Configuring
6.2 Configuring the 3RW5 Soft Starter
6.2.3

IP parameters

All Modbus TCP devices are capable of using the TCP/IP protocol. Before the 3RW5 soft
starter can be addressed as a server by a client, it must have IP parameters. The IP
parameters of the 3RW5 soft starter must match the IP parameters in the configuration, in
order for the client to communicate.
IP parameters
● IP address
● Subnet mask
● Address of router
You will find the factory setting (default) of the IP parameters in the data table
"Communication parameters" (Page 99).
Static IP parameters
The IP parameters set in the 3RW5 soft starter are stored in the 3RW5 soft starter. The IP
parameters of the 3RW5 soft starter must match the IP parameters in the configuration.
Note
Restarting the communication interface
Any change in the IP parameters via SIRIUS Soft Starter ES (TIA Portal) requires a restart of
the communication interface.
A new start interrupts all Modbus TCP links and reestablishes them afterward.
MAC address
Via the MAC address, the 3RW5 communication module can be accessed via LAN. You can
read the MAC address on the front of the 3RW5 communication module or display it on the
3RW5 HMI High Feature.
Menu: "Parameter > Communication > Modbus TCP > MAC address"
44
SIRIUS 3RW5 Modbus TCP communication module
Manual, 03/2018, A5E43676481002A/RS-AA/001