Appendix
A.2 Data tables
A.2.17

Maximum pointer

Only read access (r) to the maximum pointers is possible via Function Codes 03 and 04. The
data table "Maximum pointers" is not supported by the 3RW52 soft starter.
Register Byte
Data format
Address high / low
0x9001
high
Unsigned8
low
Unsigned8
0x9002
high
Unsigned8
0x9003
high
Unsigned8
low
Unsigned8
0x9004
high
Unsigned8
0x9005
high
Unsigned16
0x9006
high
Unsigned16
0x9007
high
Signed32
0x9009
high
Signed32
0x900B
high
Signed32
0x900D
high
Signed32
0x900F
high
Signed32
0x9011
high
Signed32
0x9013
high
Signed32
0x9015
high
Unsigned16
0x9016
high
Unsigned16
0x9017
high
Unsigned16
0x9018
high
Unsigned16
0x9019
high
Unsigned16
0x901A
high
Unsigned16
0x901D
low
Unsigned8
0x901E
high
Unsigned8
low
Unsigned8
0x901F
high
Unsigned32
0x9021
high
Unsigned32
0x9023
high
Unsigned32
0x9025
high
Unsigned32
0x9027
high
Unsigned32
0x902B
high
Signed32
0x902D
high
Signed32
0x902F
high
Signed32
0x9031
high
Signed32
Supported by SIRIUS 3RW55 soft starter
1)
88
Maximum pointer
Minimum phase current I L1 (%)
Phase current I L2 min (%)
Phase current I L3 min (%)
Maximum phase current I L1 (%)
Phase current I L2 max (%)
Phase current I L3 max (%)
Maximum trigger current
Number of motor overload trips
Maximum trigger current
Minimum phase current I L1 (rms)
Phase current I L2 min (rms)
Phase current I L3 min (rms)
Maximum phase current I L1 (rms)
Phase current I L2 max (rms)
Phase current I L3 max (rms)
Line-to-line voltage U L1-L2 min
Line-to-line voltage U L2-L3 min
Line-to-line voltage U L3-L1 min
Line-to-line voltage U L1-L2 max
Line-to-line voltage U L2-L3 max
Line-to-line voltage U L3-L1 max
Maximum switching element heating
Minimum line frequency
Maximum line frequency
Operating hours - motor current =
18 ... 49.9% x Ie
Operating hours - motor current =
50 ... 89.9% x Ie
Operating hours - motor current =
90...119.9% x Ie
Operating hours - motor current =
120...1000% x Ie
Operating hours - device
Starting current I max (rms)
Starting current I L1 max (rms)
Starting current I L2 max (rms)
Starting current I L3 max (rms)
Range of values
Increment 3RW55
0 ... 796.9 %
3.125 %
0 ... 796.9 %
3.125 %
0 ... 796.9 %
3.125 %
0 ... 796.9 %
3.125 %
0 ... 796.9 %
3.125 %
0 ... 796.9 %
3.125 %
0 ... 1000 %
3.125 %
0 ... 65 535
1
-20 000 ... 20 000 A
0.01 A
-20 000 ... 20 000 A
0.01 A
-20 000 ... 20 000 A
0.01 A
-20 000 ... 20 000 A
0.01 A
-20 000 ... 20 000 A
0.01 A
-20 000 ... 20 000 A
0.01 A
-20 000 ... 20 000 A
0.01 A
0 ... 1 500 V
0.1 V
0 ... 1 500 V
0.1 V
0 ... 1 500 V
0.1 V
0 ... 1 500 V
0.1 V
0 ... 1 500 V
0.1 V
0 ... 1 500 V
0.1 V
0 ... 250 %
1 %
0 ... 100 Hz
0.5 Hz
0 ... 100 Hz
0.5 Hz
0 ... 4 294 967 295 s
1 s
0 ... 4 294 967 295 s
1 s
0 ... 4 294 967 295 s
1 s
0 ... 4 294 967 295 s
1 s
0 ... 4 294 967 295 s
1 s
-20 000 ... 20 000 A
0.01 A
-20 000 ... 20 000 A
0.01 A
-20 000 ... 20 000 A
0.01 A
-20 000 ... 20 000 A
0.01 A
SIRIUS 3RW5 Modbus TCP communication module
Manual, 03/2018, A5E43676481002A/RS-AA/001
1)
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r