A.2.16
Statistic data
Only read access (r) to the statistical data is possible via Function Codes 03 and 04. The
data table "Statistic data" is not supported by the 3RW52 soft starter.
Register Byte
Data format
Address high / low
0x8C01
high
Unsigned8
0x8C02
high
Unsigned16
0x8C03
high
Unsigned32
0x8C05
high
Unsigned32
0x8C07
high
Unsigned32
0x8C09
high
Unsigned16
0x8C0B
high
Signed32
0x8C0D high
Signed32
0x8C0F
high
Unsigned32
0x8C11
high
Unsigned32
0x8C13
high
Unsigned32
0x8C15
high
Unsigned32
0x8C17
high
Unsigned32
0x8C1A
high
Unsigned16
0x8C1B
high
Unsigned16
0x8C1F
high
Unsigned32
0x8C21
high
Unsigned32
0x8C23
high
Unsigned32
0x8C25
high
Unsigned32
0x8C27
high
Unsigned32
0x8C3B
high
Unsigned64
0x8C3F
high
Unsigned64
0x8C43
high
Unsigned16
Supported by SIRIUS 3RW55 soft starter
1)
SIRIUS 3RW5 Modbus TCP communication module
Manual, 03/2018, A5E43676481002A/RS-AA/001
Statistic data
Phase current max (%)
Last tripping current IA (%)
Operating hours - device
Number of starts motor CW
Number of starts motor CCW
Number of motor overload trips
Maximum phase current (rms)
Last tripping current IA (rms)
Operating hours - motor
Operating hours - motor current =
18 ... 49.9% x Iemax
Operating hours - motor current =
50 ... 89.9% x Iemax
Operating hours - motor current =
90 ... 119.9% x Iemax
Operating hours - motor current =
120 ... 1000% x Iemax
Number of switching element overload
trips
Number of bypass overload trips
Number of electrical braking stops
Number of starts output 1
Number of starts output 2
Number of starts output 3
Number of starts output 4
Active energy import (total)
Active energy export (total)
Last real starting time
Range of values
Increment 3RW55
0 ... 796.9 %
3.125 %
0 ... 1 000 %
3.125 %
0 ...
1 s
4 294 967 295 s
0 ... 4 294 967 295
1
0 ... 4 294 967 295
1
0 ... 65 535
1
-20 000 ... 20 000 A 0.01 A
-20 000 ... 20 000 A 0.01 A
0 ...
1 s
4 294 967 295 s
0 ...
1 s
4 294 967 295 s
0 ...
1 s
4 294 967 295 s
0 ...
1 s
4 294 967 295 s
0 ...
1 s
4 294 967 295 s
0 ... 65 535
1
0 ... 65 535
1
0 ... 4 294 967 295
1
0 ... 4 294 967 295
1
0 ... 4 294 967 295
1
0 ... 4 294 967 295
1
0 ... 4 294 967 295
1
0 ...
1 Ws
4 294 967 295 Ws
0 ...
1 Ws
4 294 967 295 Ws
0 ... 1 000 s
0.1 s
Appendix
A.2 Data tables
1)
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
87