Table of contents 5 Table of contents 1 Safety instructions Contents of this chapter ................Use of warnings and notes ............... ATEX-certified motor thermal protection functions ..........Electrical safety precautions ..............2 Introduction Contents of this chapter ................Applicability ..................Target audience ..................
Page 6
6 Table of contents Drive / inverter ..................Switching frequency limitation ..............Reset method and status indications ............31.22 STO indication run/stop ............Motor overtemperature indication ............31.11 Fault reset selection ..............Other recommended settings ..............FSO module ..................General parameters ................Parameters for the STO function .............
Safety instructions 7 Safety instructions Contents of this chapter This chapter contains the safety instructions which you must obey when you install, operate and do maintenance on the safety functions of a drive. Use of warnings and notes Warnings tell you about conditions which can cause injury or death, or damage to the equipment.
Page 8
8 Safety instructions required with application of Ex motors in Zone 1/21 (equipment category 2) or Zone 2/22 (equipment category 2 or 3). WARNING! Obey the safety instructions of the drive. If you ignore them, injury or death, or damage to the equipment can occur. This manual does not contain the complete safety instructions of the drive.
Safety instructions 9 Electrical safety precautions These electrical safety precautions are for all personnel who do work on the drive, motor cable or motor. WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. If you are not a qualified electrical professional, do not do installation or maintenance work.
Page 10
10 Safety instructions 6. Install temporary grounding as required by the local regulations. 7. Ask the person in control of the electrical installation work for a permit to work.
Introduction 11 Introduction Contents of this chapter This chapter contains information on the manual and gives other general information for the reader. Applicability This manual is applicable to ACS880 drives, drive modules and inverter modules with the ATEX-certified Safe disconnection function (option +Q971). Target audience The manual is intended for people who install, start-up, use and service the ATEX-certified Safe disconnection function (option +Q971) of the drive.
EN/IEC 60079 series. Exclusion of liability ABB is not responsible for the implementation, verification and validation of the overall safety system. It is the responsibility of the system integrator (or other party) who is responsible for the overall system and system safety.
Later in this manual, the term “drive” is used to refer to drives, drive modules and inverter modules. Related manuals Manual Code Drive hardware ACS880-01 drives (0.55 to 250 kW) hardware manual 3AUA0000078093 ACS880-04 drive modules (200 to 710 kW, 300 to 700 hp) hardware manual 3AUA0000128301 ACS880-04 single drive module packages hardware manual 3AUA0000138495...
Page 14
Delivered with the drive You can find manuals and other product documents in PDF format on the Internet. See Document Library. For manuals not available in the Document library, contact your local ABB representative. For additional ABB safety information and solutions visit http://www.abb.com/safety.
Implementing a motor thermal protection circuit 15 Implementing a motor thermal protection circuit Contents of this chapter This chapter contains instructions on implementing an ATEX-compliant motor thermal protection circuit using the ATEX-certified Safe disconnection function (option +Q971) of the drive. Overview You can implement the motor thermal protection circuit with or without an FSO safety functions module.
16 Implementing a motor thermal protection circuit The STO stops the motor (if running) and prevents the motor start. You must select the stop category according to the system risk assessment. As an alternative, you can use the FPTC-02 ATEX-certified thermistor protection module, Ex II (2) GD (option +L537+Q971) to implement the ATEX-compliant motor thermal protection function.
Implementing a motor thermal protection circuit 17 ■ Connection diagram The diagram below shows the connections. The system integrator must get the components and do the installations drawn outside the drive border line. 24 … 240 V AC / DC XSTO +24 V Ex M...
18 Implementing a motor thermal protection circuit One-channel connection to drive STO terminals ■ General This section describes an implementation of the ATEX-compliant motor thermal protection circuit: • The circuit uses the ATEX-certified Safe disconnection function (option +Q971) of the drive.
Implementing a motor thermal protection circuit 19 ■ Connection diagram The diagram below shows the connections. The system integrator must get the components and do the installations drawn outside the drive border line. 24 … 240 V AC / DC +24VD XSTO +24 V...
20 Implementing a motor thermal protection circuit One-channel or two-channel connection to an FSO module ■ General This section describes two implementations of the ATEX-compliant motor thermal protection circuit with an FSO module: • The circuit uses the ATEX-certified Safe disconnection function (option +Q971) of the drive.
Implementing a motor thermal protection circuit 21 Make sure that at least one of these indications generates a fault if: • the protection relay does not contain a manual reset, and • the FSO module is not configured for an STO manual reset. ■...
22 Implementing a motor thermal protection circuit ■ Connection diagram (one-channel connection) The diagram below shows the wiring of the one-channel connection. The system integrator must get the components and do the installations drawn outside the drive border line. 24 … 240 V AC / DC 24 V / 1 A 1 2 3 4 X111...
(motor) and the drive control unit as required by IEC 61800-5-1. The insulation of the temperature sensor in the Ex motor and the insulation of the protection relay form the insulation of the whole circuit. All Ex motors manufactured by ABB have basic insulation between the main circuit and the temperature sensor.
Page 24
24 Implementing a motor thermal protection circuit Note: ABB recommends to use shielded twisted-pair cable for the connection between the protection relay and drive control unit when: • the drive is not installed into a cabinet, or • the drive is not installed into the same cabinet as the protection relay.
For more information, see the drive firmware manual. For Ex motors supplied by other motor manufacturers, contact the motor manufacturer for the correct value and your local ABB representative for instructions on how to make the parameter setting in the drive.
Select the correct source of an external fault reset signal with parameter 31.11 Fault reset selection. ■ Other recommended settings ABB recommends that you also set these parameters to improve the safety of the application: • minimum and maximum speeds (parameter group 30) •...
Parameter settings 27 FSO module If you use an FSO module in the safety system configuration, set the parameters according to the system requirements. Example values are shown in this section. You need the Drive composer pro PC tool to set the FSO module parameters. You also need a password to be able to download the configuration to the FSO module from Drive composer pro.
Page 28
28 Parameter settings Index Name Example value Description FSOGEN.41 Power-up acknow- Automatic Sets the power-up acknowledgement method of the ledgement FSO module. Automatic: You do not need to push a reset button after switching on the FSO module. The FSO module gener- ates the acknowledgement signal automatically after the power-up.
Parameter settings 29 Index Name Example value Description FSOGEN.62 STO indication safety Fault Sets the type of the event that the FSO module gener- limit ates and sends to the drive for limit hits during ramp and time monitoring of safety ramps SAR0 and SAR1. STO function: The value has no effect.
Page 30
30 Parameter settings Index Name Example value Description STO.14 Time to zero speed 2000 ms Sets the time that is needed to coast the motor to a with STO and modoff standstill from maximum process speed. If this time is not known, it can be measured with Drive composer pro PC tool when an encoder is used for motor control (otherwise you have to make sure that the motor shaft...
Parameter settings 31 ■ Parameters for the SSE function These parameters are related to the Safe stop emergency (SSE) function of the FSO module. The safety functions described in this manual do not use this function, but the FSO module can activate the SSE function in internal fault situations.
Page 32
32 Parameter settings Index Name Example value Description SS1.14 SS1-t delay for STO 20000 ms Sets the monitoring delay after which the FSO module activates the drive STO and SBC at the latest, if the motor speed has not gone below the zero speed limit (parameter FSOGEN.51 or FSOGEN.52) yet.
Parameter settings 33 Index Name Example value Description SBC usage SBC.15 SSE/SS1 SBC speed 0.0 rpm Sets the absolute speed below which the FSO module activates the brake (SBC) while ramping. 0.0 rpm: The feature is not in use. In the safety functions described in this manual, this feature is not used.
34 Parameter settings Index Name Example value Description 91.11 Module 1 type FSE-31 Sets the type of the safety pulse encoder interface module 1. 91.12 Module 1 location Sets the slot in which the safety pulse encoder interface module 1 is located. 92.01 Encoder 1 type HTL1...
Technical data 35 Technical data Contents of this chapter This chapter contains a list of related standards and directives, safety data and the drive ATEX certificates and Declaration of Conformity documents. Related standards and directives EN 50495:2010 Safety devices required for the safe functioning of equipment with respect to explo- sion risks IEC 61508:2010 Functional safety of electrical/electronic/programmable electronic safety-related...
36 Technical data ■ Drive/inverter module STO function and an FSO module The table below lists the safety data for the Safe disconnection function, including the safety data of the FSO module, the FSE-31 module (optional) and the safety data of worst case ACS880 Safe torque off (STO).
Technical data 37 One-channel digital input Customer motor sensor(s) Customer protection relay(s) FSO module FSE module (optional) Drive STO Two-channel digital input Customer motor sensor(s) Customer protection relay(s) FSO module FSE module (optional) Drive STO ■ Response times The response time of the Safe disconnection (STO) function is < 50 ms for all ACS880 drives.
38 Technical data Markings of the drive/inverter module CE marking with Notified Body identification: The manufacturer declares that the product conforms with ATEX Product Directive 2014/34/EU. Notified Body: Eurofins Expert Services (Formerly VTT Expert Services, now part of the Eurofins Group). Specific marking of explosion protection Equipment group II: Product for surface industry (other than mining applications) Equipment category 2.
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.