hit counter script
Download Print this page

Honeywell ADEMCO 5819 Installation And Setup Manual page 2

Shock processor transmitter

Advertisement

WIRING CONNECTIONS
With the battery still not inserted, connect the shock processor
loop (if used) to the unit's loop TB1 terminals (see Detail "B").
The contact loops must use closed circuit devices. TB2 can be
used for normally closed contacts.
Note: If the contact loops are not used, no connection is needed
across their terminals.
"ENROLLING" THE TRANSMITTER SERIAL NUMBER
Each 5819 Shock Processor has its own unique serial number
permanently assigned during manufacture.
transmitter also has a distinct "loop" number that must be input to
the control panel during installation. Assign each to an individual
zone and designate the Input Type as "RF" (Supervised RF).
The serial number can be input by one of the following methods:
"Enrolled" by transmitting from the device during zone
programming (pressing the tamper switch, shorting any loop,
etc.).
Entered through the keypad at the "Input S/N" or "Transmit
Now" prompt during manual zone programming.
Entered through COMPASS Downloading Software and
downloaded to the control.
When programming the 5819 transmitter's serial number at
the control panel, do the following:
1. At the "Input Type" prompt, enter "3" for RF (Supervised RF).
2. When prompted for the loop number, enter the input loop you
are using (see Diagram 2).
installation instructions for specific programming procedures.
For the latest warranty information, please go to:
The user shall not make any changes or modifications to the equipment unless authorized by the
Installation and Setup Guide or User Guide.
This device complies with Part 15 of the FCC Rules and RSS210 of the Industry Canada. Operation
is subject to the following two conditions: (1) This device may not cause harmful interference (2) This
device must accept any interference received, including interference that may cause undesired
operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS 210 des Industries Canada.
Son fonctionnement est soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer
d'interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue y compris les
interférences causant une réception indésirable.
ÊN7491V5xŠ
N7491V5
3/09 Rev. B
Each input of the
See the control panel's
http://www.security.honeywell.com/hsc/resources/wa/index.html
FCC AND INDUSTRY CANADA STATEMENT
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Honeywell International Inc.
BATTERY INSTALLATION/REPLACEMENT
1.
Remove the transmitter's cover as described in Mounting,
Step 1.
2.
Observe correct polarity and insert the battery provided into
the battery holder (see Diagram 2).
3.
Replace the cover, engage the hooks along one edge, and
snap shut.
Do not bend the antenna.
Note:
Replace with 3V, 1300mAH Lithium battery only:
Panasonic CR123A, Duracell DL123, DL123A, or
ADEMCO 466.
BATTERY CAUTION: Risk of fire, explosion, and burns. Do not
recharge, disassemble, heat above 212°F (100°C), or incinerate.
Dispose of used batteries promptly. Keep away from children.
UNIT DIMENSIONS
4.8" H x 1.5" W x 1" D
Regular maintenance and inspection (at least annually by the
installer) and frequent testing by the user are vital to continuous
satisfactory operation of any alarm system. The installer should
assume the responsibility of developing and offering a regular
maintenance program to the user, as well as acquainting the user
with the proper operation and limitations of the alarm system and
its component parts. Recommendations must be included for a
specific program of frequent testing (at least weekly) to insure the
system's operation at all times.
Copyright
2009
TO THE INSTALLER

Advertisement

loading