Indoor Unit Installation
• Select and mark the position for fixing bolts.
• Drill the hole for set anchor on the face of ceiling.
CAUTION : Tighten the nut and bolt
to prevent unit falling.
Wiring Connection
Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor
unit respectively.
<M1 Chassis>
Terminal Block Indoor
1(L)
2(N)
INDOOR POWER INPUT
<M2/M3 Chassis>
Terminal Block Indoor
Terminal Block Indoor
1(L)
INDOOR POWER INPUT
WARNING : Make sure that the screws of the terminal are free from looseness.
Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump
model, put the 0.75mm
the other boss of the control panel.
CAUTION : The Power cord connected to the unit should be selected according
to the following specifications.
Outdoor unit Indoor unit
Terminal Block Indoor
3
4
SODU SODU
Terminal Block Indoor
2(N)
3
4
2
cable(thinner cable) on the clamp and tighten it with a plastic clamp to
• Insert the set anchor and washer onto the sus-
pension bolts for locking the suspension bolts
on the ceiling.
• Mount the suspension bolts to the set anchor firmly.
• Secure the installation plates onto the suspen-
sion bolts (adjust level roughly) using nuts,
washers and spring washers.
Old building
1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts