor Cover with control panel holder (can optionally be left out) Varistor board connecting screw (VAR). Should not be present in an ACS880-104.
ABB or third party Common DC fuses ABB or third party Fuse disconnector ABB or third party Inverter modules Motor ABB (not part of ACS880-104 product offering) or third party Cabinet layout and cooling See chapter Cabinet construction (page 47).
Front cover retaining clip To remove the front cover, use a screwdriver to push the clip down, and pull cover outwards by its bottom edge. Varistor board and EMC filter connecting screws (VAR and EMC). Should not be present in an ACS880-104.
ABB or third party Common DC fuses ABB or third party Fuse disconnector ABB or third party Inverter modules Motor ABB (not part of ACS880-104 product offering) or third party Cabinet layout and cooling See chapter Cabinet construction (page 47).
Hardware description 31 Frames R6i and R7i The DC input terminals are located at the top of the module; the AC output are located at the bottom. The ZCU-14 control unit is mounted onto the module; the control unit contains the basic I/Os and slots for optional I/O modules.
32 Hardware description Module layout (Frame R6i shown.) Item Explanation DC (input) connection Motor (output) connection ZCU-14 control unit (with I/O connections and slots for optional I/O modules) I/O terminal blocks Control panel connector, memory unit Grounding/clamping plates for control cables Cooling fan holder with one (R6i) or two (R7i) fans Lifting eyes Terminal block X7 for connection of charging...
R6i inverter module. Item Explanation Available through Inverter cubicle DC supply DC switch/disconnector (optional) ABB or third party DC fuses ABB or third party Common mode filters Inverter module Motor ABB (not part of ACS880-104 product offering) or third party...
Charging contactor (optional) ABB or third party Charging resistors (optional) ABB or third party Common mode filters Inverter module Motor ABB (not part of ACS880-104 product offering) or third party Cabinet layout and cooling See chapter Cabinet construction (page 47).
Hardware description 35 Frame R8i and multiples Frame R8i modules are used to achieve output powers from approximately 250 kW upwards in single or parallel configurations. R8i modules run on wheels, and can easily be removed from the cubicle for cable installation or service. The motor connection is via a quick connector at the back of the module that couples when the module is inserted into the cubicle.
36 Hardware description Module layout Front view Rear view Description DC input busbars Handle LEDs (see section LED indications on page 200) Fiber optic connectors (see section Fiber optic connectors on page 38) Cooling fan (standard speed-controlled fan shown; a direct-on-line fan is available as option +C188) Quick connector (AC output) (the counterpart fastened to the cabinet behind the module) Wheels Type designation label...
Hardware description 37 Connectors X50…X53 R8i modules contain a power supply (BDPS) that provides 24 V DC for the circuit boards of the module. The BDPS is powered internally from the DC link. An auxiliary voltage of 230 V AC (standard) or 115 V AC (option +G304) can optionally be fed to X50 (X50:4 and X50:5) to power the BDPS even when the DC link is not live.
38 Hardware description Fiber optic connectors Name Description BSFC Charging controller connection (see section BSFC connection and capacitor charging on page 35). Must be connected by the installer. BFPS BFPS Fan control connection (to fan control box). Connected at the factory. Control unit connection.
ABB or third party Charging switch (optional) ABB or third party Charging resistors (optional) ABB or third party DC fuses ABB or third party Common mode filters Inverter module Motor ABB (not part of ACS880-104 product offering) or third party...
ABB or third party Charging resistors (optional) ABB or third party DC fuses ABB or third party Common mode filters Inverter modules Motor ABB (not part of ACS880-104 product offering) or third party Cabinet layout and cooling See chapter Cabinet construction (page 47).
Hardware description 41 Inverter unit control interfaces Overview of control connections of the ZCU control unit The diagram shows the control connections and interfaces of the ZCU-14 control unit, used with module frame sizes R1i…R7i. Frame R5i modules employ a type ZCU-12 unit which has a different layout but the same connectivity as the ZCU-14.
42 Hardware description Overview of control connections of the BCU control unit The diagram shows the control connections and interfaces of the BCU control unit, used with module frame size R8i and multiples. Description Description Analog and digital I/O extension modules Control panel.
Hardware description 43 The ACS-AP-x control panel The ACS-AP-x is the user interface of the inverter unit, providing the essential controls such as Start/Stop/Direction/Reset/Reference, and the parameter settings for the control program. The control panel can be mounted on the cabinet door using a DPMP-01 mounting platform (available separately).
Each inverter module has a type designation label attached to it. The type designation stated on the label contains information on the specifications and configuration of the unit. The first digits express the basic construction of the unit, for example “ACS880-104- 0100A-3”. Any optional selections are given thereafter, separated by plus signs.
Unpacking the module 45 Unpacking the module Contents of this chapter This chapter gives basic information on unpacking the module. Unpacking – Frames R1i…R5i The module is delivered in a corrugated cardboard box. The module and its parts (such as grounding/clamp plates, terminal blocks, etc.) are placed in the different compartments of the box.
46 Unpacking the module Unpacking – Frames R6i…R8i The modules are delivered on a wooden base, boxed in corrugated cardboard. The cardboard box is tied to the base with PET bands. 1. Cut off the bands. 2. Lift off the cardboard box. 3.
Cabinet construction 47 Cabinet construction Contents of this chapter This chapter contains instructions for constructing the cabinet for ACS880-104 inverter modules. For general instructions, refer to Cabinet design and construction instructions for ACS880 multidrive modules (3AUA0000107668 [English]). Liability The installation must always be designed and made according to applicable local laws and regulations.
You can find the kit-specific assembly drawings, step-by-step instructions and kit information on the Internet (https://sites-apps.abb.com/sites/lvacdrivesengineeringsupport/content). If necessary, contact your local ABB representative. The example includes also cabinet assembly drawings that show each stage listed in the table. More detailed steps of each stage are described in the kit-specific assembly drawings.
Cabinet construction 49 R1i…R4i modules in a 400 mm wide Rittal TS 8 enclosure A maximum of four frame R1i or R2i modules, or two frame R3i or R4i modules can be fitted into a 400 mm wide TS 8 enclosure, but the number can be reduced by optional equipment.
Page 50
50 Cabinet construction Installation stage Instruction code Kit code Kit ordering code Common parts: • Baying parts 3AUA0000114535 • PE busbar 3AUA0000114475 • Divider panel 3AUA0000115695 • DC busbars 3AUA0000115891 A-468-X-001 3AUA0000115906 Bottom plate Mounting plate (IEC) 3AUA0000114470 Mounting plate (UL) 3AXD50000003890 DC busbars (IEC) 3AUA0000114418...
Cabinet construction 59 R1i…R4i modules in a 600 mm wide Rittal TS 8 enclosure A maximum of eight frame R1i or R2i modules, or four frame R3i or R4i modules can be fitted into a 600 mm wide TS 8 enclosure, but the number can be reduced by optional equipment.
Page 60
60 Cabinet construction Installation stage Instruction code Kit code Kit ordering code Common parts: • Baying parts 3AUA0000114535 • PE busbar 3AUA0000114475 • Divider panel 3AUA0000115695 • DC busbars 3AUA0000115891 A-468-X-001 3AUA0000115906 Bottom plate Mounting plate 3AUA0000114480 DC busbars 3AUA0000114054 A-6-1234-271 3AUA0000114079 Mounting plate shrouds...
Cabinet construction 69 R1i…R4i modules in a 800 mm wide Rittal TS 8 enclosure A maximum of twelve frame R1i or R2i modules, or six frame R3i or R4i modules can be fitted into a 800 mm wide TS 8 enclosure, but the number can be reduced by optional equipment.
Page 70
70 Cabinet construction Installation stage Instruction code Kit code Kit ordering code Common parts: • Baying parts 3AUA0000114535 • PE busbar 3AUA0000114475 • Divider panel 3AUA0000115695 • DC busbars 3AUA0000115891 A-468-X-001 3AUA0000115906 Bottom plate Mounting plate (IEC) 3AUA0000114481 Mounting plate (UL) 3AXD50000003698 DC busbars (IEC) 3AUA0000114413...
Cabinet construction 79 R5i modules in a 400 mm wide Rittal TS 8 enclosure Description Cubicle including: 1. DC input 2. DC switch/disconnector handle for all inverter modules. The main DC fuses are installed next to the switch/disconnector behind the shroud 3.
Page 80
80 Cabinet construction Installation stage Instruction code Kit code Kit ordering code Common parts: • Baying parts 3AUA0000114535 • PE busbar 3AUA0000114475 • Divider panel 3AUA0000115695 • DC busbars 3AUA0000115891 A-468-X-001 3AUA0000115906 Bottom plate Mounting plates and 3AXD50000014638 supports DC busbars 3AXD50000013532 A-4-5-276 3AXD50000013505...
Cabinet construction 89 R5i modules in a 600 mm wide Rittal TS 8 enclosure Description Cubicle including: 1. DC input 2. DC switch/disconnector handle for all inverter modules. The main DC fuses are installed next to the switch/disconnector behind the shroud 3.
Page 90
90 Cabinet construction Installation stage Instruction code Kit code Kit ordering code Common parts: • Baying parts 3AUA0000114535 • PE busbar 3AUA0000114475 • Divider panel 3AUA0000115695 • DC busbars 3AUA0000115891 A-468-X-001 3AUA0000115906 Bottom plate Mounting plates and 3AXD50000014638 supports DC busbars 3AXD50000013496 A-6-5-277 3AXD50000013506...
Cabinet construction 99 One R6i/R7i module in a 400 mm wide Rittal TS 8 enclosure Description Cubicle including: 1. DC bus 2. DC switch/disconnector and DC fuses 3. Charging contactor and resistors (frame R7i only) 4. Inverter module 5. AC output 6.
Page 100
100 Cabinet construction Installation stage Instruction code Kit code Kit ordering code Common parts: • Baying parts 3AUA0000114535 • PE busbar 3AUA0000114475 • Divider panel 3AUA0000115695 • DC busbars 3AUA0000115891 A-468-X-001 3AUA0000115906 Bottom plate Support beams 3AUA0000117053 DC busbars and charging components: •...
112 Cabinet construction One R8i module in a 400 mm wide Rittal TS 8 enclosure With DC Without DC switch/disconnector switch/disconnector and charging and charging Description Cubicle including: 1. DC switch/disconnector (obscured) 2. DC fuses 3. Charging switch 4. Common mode filters 5.
Page 113
Cabinet construction 113 Installation stage Instruction code Kit code Kit ordering code Common parts: • Baying parts 3AUA0000114535 • PE busbar 3AUA0000114475 • Divider panel 3AUA0000115695 • DC busbars 3AUA0000115891 A-468-X-001 3AUA0000115906 DC connection 1 of 2 (from DC bus to DC fuses) without DC switch/charging: •...
Cabinet construction 125 Two R8i modules in a 600 mm wide Rittal TS 8 enclosure With DC Without DC switch/disconnector switch/disconnector and charging and charging Description Cubicle including: 1. DC switch/disconnector (obscured) 2. DC fuses 3. Charging switch 4. Common mode filters 5.
Page 126
126 Cabinet construction Installation stage Instruction code Kit code Kit ordering code Common parts: • Baying parts 3AUA0000114535 • PE busbar 3AUA0000114475 • Divider panel 3AUA0000115695 • DC busbars 3AUA0000115891 A-468-X-001 3AUA0000115906 DC connection 1 of 2 (from DC bus to DC fuses) without DC switch/charging: •...
Cabinet construction 139 One R8i module in a 400 mm wide generic enclosure Parts to be installed Instruction code Kit code Kit ordering code DC switch/charging mechanics 3AXD50000043644 A-4-8-292 3AXD50000044559 (optional) DC busbars (without DC switch/charging): • Busbar assembly 3AXD50000006441 A-4-8-256 3AXD50000006418...
Cabinet construction 141 Two R8i modules in a 600 mm wide generic enclosure Parts to be installed Instruction code Kit code Kit ordering code DC switch/charging mechanics 3AXD50000043784 A-6-8-293 3AXD50000044560 (optional) DC busbars (without DC switch/charging): • Busbar assembly 3AXD50000006447 A-6-8-257 3AXD50000006444...
Cabinet construction 143 Three R8i modules in a 800 mm wide generic enclosure Parts to be installed Instruction code Kit code Kit ordering code DC switch/charging mechanics 3AXD50000044586 A-8-8-294 3AXD50000044581 (optional) DC busbars (without DC switch/charging): • Busbar assembly 3AXD50000006455 A-8-8-258 3AXD50000006450...
Note: The installation must always be designed and made according to applicable local laws and regulations. ABB does not assume any liability whatsoever for any installation that breaches the local laws and/or other regulations. Furthermore, if the recommendations given by ABB are not followed, the drive system may experience problems that the warranty does not cover.
146 Electrical installation Electrical safety precautions WARNING! Perform the electrical safety precautions before starting any work on the installation. Ignoring the precautions can cause physical injury or death, or damage to the equipment. Only a qualified electrician is allowed to work on the installation.
• Flexing: Max. 1000 cycles ABB drive products in general utilize 5 and 10 MBd (megabaud) optical components from Avago Technologies’ Versatile Link range. Please note that the optical component type is not directly related to the actual communication speed.
148 Electrical installation Note: Moisture inside the motor casing will reduce the insulation resistance. If moisture is suspected, dry the motor and repeat the measurement. Brake resistor assembly See section Checking the insulation of the brake resistor assembly (page 329).
Electrical installation 149 Power connections – Frames R1i…R5i A simplified diagram of the power connections is presented below. For more detailed diagrams, see page 383. Inverter cubicle DC supply DC switch/disconnector for all inverter modules Main DC fuses DC fuse disconnectors for each inverter module Inverter modules Motors Power cable connection procedure...
150 Electrical installation Frames R3i…R5i 1. Run the output (motor) cable into the cubicle through a cable gland or grommet. 360° grounding of the cable shield is recommended to suppress interference. In case a grounding cable gland is available, remove the outer jacket of the cable where it passes through the cable gland.
Electrical installation 151 Power connections – Frames R6i…R8i Simplified diagrams of the power connections are presented below. For more detailed diagrams, see page 389. R6i inverter module Inverter cubicle DC supply DC switch/disconnector DC fuses Common mode filter Inverter module Motor...
152 Electrical installation R7i inverter module Inverter cubicle DC supply DC switch/disconnector DC fuses Charging circuit (contactor and resistors) Common mode filter Inverter module Motor R8i inverter module Inverter cubicle DC supply DC switch/disconnector Charging circuit (fuses, resistors, charging controller) DC fuses Common mode filter Inverter module...
154 Electrical installation Connection procedure WARNING! Read and follow the instructions given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). Ignoring the instructions can cause physical injury or death, or damage to the equipment. 1. Ground the inverter modules by the top edge of the front plate. The grounding point is marked on the module.
Electrical installation 155 Grounding the motor cable shield at the motor end For minimum radio-frequency interference, ground the cable shield 360 degrees at the lead-through of the motor terminal box.
156 Electrical installation Replacing ACS800 R8i modules with ACS880 R8i modules ACS880 R8i modules can be ordered with option +P942 for mechanical compatibility with ACS800 R8i modules. A dimension drawing is presented on page 345. The following procedure explains the additional wiring changes that are required. WARNING! Repeat the steps described in section Electrical safety precautions...
Page 157
Electrical installation 157 7. On the BCU control unit, connect the DIIL input to a +24VD terminal. 8. If the Safe torque off (STO) function is to be used, remove the jumper connection between X52 and X53 on each module. Wire the STO link to all inverter modules of the inverter unit.
Page 158
158 Electrical installation STO OUT STO signal forwarding output to next inverter module (if present) STO IN STO signals from BCU control unit 9. Connect an ACS-AP-x control panel to X13 on the BCU control unit. 10. If the modules are equipped with option +C183 (heating elements), connect a 230/115 V AC (50/60 Hz) supply to X50:7…8.
Electrical installation 159 Connecting the control cables – All frame sizes For technical data and default I/O connections of the inverter control unit, refer to chapter The inverter control unit (page 293). 1. In the cabinet, remove shrouding wherever necessary to allow access to the cable entries and any trunking inside the cubicle.
Page 160
160 Electrical installation 6. Strip the cable ends and conductors. When connecting to the drive I/O, also remove the shield along with the outer sheathing, and use electrical tape or shrink tubing to contain the strands. Elsewhere, twist the outer shield strands into a bundle, crimp a lug onto it and connect it to the nearest chassis grounding point.
Electrical installation 161 Installing optional modules Installation of I/O extension and fieldbus adapter modules Note: Pay attention to the free space required by the cabling or terminals coming to the optional modules. 1. Disconnect the inverter unit from the supply, lock out the disconnecting device, and ensure by measuring that there is no voltage present.
162 Electrical installation Installation of an FSO-xx safety functions module Installation onto a ZCU control unit (Frames R1i…R7i) 1. Stop the inverter unit and do the steps in section Electrical safety precautions (page 146) before you start the work. 2.
Electrical installation 163 Installation onto a BCU control unit (Frame R8i and multiples) 1. Stop the inverter unit and do the steps in section Electrical safety precautions (page 146) before you start the work. 2. The FSO-xx comes with alternative bottom plates for mounting on different units. For mounting on the BCU, the mounting points should be located at the long edges of the module as shown.
Electrical installation 165 Installation beside the control unit To reserve the slots of the control unit for other modules, you can install the FSO-xx separate from the control unit using mounting kit 3AXD50000025495. The kit contains the parts for mounting the FSO-xx either onto a DIN rail nearby the ZCU or BCU control unit, or onto the grounding/clamping plate of a ZCU-14 (used in frames R1i…R4i) control unit.
166 Electrical installation Connecting a PC A PC (with eg. the Drive composer PC tool) can be connected to the inverter unit as follows: 1. Connect an ACS-AP-W or ACS-AP-I control panel to the inverter control unit either by using an Ethernet (eg. CAT5E) networking cable, or by inserting the panel into the panel holder (if present).
Electrical installation 167 Panel bus (Control of several inverter units from one control panel) One control panel (or PC) can be used to control several inverter units by constructing a panel bus. This is done by daisy-chaining the panel connections of the units. Frame R1i…R5i modules have the necessary panel connectors in the control panel holder which is optional for some frame sizes (for details, see chapter Ordering...
Installation checklist 169 Installation checklist Check the mechanical and electrical installation of the drive before start-up. Go through the checklist below together with another person. Check that… MECHANICAL INSTALLATION The unit is properly fastened to the floor. There is sufficient free space around the unit. The ambient operating conditions are fulfilled;...
Page 170
170 Installation checklist Check that… Appropriate DC fuses are installed. The motor is of the correct voltage. The star/delta connection in the motor terminal box is correct. The motor connections at U2, V2 and W2 and their tightening torques are OK. The motor cable is routed away from other cables.
Start-up 171 Start-up Contents of this chapter This chapter contains the start-up procedure of the inverter. Note: These instructions do not cover all possible cabinet constructions. Always refer to the delivery-specific circuit diagrams when proceeding with the start-up. WARNING! Only qualified electricians are allowed to do the work described in this chapter.
172 Start-up Tasks Checks/Settings with no voltage connected Check the mechanical and electrical installation. See Installation checklist (page 169). Make sure that the insulation resistance of the assembly has been checked. See Checking the insulation of the assembly (page 147). The supply unit of the drive system has been set up according to the instructions in its manuals.
Start-up 173 Tasks Set the parameters for each inverter unit. Refer to the firmware manual and/or start-up guide of the control program. You can also use the start-up assistant if available in the particular control program. In addition to the parameter settings required by the application, make the following settings: •...
174 Start-up Tasks WARNING! Before closing the main contactor/air circuit breaker, make sure that sufficient inverter power is connected to the intermediate (DC) bus. As a rule of thumb, • the sum power of the inverters connected must be at least 30% of the sum power of all inverters •...
The table below shows the maintenance tasks which can be done by the end user. The complete maintenance schedule is available on the Internet (http://www.abb.com/drivesservices). For more information, consult your local ABB Service representative (http://www.abb.com/searchchannels). Recommended annual actions by the user...
Performance of on/off-site work (commissioning, tests, measurements or other work) Replacement Maintenance and component replacement intervals are based on the assumption that the equipment is operated within the specified ratings and ambient conditions. ABB recommends annual drive inspections to ensure the highest reliability and optimum performance.
Maintenance 177 Cleaning WARNING! Repeat the steps described in section Electrical safety precautions on page 146. The complete safety instructions are given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). Ignoring the instructions can cause physical injury or death, or damage to the equipment. WARNING! Use a vacuum cleaner with an antistatic hose and nozzle, and wear a grounding wristband.
178 Maintenance Cleaning the door air inlets Follow the instructions of the manufacturer of the cabinet system. The cleaning instructions for the inlet kits specified in Ordering information (starting page 203) are given below. Cleaning the door air inlets (IP20) Use a vacuum cleaner and brush to clean the grating.
Maintenance 179 Cleaning the door air inlets (IP54) 1. Remove the fasteners at the top of the grating. 2. Lift the grating and pull it away from the door. 3. Remove the air filter mat. 4. Place the new filter mat in the grating the metal wire side facing the door. 5.
For resetting the running time signal after a fan replacement, please contact ABB. Replacement fans are available from ABB. Do not use other than ABB specified spare parts. Frames R1i and R2i...
Maintenance 181 Frames R3i and R4i WARNING! Repeat the steps described in section Electrical safety precautions on page 146. The complete safety instructions are given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). Ignoring the instructions can cause physical injury or death, or damage to the equipment.
182 Maintenance Frame R5i – Main cooling fan WARNING! Repeat the steps described in section Electrical safety precautions on page 146. The complete safety instructions are given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). Ignoring the instructions can cause physical injury or death, or damage to the equipment.
Maintenance 183 Frame R5i – Auxiliary cooling fan Frame R5i modules have an auxiliary fan located at the top front of the module. WARNING! Repeat the steps described in section Electrical safety precautions on page 146. The complete safety instructions are given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]).
184 Maintenance Frames R6i and R7i WARNING! Repeat the steps described in section Electrical safety precautions on page 146. The complete safety instructions are given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). Ignoring the instructions can cause physical injury or death, or damage to the equipment.
Maintenance 185 Frame R8i – Main cooling fan (modules without option +C188) If the inverter module is equipped with a direct-on-line cooling fan (option +C188), see page 187. WARNING! Repeat the steps described in section Electrical safety precautions on page 146. The complete safety instructions are given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]).
Maintenance 187 Frame R8i – Direct-on-line main cooling fan (option +C188) If the inverter module is not equipped with a direct-on-line cooling fan (option +C188), see page 185. WARNING! Repeat the steps described in section Electrical safety precautions on page 146. The complete safety instructions are given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]).
Maintenance 189 Frame R8i – Circuit board compartment fan The R8i module is equipped with a fan blowing air through the circuit board compartment. The fan is accessible from the front of the module. WARNING! Repeat the steps described in section Electrical safety precautions on page 146.
Page 190
190 Maintenance 7. Put the fan onto the threaded studs on the fan holder with the airflow direction arrow pointing towards the fan holder. 8. Install and tighten the four nuts removed earlier. 9. Connect the fan cable. 10. Align and push the fan holder into the module. 11.
Maintenance 191 Replacing the cabinet cooling fans Cabinets with ABB air outlet kits WARNING! Repeat the steps described in section Electrical safety precautions on page 146. The complete safety instructions are given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]).
• Only lift the module by its lifting eyes (see drawing on page 32). A lifting device that can be attached to the cubicle is available from ABB; see page 243. Refer to the drawings below. 1. Disconnect the drive system from the AC power line.
Maintenance 195 Replacing a frame R8i inverter module WARNING! Only qualified electricians are allowed to do the work described below. Read the complete safety instructions given in Safety instructions for ACS880 multidrive cabinets and modules [3AUA0000102301 (English)] before you service the drive. Ignoring the instructions can cause physical injury or death, or damage to the equipment.
Page 196
196 Maintenance 1. Stop the drive and disconnect it from the AC power line. Obey the instructions in section Electrical safety precautions on page 146. Open the main switch-disconnector or main breaker. If the disconnecting equipment is located outside the cabinet, make sure that it is in the disconnected position.
Capacitor failure is usually followed by damage to the unit and an input fuse failure, or a fault trip. Contact an ABB service representative for spare parts and repair services. Reforming the capacitors ...
Maintenance 199 Control panel Replacing the control panel battery 1. Turn the lid on the back of the panel counter-clockwise until the lid opens. 2. Replace the battery with a new CR2032 battery. 3. Put the lid back and tighten it by turning it clockwise. 4.
200 Maintenance LED indications Warnings and faults reported by the control program are displayed on the control panel or in the Drive composer PC tool. For further information, see the firmware manual of the inverter control program. The ACS-AP-x control panel has a status LED. The control panel holder (frames R1i…R4i) or door mounting kit DPMP-xx has two status LEDs.
202 Maintenance Resuming normal operation WARNING! Repeat the steps described in section Electrical safety precautions on page 146. The complete safety instructions are given in Safety instructions for ACS880 multidrive cabinets and modules (3AUA0000102301 [English]). Ignoring the instructions can cause physical injury or death, or damage to the equipment.
Ordering information 203 Ordering information Contents of this chapter This chapter lists the types and ordering codes of ACS880-104 inverter unit components. Notes: • This chapter only lists the installation accessories available from ABB. All other parts must be sourced from a third party (such as Rittal) by the system integrator. For a listing, refer to the kit-specific installation instructions available at https://sites-apps.abb.com/sites/lvacdrivesengineeringsupport/content.
204 Ordering information Kit code key The kit codes shown in this chapter break down as follows. The format of the kit code is A-w-s-xxx, for example, A-4-X-022 where: • A = air-cooled • w = cabinet width in mm/100, for example 6 = 600 mm •...
Ordering information 205 Frames R1i…R4i Inverter modules As standard, frame R1i to R4i inverter modules come with a cover that also acts as a control panel holder. The cover is fitted with a panel interface board (ZDPI-01) which enables the construction of a panel bus. The panel bus makes it possible to control several inverter units from a single control panel (see page 167).
Page 206
• Inverter module (1) with ZCU control unit (1a) • ZMU memory unit (2) with ACS880 primary control program. For For example, availability of other control programs, contact your local ABB ACS880-104-008A0-3 representative. • Module cover with control panel holder (3) •...
Ordering information 207 ACS-AP-x control panel The control panel is not included with the inverter module but must be ordered separately. One control panel is required for the commissioning of an ACS880 drive system, even if the Drive composer PC tool is used. For more information on the control panel, see ACX-AP-x assistant control panels user’s manual (3AUA0000085685 [English]).
Ordering code Illustration 400 mm 600 mm A-468-X-001 3AUA0000115906 800 mm Instruction code: 3AUA0000115891 Module-specific DC fuses (IEC, UL) Fuse Module type Ordering code ACS880-104-… Type Data 004A8-3 003A6-5 Bussmann FWP-10A14F* 10 A, 660 V 3AUA0000089115 006A0-3 004A8-5 008A0-3 006A0-5...
Ordering information 209 Module-specific DC fuse bases (IEC, UL) Fuse base Module type Ordering code ACS880-104-… Type Data 004A8-3 003A6-5 3AUA0000089224 (fuse base) Mersen US141 14 × 51 mm … … (Z331153F) 50 A, 690 V 3AUA0000089228 (microswitch) 0018A-3 0018A-5...
Page 210
210 Ordering information Busbars between main DC switch/disconnector and fuses Enclosure width Kit code Ordering code Illustration 400 mm A-4-1234-272 3AUA0000114423 Instruction code: 3AUA0000114418 600 mm A-6-1234-271 3AUA0000114079 Instruction code: 3AUA0000114054 800 mm A-8-1234-273 3AUA0000114426 Instruction code: 3AUA0000114413...
Page 211
Ordering information 211 Enclosure width Kit code Ordering code Illustration 400 mm A-4-1234-274 3AXD50000003918 Instruction code: 3AXD50000003895 600 mm A-6-1234-271 3AUA0000114079 Instruction code: 3AUA0000114054 800 mm A-8-1234-275 3AXD50000003919 Instruction code: 3AXD50000003875...
Output (du/dt) filters For information on the usage of output (du/dt) filters, see document ACS880 multidrive cabinets and modules electrical planning instructions (3AUA0000102324 [English]). Filter Module type Ordering code ACS880-104-… Type Data 004A8-3 003A6-5 : 15 A 006A0-3 004A8-5 L: 150 µH...
Ordering information 213 Mechanical installation accessories These kits include parts that are required for installing the inverter module in the enclosure. Mounting plate shroud kits The plates are installed in front of the main DC switch and fuses. The module-specific fuse disconnectors are installed onto this plate.
216 Ordering information Enclosure width / Kit code Ordering code Illustration Degree of protection 800 mm / IP42 A-8-X-026 3AUA0000117009 Instruction code: 3AUA0000116875 800 mm / IP54 A-8-X-029 3AXD50000009186 Instruction code: 3AXD50000010001 Air outlet kits Note: The fan is to be ordered separately. Enclosure width / Kit code Ordering code...
Page 217
Ordering information 217 Enclosure width / Kit code Ordering code Illustration Degree of protection 400 mm / IP42 A-4-X-060 3AUA0000114967 800 mm / IP42 Instruction code: 3AUA0000115290 Note: Fan to be ordered separately 600 mm / IP42 A-6-X-061 3AUA0000114971 Instruction code: 3AUA0000115152 Note: Fan to be ordered separately 400 mm / IP54 (IEC)
218 Ordering information Enclosure width / Kit code Ordering code Illustration Degree of protection 600 mm / IP54 A-6-X-065 3AXD50000009189 (IEC) Instruction code: 3AXD50000010004 Note: Fan to be ordered separately 600 mm / IP54 A-6-X-066 3AXD50000010327 (UL) Instruction code: 3AXD50000010004 Note: Fan to be ordered separately Cooling fans One or two cooling fans are to be installed inside the air outlet compartment to ensure...
Page 219
Ordering information 219 Enclosure width / Component Degree of protection Ordering code Name Data (Auxiliary voltage) R3G225-RH17-23 3AXD50000000592 800 mm / Connector 3AXD50000000723 IP20, IP42 SPB2,5/7 (2.5 mm , 12AWG) (230 V 50/60 Hz) Connector 3AXD50000000724 SC 2,5-RZ/7 (2.5 mm , 12AWG) RB4C-355/170 3AXD50000006934...
Page 220
220 Ordering information Enclosure width / Component Degree of protection Ordering code Name Data (Auxiliary voltage) RH35M-4EK.4F.1R 64750062 Capacitor 25 µF, 220 V 68713188 800 mm / IP54 (115 V 50/60 Hz) Connector 3AXD50000000723 SPB2,5/7 (2.5 mm , 12AWG) Connector 3AXD50000000724 SC 2,5-RZ/7 (2.5 mm , 12AWG)
Ordering information 221 Frame R5i Inverter module As standard, frame R5i inverter modules come with a two-part front cover, the top part of which also acts as a control panel holder. The holder is fitted with a panel interface board (ZDPI-01) which enables the construction of a panel bus.
Page 222
• Inverter module (1) with ZCU-12 control unit (2) • ZMU memory unit (3) with ACS880 primary control program. For For example, availability of other control programs, contact your local ABB ACS880-104-007A3-7 representative. • Module front cover, top (4) including •...
Ordering information 223 ACS-AP-x control panel The control panel is not included with the inverter module but must be ordered separately. One control panel is required for the commissioning of an ACS880 drive system, even if the Drive composer PC tool is used. For more information on the control panel, see ACX-AP-x assistant control panels user’s manual (3AUA0000085685 [English]).
Ordering code Illustration 400 mm A-468-X-001 3AUA0000115906 600 mm Instruction code: 3AUA0000115891 Module-specific DC fuses (IEC, UL) Fuse Module type Ordering code ACS880-104-… Type Data 007A3-7 009A8-7 Mersen 1021 CP URB 27x60/40* 40 A, 1000 V 3AUA0000089197 014A2-7 0018A-7 0022A-7...
Main DC switch/disconnector kits DC switch/disconnector Enclosure Qty of Ordering code width modules Type Data 400 mm 2 × R5i ABB OT200E11 2-pole, 200 A 3AXD50000015608 600 mm 4 × R5i ABB OT400E11 2-pole, 400 A 3AXD50000000891 DC switch/disconnector Enclosure Qty of...
Output (du/dt) filters For information on the usage of output (du/dt) filters, see document ACS880 multidrive cabinets and modules electrical planning instructions (3AUA0000102324 [English]). Filter Module type Ordering code ACS880-104-… Type Data : 15 A L: 150 µH 007A3-7 Power loss: 110 W...
Ordering information 227 Fuse base shroud kit IP20 protection of the DC fuse bases requires shrouding both above and below. One shroud kit contains the shrouds for each dual fuse base. Used with… Kit code Ordering code Illustration R5i modules installed in 1 per 400 or 600 mm wide A-X-5-356...
Page 228
228 Ordering information Enclosure width / Kit code Ordering code Illustration Degree of protection 400 mm / IP54 A-4-X-027 3AXD50000009184 Instruction code: 3AXD50000009989 600 mm / IP20 A-6-X-022 3AUA0000117003 Instruction code: 3AUA0000116880 600 mm / IP42 A-6-X-025 3AUA0000117008 Instruction code: 3AUA0000116874 600 mm / IP54 A-6-X-028 3AXD50000009185 Instruction code: 3AXD50000009990...
Ordering information 229 Air outlet kits Note: The fan is to be ordered separately. Enclosure width / Kit code Ordering code Illustration Degree of protection 400 mm / IP20 A-4-X-062 3AUA0000125201 Instruction code: 3AXD50000001982 Note: Fan to be ordered separately 600 mm / IP20 A-6-X-063 3AUA0000125202...
Page 230
230 Ordering information Enclosure width / Kit code Ordering code Illustration Degree of protection 400 mm / IP54 A-4-X-064 3AXD50000009187 (IEC) Instruction code: 3AXD50000010284 Note: Fan to be ordered separately 400 mm / IP54 A-4-X-067 3AXD50000010362 (UL) Instruction code: 3AXD50000010284 Note: Fan to be ordered separately...
Page 231
Ordering information 231 Enclosure width / Kit code Ordering code Illustration Degree of protection 600 mm / IP54 A-6-X-065 3AXD50000009189 (IEC) Instruction code: 3AXD50000010004 Note: Fan to be ordered separately 600 mm / IP54 A-6-X-066 3AXD50000010327 (UL) Instruction code: 3AXD50000010004 Note: Fan to be ordered separately...
232 Ordering information Cooling fan A cooling fan is to be installed inside the air outlet compartment to ensure sufficient cooling of the cabinet. Enclosure width / Component Degree of protection Ordering code Name Data (Auxiliary voltage) R3G225-RH17-23 3AXD50000000592 400 mm, 600 mm / IP20, IP42 Connector 3AXD50000000723...
Page 233
Ordering information 233 The following parts (or equivalent) are used to implement the circuit. These parts are to be sourced by the customer. • Phoenix Contact ST 2,5-DIO/L-R - 3036262 spring cage component terminal block with a 1N4007 diode • Relpol PI84-24DC-M41G relay •...
• Inverter module with ZCU control unit • ZMU memory unit with ACS880 primary control program. For availability For example, of other control programs, contact your local ABB representative. ACS880-104-0210A-3 [Module type] +C132 • Marine type approval. For more information, see ACS880 +C132 marine...
Ordering information 235 The control panel can be flush mounted on the cabinet door with the help of a door mounting kit. Type Description Ordering code Illustration Control panel with ACS-AP-W 3AXD50000025965 Bluetooth ACS-AP-I Control panel 3AUA0000088311 Door mounting kit DPMP-01 3AUA0000108878 (IP55)
Ordering code Kit code Illustration 400 mm 3AUA0000115906 A-468-X-001 Instruction code: 3AUA0000115891 DC fuses (IEC, UL) Fuse Module type Ordering code Type ACS880-104-… Data Size (Bussmann) 0110A-5 170M4409 250 A, 690 V 3AUA0000066038 0140A-3 0140A-5 170M4410 315 A, 690 V 3AXD50000000234...
238 Ordering information DC connection kit (for Rittal TS 8 enclosures) This kit contains the busbars from the DC bus towards the module as well as an air guide, mounting plate, insulators and screws. The assembly incorporates the electrical components (such as DC fuses, DC switch/disconnector, and charging components) whenever required;...
Page 239
Ordering information 239 Used with… Kit code Ordering code Illustration Frame size R6i with DC switch/disconnector A-4-6-285 3AXD50000004381 (UL) Instruction code: 3AXD50000004422 Frame R7i without DC switch/disconnector or A-4-67-283 3AUA0000122202 charging circuit Instruction code: 3AUA0000123371 Frame size R7i without DC switch/disconnector, A-4-7-282 3AUA0000122237 with charging circuit...
240 Ordering information DC busbars with common mode filter holder (for Rittal TS 8 enclosures) This kit contains the busbars that connect to the DC input of the inverter module. The busbars have a holder for the common mode filters; note that the filters shown in the illustration are not included in the kit.
Ordering information 241 AC-side components AC busbar kit This kit contains the busbars for connection of the motor cable. Note that the output (du/dt) filters (if required) are to be ordered separately (see further below). Module frame size Kit code Ordering code Illustration R6i, R7i...
242 Ordering information Mechanical installation accessories and tools These kits include parts that are used for installing the inverter module in the Rittal TS 8 enclosure. Inverter module mounting parts This kit contains the rails on which the inverter module rests, and provides air baffles for blocking unwanted air flow along the sides of the module.
Ordering information 243 Lifting device The lifting device is designed for maneuvering a frame R6i/R7i module when installing it into (or extracting it from) the Rittal TS 8 enclosure. See also section Replacing a frame R6i/R7i inverter module (page 192). Frame size Kit code Ordering code...
Ordering information 245 Air outlet kits Note: The IP54 kits require a cooling fan that must be ordered separately. Degree of protection Kit code Ordering code Illustration IP20 A-4-X-042 3AUA0000125203 Instruction code: 3AXD50000001983 IP42 A-4-X-040 3AUA0000114968 Instruction code: 3AUA0000115292 400 mm / IP54 A-4-X-064 3AXD50000009187 (IEC) Instruction code: 3AXD50000010284...
246 Ordering information Degree of protection Kit code Ordering code Illustration 400 mm / IP54 A-4-X-067 3AXD50000010362 (UL) Instruction code: 3AXD50000010284 Note: Fan to be ordered separately Cooling fan for IP54 air outlets A cooling fan is to be installed inside the IP54 air outlet compartment to ensure sufficient cooling of the cabinet.
Page 248
+C132: Marine type approval. For more information, see ACS880 +C132 marine type-approved drive modules and module packages supplement For example, (3AXD50000037752 [English]). ACS880-104-0470A-3 +E205 +C183: Heating element mounted to module base +C188: Direct-on-line (DOL) cooling fan +E205: Internal du/dt filtering. Standard with 690 V modules, required with...
Ordering information 249 ACS-AP-x control panel The control panel is not included with the inverter module but must be ordered separately. One control panel is required for the commissioning of an ACS880 drive system, even if the Drive composer PC tool is used. For more information on the control panel, see ACX-AP-x assistant control panels user’s manual (3AUA0000085685 [English]).
The control unit is delivered with a memory unit containing the ACS880 primary control program, optionally with application programmability. For availability of other control programs, contact your local ABB representative. Application...
Ordering information 251 Wire sets for use with the reduced run function A “reduced run” function (for inverter unit frame sizes 3×R8i and above) makes it possible to continue operation with limited current even if some modules of the inverter unit are out of service.
252 Ordering information DC connection parts 1 of 2 (for Rittal TS 8 enclosures) These parts connect the Flat-PLS busbars to the DC fuses, and provide the mounting base for the charging components if required. Used with… Kit code Ordering code Illustration 400/600 mm TS 8 enclosure...
Page 253
Ordering information 253 Used with… Kit code Ordering code Illustration A-4-8-288 3AXD50000044554 400 mm TS 8 enclosure with DC Instruction code: 3AXD50000043516 switch/disconnector and charging A-4-8-290 3AXD50000044557 Instruction code: 3AXD50000043504 A-6-8-289 3AXD50000044555 600 mm TS 8 enclosure with DC Instruction code: 3AXD50000043542 switch/disconnector and charging A-6-8-291...
254 Ordering information DC connection parts 1 of 2 (for generic enclosures) These parts provide the DC connection between the input busbars and the DC fuses (including a mounting base for the charging components if required). Used with… Kit code Ordering code Illustration 400 mm generic...
Page 255
Ordering information 255 Used with… Kit code Ordering code Illustration A-6-8-293 3AXD50000044560 600 mm generic enclosure with DC Instruction code: 3AXD50000043784 switch/disconnector and charging A-6-8-296 3AXD50000044583 Instruction code: 3AXD50000043737 A-8-8-294 3AXD50000044581 800 mm generic enclosure with DC Instruction code: 3AXD50000044586 switch/disconnector and charging A-8-8-297...
256 Ordering information DC connection parts 2 of 2 (for Rittal TS 8 or generic enclosures) These parts connect the DC fuses to the inverter module. Used with… Kit code Ordering code Illustration 1 per A-468-8-235 3AXD50000028401 module All TS 8 and generic enclosures without DC Instruction code: 3AXD50000028418 switch/disconnector and...
Ordering information 257 Common mode filters Common mode filtering reduces bearing currents and is required for electromagnetic compatibility (EMC). The filtering is implemented by installing two toroidal cores onto the DC busbars. Kits 3AXD50000028401 3AXD50000044551 (see above) contain a holder for the filters.
258 Ordering information DC fuses (IEC, UL) Fuse Unit type ACS880-104-… Ordering code Type Data Size 0470A-3 3AXD50000000148 Bussmann 170M6413 900 A, 690 V 0640A-3 68244463 Bussmann 170M6416 1250 A, 690 V 0760A-3 3AXD50000000150 Bussmann 170M6417 1400 A, 690 V...
Ordering information 259 DC switch/disconnector kits IEC – 230 V 50 Hz Unit type Enclosure type Ordering code Switch type ACS880-104-… 0470A-3 0440A-5 0340A-7 0640A-3 0590A-5 0410A-7 Rittal TS 8 or generic 3AXD50000009534 ABB OT1600E11 0760A-3 0740A-5 0530A-7 0900A-3 0810A-5...
Page 260
260 Ordering information UL – 115 V 60 Hz Unit type Enclosure type Ordering code Switch type ACS880-104-… 0470A-3 0440A-5 0340A-7 0640A-3 0590A-5 0410A-7 Rittal TS 8 or generic 3AXD50000009540 ABB OT1200U11 0760A-3 0740A-5 0530A-7 0900A-3 0810A-5 0600A-7 1250A-3 1150A-5...
(with shaft, handle, terminal shrouds and a set of auxiliary contacts), fuses, connectors and the charging controller. Note that the charging resistors or fiber optic cables are not included in the kit and must be ordered separately. Unit type Enclosure type Ordering code ACS880-104-… 0470A-3 0440A-5 0340A-7 0640A-3 0590A-5...
• The charging controller connects to each inverter module by a pair of fiber optic cables. The cables are not included and must be ordered separately. See section Fiber optic cables, page 250. Charging resistors Unit type Enclosure type Ordering code Data ACS880-104-… 0470A-3 0440A-5 0640A-3 0590A-5 Rittal TS 8 or generic 10037531 ZRF 30/165 S 24R 0760A-3...
Page 263
Ordering information 263 Unit type Enclosure type Ordering code Data ACS880-104-… 0470A-3 0440A-5 0640A-3 0590A-5 Rittal TS 8 or generic 10037531 ZRF 30/165 S 24R 0760A-3 0740A-5 0900A-3 0810A-5 1250A-3 1150A-5 1480A-3 1450A-5 Rittal TS 8 or generic 10037531 ZRF 30/165 S 24R...
264 Ordering information AC-side components Quick connector Used with… Kit code Ordering code Illustration 1 per All enclosure types A-468-8-100 3AUA0000119227 module Instruction code: 3AUA0000118667 Output busbars/shrouds kit This kit contains the busbars that connect to the quick connector(s), the busbars for the motor cable connection, and shrouding.
Page 265
Ordering information 265 Used with… Kit code Ordering code Illustration 400 mm TS 8 enclosure A-4-8-132 3AXD50000004414 (cable connection) Instruction code: 3AXD50000004838 400 mm TS 8 enclosure (common AC output A-4-8-140 3AXD50000008705 busbar connection) Instruction code: 3AXD50000010278 600 mm TS 8 enclosure A-6-8-133 3AXD50000005051 (cable connection)
Page 266
266 Ordering information Used with… Kit code Ordering code Illustration 400 mm generic enclosure (cable A-4-8-135 3AXD50000006435 connection) Instruction code: 3AXD50000006497 600 mm generic enclosure (cable A-6-8-136 3AXD50000006491 connection) Instruction code: 3AXD50000006489 600 mm generic enclosure A-6-8-138 3AXD50000006493 (cable connection with bridging busbars) Instruction code: 3AXD50000006505 800 mm generic...
Ordering information 267 Lead-through kit This kit, to be installed on the bottom plate of the enclosure, contains four lead-throughs for motor cables with grommets, wire meshing for 360° grounding, and a strain relief bracket. Used with… Kit code Ordering code Illustration 1 per All enclosure types...
268 Ordering information Used with… Kit code Ordering code Illustration 400 mm generic A-4-8-315 3AXD50000005875 enclosure Instruction code: 3AXD50000005874 600 mm generic A-6-8-311 3AXD50000005876 enclosure Instruction code: 3AXD50000005864 800 mm generic A-8-8-312 3AXD50000005877 enclosure Instruction code: 3AXD50000005848 Ramp (for Rittal TS 8 enclosures) The ramp can be used when installing or removing an R8i module.
Ordering information 269 Shrouding This kit contains the shroud for the top part of the cubicle with the necessary brackets and screws. Frame size Kit code Ordering code Illustration 400 mm Rittal TS 8 A-4-8-359 3AXD50000045738 enclosure Instruction code: 3AXD50000045749 600 mm Rittal TS 8 A-6-8-360 3AXD50000045779...
Page 270
270 Ordering information Enclosure width / Kit code Ordering code Illustration Degree of protection 400 mm / IP42 A-4-X-024 3AUA0000117007 Instruction code: 3AUA0000116873 400 mm / IP54 A-4-X-027 3AXD50000009184 Instruction code: 3AXD50000009989 600 mm / IP20 A-6-X-022 3AUA0000117003 Instruction code: 3AUA0000116880...
Page 271
Ordering information 271 Enclosure width / Kit code Ordering code Illustration Degree of protection 600 mm / IP42 A-6-X-025 3AUA0000117008 Instruction code: 3AUA0000116874 600 mm / IP54 A-6-X-028 3AXD50000009185 Instruction code: 3AXD50000009990 800 mm / IP20 A-8-X-023 3AUA0000117005 Instruction code: 3AUA0000116887 800 mm / IP42 A-8-X-026 3AUA0000117009...
272 Ordering information Enclosure width / Kit code Ordering code Illustration Degree of protection 800 mm / IP54 A-8-X-029 3AXD50000009186 Instruction code: 3AXD50000010001 Air outlet kits Note: The IP54 kits require a cooling fan that must be ordered separately. Enclosure width / Kit code Ordering code Illustration...
Page 273
Ordering information 273 Enclosure width / Kit code Ordering code Illustration Degree of protection 600 mm / IP42 A-6-X-041 3AUA0000114789 Instruction code: 3AUA0000115166 400 mm / IP54 (IEC) A-4-X-064 3AXD50000009187 800 mm / IP54 (IEC) Instruction code: 3AXD50000010284 Note: Fan to be ordered separately 400 mm / IP54 (UL) A-4-X-067 3AXD50000010362...
274 Ordering information Enclosure width / Kit code Ordering code Illustration Degree of protection 600 mm / IP54 A-6-X-065 3AXD50000009189 (IEC) Instruction code: 3AXD50000010004 Note: Fan to be ordered separately 600 mm / IP54 A-6-X-066 3AXD50000010327 (UL) Instruction code: 3AXD50000010004 Note: Fan to be ordered separately Cooling fans for IP54 air outlets One or two cooling fans are to be installed inside the air outlet compartment to ensure...
Page 275
Ordering information 275 RH40M-4EK.4I.1R 64750038 Capacitor 25 µF, 220 V 68713188 600 mm / IP54 (115 V 50/60 Hz) Connector 3AXD50000000723 SPB2,5/7 (2.5 mm , 12AWG) Connector 3AXD50000000724 SC 2,5-RZ/7 (2.5 mm , 12AWG) RB4C-355/170 3AXD50000006934 Capacitor MSB MKP 6/603/E1679 3AXD50000006959 800 mm / IP54 (230 V 50/60 Hz)
This chapter contains the technical specifications of the inverter modules and associated components. Ratings Output ratings Inverter unit Input Light-overload type ratings No-overload use Heavy-duty use Frame size ACS880-104- Input … = 400 V 004A8-3 006A0-3 008A0-3 10.5 0011A-3 12.6 13.5 10.5 0014A-3 16.8...
Page 278
278 Technical data Output ratings Inverter unit Input Light-overload type ratings No-overload use Heavy-duty use Frame size ACS880-104- Input … 0470A-3 0640A-3 0760A-3 0900A-3 1013 1080 1250A-3 2×R8i 1406 1630 1250 1200 1480A-3 2×R8i 1665 1930 1480 1025 1421 1107 1760A-3 2×R8i...
Page 279
• To achieve the rated motor power given in the table, the rated current of the drive must be higher than or equal to the rated motor current. The DriveSize dimensioning tool available from ABB is recommended for selecting the drive, motor and gear combination.
1% for every 100 m (328 ft). For a more accurate derating, use the DriveSize PC tool. Switching frequency derating Switching frequencies other than default can require output current derating. Contact ABB for more information. Output frequency derating ...
Page 281
Technical data 281 Power loss Air flow Noise level Inverter unit type capacitance ACS880-104-… dB(A) µF /min 0300A-3 2500 9000 0350A-3 3100 9000 0470A-3 4800 1300 11250 0640A-3 6700 1300 13500 0760A-3 8600 1300 18000 0900A-3 10000 1300 18000 1250A-3...
Technical data 283 Dimensions and weights The weights of the ACS880-104 modules are shown below. For the dimensions, see chapter Dimension drawings (page 335). Inverter module type Weight ACS880-104-… 004A8-3 003A6-5 006A0-3 004A8-5 008A0-3 006A0-5 008A0-5 0011A-3 0011A-5 0014A-3 0014A-5...
284 Technical data Free space requirements Inverter module type Above Below Front Left/Right inch inch inch inch ACS880-104-… 004A8-3 003A6-5 006A0-3 004A8-5 008A0-3 006A0-5 0011A-3 008A0-5 0014A-3 0011A-5 0018A-3 0014A-5 0018A-5 0025A-3 0025A-5 0035A-3 0030A-5 0044A-3 0035A-5 0050A-3 0050A-5 0061A-3...
Technical data 285 Input power (DC) connection ACS880-104-xxxxx-3: 513…566 V DC. This is indicated in the type Voltage (U designation label as typical input voltage level (566 V DC). ACS880-104-xxxxx-5: 513…707 V DC. This is indicated in the type designation label as typical input voltage levels (566/679/707 V DC).
IEC/EN 60721-3-1:1997 58…150 Hz: 1 g Classification of IEC 60068-2-6:2007, Classification of environmental EN 60068-2-6:2008 Tested in ABB multidrive environmental conditions - Part 3: Environmental testing Part 2: cabinet (ACS880-x07) conditions - Part 3: Classification of groups Tests -Test Fc: Vibration...
EU. They must be removed and handled according to local regulations. For further information on environmental aspects and more detailed recycling instructions, please contact your local ABB distributor. Standards See Electrical planning instructions for ACS880 multidrive cabinets and modules (3AUA0000102324 [English]).
Technical data 289 Auxiliary power consumptions Control equipment cont start cont Device 24 V DC ( + 10%) ZCU/BCU control unit 230 V AC (+15%/-20%) 0.45 R8i module: internal electronics 115 V AC (+15%/-20%) 230 V AC 50/60 R8i module: heating element (option +C183) 115 V AC R8i module: direct-on-line fan...
290 Technical data Fuse data Ferrules used with 400 V and 500 V units Power Rating Clearing I loss at I Class Example A rms Bussmann FWP-10A14F Bussmann FWP-15A14F 660 (IEC), Bussmann FWP-20A14F 700 (UL) Bussmann FWP-25A14F Bussmann FWP-32A14F Mersen 6,921 CP URQ 27x60/50 Mersen 6,921 CP URQ 27x60/63 Mersen 6,921 CP URQ 27x60/80...
Technical data 291 Flush-end fuse blocks used with 690 V units Power Rating Clearing I loss at I Class Example Size A rms Bussmann 170M3392 9000 1000 Bussmann 170M4388 11500 1000 Bussmann 170M4389 22500 1000 1250 (IEC), Bussmann 170M4390 46000 1000 1300 (UL)
The inverter control unit 293 The inverter control unit Contents of this chapter This chapter • describes the connections of the inverter control units used with ACS880 multidrive modules • contains the specifications of the inputs and outputs. General The ZCU-14 control unit is used with inverter module frame sizes R1i…R4i, R6i and R7i, while the ZCU-12 unit is used with frame size R5i.
294 The inverter control unit Layout and connections ZCU-12 layout and connections Description Analog inputs X202 Analog outputs X208 Digital inputs XDIO Digital input/outputs X205 XD24 Start interlock connection (DIIL) and +24 V output XD2D Drive to drive link XPOW External power input XRO1...
The inverter control unit 295 ZCU-14 layout and connections Description XPOW External power input X202 XRO1 Analog inputs Analog outputs XRO2 XD2D Drive to drive link XRO1 Relay output RO1 XRO3 XRO2 Relay output RO2 XRO3 Relay output RO3 XPOW XD24 Start interlock connection (DIIL) and +24 V output...
296 The inverter control unit BCU layout and connections Description I/O terminals (see following diagram) SLOT 1 I/O extension, encoder interface or fieldbus adapter module connection. (This is the sole location for an FDPI-02 diagnostics and panel interface.) SLOT 2 I/O extension, encoder interface or fieldbus adapter module connection SLOT 3...
Page 297
The inverter control unit 297 Description Analog inputs Analog outputs Digital inputs, Digital input interlock (DIIL) XRO3 XDIO Digital input/outputs XD24 XPOW XD2D Drive-to-drive link XD24 +24 V output (for digital inputs) XRO2 XETH Ethernet port (eg. for PC communication) XDIO XPOW External power input...
298 The inverter control unit Default I/O connection diagram (ZCU) Relay outputs XRO1…XRO3 Ready 250 V AC / 30 V DC Running 250 V AC / 30 V DC Faulted(-1) 250 V AC / 30 V DC Fault External power input XPOW 24 V DC, 2 A min.
Page 299
The inverter control unit 299 Notes: The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5 … 2.5 mm (24…12 AWG). The torque is 0.5 N·m (5 lbf·in). Current [0(4)…20 mA, R = 100 ohm] or voltage [0(2)…10 V, R >...
300 The inverter control unit Default I/O connection diagram (BCU) Drive-to-drive link XD2D Drive-to-drive link BGND Shield RS485 connection X485 Not in use BGND Shield Relay outputs XRO1…XRO3 Ready 250 V AC / 30 V DC Running 250 V AC / 30 V DC Fault Faulted(-1) 250 V AC / 30 V DC...
The inverter control unit 301 Notes: The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5 … 2.5 mm (24…12 AWG). The torque is 0.5 N·m (5 lbf·in). See section Drive-to-drive link (page 303). See chapter The Safe torque off function (page 309).
302 The inverter control unit used at one end, leave that end of the shield unconnected. See the firmware manual for parameter settings. +24VD 3.3 nF > 630 V AC WARNING! As the inputs pictured above are not insulated according to IEC 60664, the connection of the motor temperature sensor requires double or reinforced insulation between motor live parts and the sensor.
The inverter control unit 303 DIIL input The DIIL input can used for the connection of safety circuits. By default, the input is parametrized to stop the unit when the input signal is lost. Drive-to-drive link The drive-to-drive link is a daisy-chained RS-485 transmission line that allows basic master/follower communication with one master drive and multiple followers.
The BCU-x2 has an on-board data logger that collects real-time data from the inverter module power stages to help fault tracing and analysis. The data is stored onto the SDHC memory card inserted into the SD CARD slot and can be analyzed by ABB service personnel.
The inverter control unit 305 Control unit connector data Power supply Connector pitch 5 mm, wire size 2.5 mm (XPOW) 24 V (±10%) DC, 2 A External power input. Two supplies can be connected to BCU for redundancy. Relay outputs RO1…RO3 Connector pitch 5 mm, wire size 2.5 mm (XRO1…XRO3) 250 V AC / 30 V DC, 2 A...
Page 306
306 The inverter control unit Analog outputs AO1 and AO2 Connector pitch 5 mm, wire size 2.5 mm (XAO) 0…20 mA, R < 500 ohm load Frequency range: 0…300 Hz (ZCU), 0…500 Hz (BCU) Resolution: 11 bit + sign bit Inaccuracy: 2% of full scale range Drive-to-drive link Connector pitch 5 mm, wire size 2.5 mm...
Page 307
The inverter control unit 307 Ground isolation diagram (ZCU) XPOW +24VI +VREF -VREF AGND AI1+ Common mode voltage between AI1- AI2+ channels +30 V AI2- AGND AGND XD2D BGND XRO1, XRO2, XRO3 XD24 DIIL +24VD DICOM +24VD DIOGND XDIO DIO1 DIO2 XSTO OUT1...
Page 308
308 The inverter control unit Ground isolation diagram (BCU) XPOW +24VI +24VI +VREF -VREF AGND AI1+ Common mode voltage between AI1- each AI input and AGND is AI2+ AI2- +30 V AGND AGND XD2D BGND SHIELD XRO1, XRO2, XRO3 XD24 +24VD DICOM +24VD...
The Safe torque off function 309 The Safe torque off function Contents of this chapter This chapter describes the Safe torque off (STO) function of the inverter and gives instructions for its use. Description The Safe torque off function can be used, for example, to construct safety or supervision circuits that stop the inverter in case of danger (such as an emergency stop circuit).
310 The Safe torque off function Standard Name IEC 61508-1:2010 Functional safety of electrical/electronic/programmable electronic safety- related systems – Part 1: General requirements IEC 61508-2:2010 Functional safety of electrical/electronic/programmable electronic safety- related systems – Part 2: Requirements for electrical/electronic/programmable electronic safety-related systems IEC 61511-1:2016 Functional safety –...
The Safe torque off function 311 Cable types and lengths • Double-shielded twisted-pair cable is recommended. • Maximum cable lengths: • 30 m (100 ft) between activation switch [K] and inverter control unit. • 60 m (200 ft) between multiple inverter units •...
312 The Safe torque off function Single inverter unit (internal power supply) Dual-channel connection Inverter unit Control unit OUT1 +24 V SGND Control logic UDC+ T1/U, T2/V, T3/W UDC– Single-channel connection Inverter unit Control unit OUT1 +24 V SGND Notes: •...
The Safe torque off function 313 Frame n×R8i inverter unit (internal power supply) WARNING! Frame R8i inverter modules are as standard delivered with a jumper wire set that supplies 24 V from connector X53 to connector X52. The jumper wire set must be removed before wiring the Safe torque off circuit.
314 The Safe torque off function Multiple inverter units (internal power supply) Inverter unit Control unit XSTO OUT1 +24 V SGND Inverter unit Control unit XSTO OUT1 SGND Inverter unit Control unit XSTO OUT1 SGND...
The Safe torque off function 315 Multiple inverter units (external power supply) Inverter unit 24 V DC – Control unit XSTO OUT1 +24 V SGND Inverter unit Control unit XSTO OUT1 SGND Inverter unit Control unit XSTO OUT1 SGND...
316 The Safe torque off function Operation principle 1. The Safe torque off activates (the activation switch is opened, or safety relay contacts open). 2. The STO inputs on the inverter control unit de-energize. 3. The control unit cuts off the control voltage from the inverter IGBTs. 4.
Page 317
The Safe torque off function 317 Action Stop the inverter (if running), switch the input power off and isolate the inverter from the power line by a disconnector. Check the Safe torque off circuit connections against the wiring diagram. Close the disconnector and switch the power on. Test the operation of the STO function when the motor is stopped.
318 The Safe torque off function 1. Open the activation switch, or activate the safety functionality that is wired to the STO connection. 2. STO inputs on the inverter control unit de-energize, and the inverter control unit cuts off the control voltage from the inverter IGBTs. 3.
See the inverter firmware manual for the indications generated by the inverter, and for details on directing fault and warning indications to an output on the control unit for external diagnostics. Any failures of the Safe torque off function must be reported to ABB.
320 The Safe torque off function Safety data The safety data for the Safe torque off function is given below. Note: The safety data is calculated for redundant use, and does not apply if both STO channels are not used. = 20 MTTF Lifetime...
The Safe torque off function 321 Abbreviations Abbr. Reference Description Cat. EN ISO 13849-1 Classification of the safety-related parts of a control system in respect of their resistance to faults and their subsequent behavior in the fault condition, and which is achieved by the structural arrangement of the parts, fault detection and/or by their reliability.
The internal brake choppers of frame R1i…R4i inverter modules can be used for resistor braking of other modules. Brake resistors are available from ABB as add-on kits and must be installed in separate cubicles; contact your local ABB representative for details.
Restrictions • Internal brake choppers are only available for frame R1i…R4i, ACS880-104-xxxxx-3 and ACS880-104-xxxxx-5 inverter module types. • The maximum number of modules doing the braking is 12 frame R1i…R2i modules or 6 frame R3i…R4i modules, ie. the number of modules that can be mounted into a 800 mm wide Rittal TS 8 cubicle.
The ratings table (page 331) lists an example brake resistor for each inverter type. These resistors are available from ABB. When sourcing a resistor from a third party, make sure that: 1. The resistance of the custom resistor is greater or equal than the minimum allowed resistance: R >...
This is essential for safety since the inverter module may not be able to break the current if the chopper remains conductive in a fault situation. An example wiring diagram is shown below. ABB resistors are equipped with a thermal switch (1) inside the resistor assembly as standard. The switch indicates overtemperature and overload.
Resistor braking using frame R1i…R4i inverter modules 329 Protecting the resistor cable against short circuit The DC fuses of the inverter module will also protect the resistor cable if the cable is identical with the inverter input cable. Mechanical installation All brake resistors must be installed outside the drive.
Match the brake chopper operating limits of all braking inverters. You will need to enter a service-level pass code into parameter 96.02 to access the limit parameters. To obtain the pass code, contact your local ABB representative. • Stop all inverters of the drive system (even those not used for braking) if any are running.
Resistor braking using frame R1i…R4i inverter modules 331 Technical data Ratings Output ratings Brake resistor example Inverter unit type brcont brmax Type ACS880-104-… = 400 V 004A8-3 JBR-01 (Danotherm 006A0-3 CAR 155 D T 414 120R) 008A0-3 JBR-03 (Danotherm 0011A-3 CAR 200 D T 415 80R) 0014A-3 10.0...
Dimension drawings 335 Dimension drawings Contents of this chapter This chapter contains dimension drawings of the ACS880-104 inverter modules as well as auxiliary components. Dimensional drawings of most installation accessories are available from ABB on request.
348 Dimension drawings Control electronics ZCU-14 control unit Note: The control cable grounding plate can be attached to either top or bottom edge of the control unit.
Dimension drawings 351 DC fuses and fuse bases Fuse, 14 × 51 mm 14.3 mm (0.563”) 50.8 mm (2.000”) 15.5 mm (0.610”) Mersen US141 (Z331153F) fuse disconnector (for 14 × 51 mm fuses) ...
354 Dimension drawings DC fuse blocks for frames R5i…R8i (Bussmann) 690 V fuses (as used with 400 and 500 V units) Size A (mm) B (mm) D (mm) E (mm) G (mm) H (mm) 1000…1250 V fuses (as used with 690 V units) Size A (mm) B (mm)
Dimension drawings 367 OHB_ switch handles Note: The drawings are not to scale. OHB65J6, OHB125J12, OHB145J12 Handle type L (mm) B (mm) Notes OHB65J6 6 × 6 Used with OS_, OT200_ OHB125J12 12 × 12 Used with OT400_ OHB145J12 12 ×...
368 Dimension drawings OHB274J12 The drilling pattern is the same as OHB65/125/145. Handle type L (mm) Shaft (mm) Notes Used with OT1200U22, OT1600E22 and OHB274J12 12 × 12 OT2500E22 OA1G10/OA3G01 auxiliary contact blocks 2×0.75…2.5 mm (2×18…14 AWG) 0.8 N·m (7 lb.in) Pozidriv M3.5 Form 2...
Circuit diagrams 379 Circuit diagrams Contents of this chapter This chapter contains connection diagram examples for the whole inverter unit. Note: By default, the Safe torque off (STO) function is not in use, and has been bridged at the factory as shown in the diagrams. For information on implementing the function, see chapter The Safe torque off function (page 309).
380 Circuit diagrams Component designations used in the diagrams Frames R1i…R5i • R1i…R4i: see page • R5i: see page 386. Designation Component A41.x ZCU control unit FDPI diagnostics and control panel interface. For constructing a panel bus between inverter modules without front cover (see page 167). DPMP-01 panel mounting platform kit (to be ordered separately) ACS-AP-x control panel F10.x...
Circuit diagrams 381 Frame R7i See page 391. Designation Component FDPI diagnostics and control panel interface. For constructing a panel bus between inverter modules without front cover (see page 167). DPMP-01 panel mounting platform kit (to be ordered separately) ACS-AP-x control panel ZCU control unit F11.x...
DC SWITCH STATUS R1i 4mm2 BETATHERM FOR INVERTER 2 FOR INVERTER N R2i 10mm2 BETATHERM R3i 16mm2 BETATHERM R4i 35mm2 BETATHERM 29.12.2016 Vanin Oleg ACS880-104 Circuit Diagram 29.12.2016 Asikainen Mika INU Frames R1i-R4i Main Circuit, ZCU-14 Control Unit 1/2 3AXD10000016758 ABB Drives...
DC SWITCH STATUS -X103 FOR INVERTER 1 FOR INVERTER 3 DC SWITCH STATUS DC SWITCH STATUS FOR INVERTER 2 FOR INVERTER N 29.12.2016 Vanin Oleg ACS880-104 Circuit Diagram 29.12.2016 Asikainen Mika INU R5i Main Circuit, ZCU-12 Control Unit 1/2 3AXD10000332272...
020/14G ;HEAT.1:N =-X53.1 GND BCON 24VDC BCON 24 VDC ;A41:V1R 040/4K ;A41:V1T ;I1V60 ;I1V50 001/4E DC FAN AC FAN FAN BOX DC FAN HEATER 05.01.2017 Vanin Oleg ACS880-104-0760A-3+C183 Circuit Diagram 05.01.2017 Asikainen Mika 1xR8i INU Module connections 3AXD10000077658 ABB Drives...
;A41:V1R ;A41:V2R 040/4K 040/5K ;A41:V1T ;A41:V2T DC FAN AC FAN DC FAN AC FAN FAN BOX FAN BOX HEATER HEATER DOL FAN DOL FAN 29.12.2016 Vanin Oleg ACS880-104-1150A-5+C183+C188 Circuit Diagram 29.12.2016 Asikainen Mika 2xR8i INU Modules connections 3AXD10000407765 ABB Drives...
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
Page 404
Contact us www.abb.com/drives www.abb.com/drivespartners 3AUA0000104271 Rev G (EN) 2017-01-16...