HNET
Output Zones
Siemens Industry, Inc.
Building Technologies Division
S2-SW1: Set to ON if Zone 1 usage = Leased Line, Alarm Default only
S2-SW2: Set to ON if Zone 2 usage = Leased Line, Alarm Default only
S2-SW3: Set to ON if Zone 3 usage = Leased Line, Trouble Default only
S2-SW4: Set to OFF: Not Used
S3, Reset Switch: Momentarily Closed switch that when pressed will initiate a hard
reset to the ZIC-4A (similar to a cold boot).
S4, S6, S7 Network Address Switch: Set the three-digit HNET network address for
the ZIC-4A using the three rotary dial address switches located near the bottom of
the front panel. (Refer to Figure 1 for the location of the switches.) The address for
the ZIC-4A must be the same as the address selected for it in the Zeus Programming
Tool. To set the address, turn the pointers on each of the three dials to the numbers
for the selected address. For example, if the address is 123, set the pointer for the
HUNDREDS dial to "1" , set the pointer for the TENS dial to "2" , and set the pointer for
the ONES dial to "3" . The range of allowable addresses is from 001 to 251 (leading
zeros must be used).
S5 Input Power Select: This switch selects the source of voltage input to power the
ZIC-4A. BP Power indicates that the input is derived from the backplane of the CC-2/
CC-5 and EXT Power indicates that the input is derived from E5/E11 terminal of the
CC-2/CC-5, normally connected to non-power limited output of the PSC-12/PSX-12. It
is important to take into account the source of the voltage during battery calculations.
P1, P2, P3, P4 Shunt Headers, NAC Input Supervision Enable: These headers
select the NAC input zone supervision. If usage application is set for speaker func-
tion, place the shunt jumpers of the corresponding zone between 1—2 and between
5—6, otherwise place the shunt jumpers between 1—3 and 4—6.
P1 selects NAC input supervision for Zone 1
P2 selects NAC input supervision for Zone 2
P3 selects NAC input supervision for Zone 3
P4 selects NAC input supervision for Zone 4
The ZIC-4A can be configured for the following usages:
Standard NAC Zone - Configurable as the following NAC zones:
Steady
Zone Coding
March Time 120
March Time 30
Releasing Zone - For release of FM-200, Halon, Pre-action & Deluge Sprinklers for
Canada or USA. Releasing zone requires an REL -EOL module for proper wire supervision.
Municipal Tie - Configurable as a supervised connection to municipal tie. Municipal
Tie usage application requires the LLM-1 interface module.
Leased Line - Configurable as a connection to a remote monitoring system. Leased
Line usage application requires LLM-1 interface module.
Bell Follower Primary - Configurable as a Bell Follower Primary (Zone 1 only).
Bell Follower Secondary - Configurable as a Bell Follower Secondary.
Strobe (Synchronized or Unsynchronized)
Temporal Code
Temporal 4, when used with Audible Base SBGA-34
March Time 60
Horn / Strobe
6
6
5
4
3
2
1
P/N 315-033050-15