Programming instructions
6.2 Extended instructions
ERROR
0
1
1
1
1
1
1
Condition codes for TRCV
ERROR
0
0
0
0
1
1
1
1
1
1
166
STATUS
Explanation
(W#16#...)
7002
Follow-on call (REQ irrelevant), job being processed: The operating system
accesses the data in the DATA send area during this processing.
8085
LEN parameter is greater than the largest permitted value.
8086
The ID parameter is not in the permitted address range
8088
LEN parameter is larger than the memory area specified in DATA
80A1
Communications error:
The specified connection was not yet established
The specified connection is currently being terminated. Transmission over
this connection is not possible.
The interface is being reinitialized.
80C3
Internal lack of resources: A block with this ID is already being processed in a
different priority class.
80C4
Temporary communications error:
The connection to the communications partner cannot be established at
this time.
The interface is receiving new parameters or the connection is currently
being established.
STATUS
Explanation
(W#16#...)
0000
New data accepted: The current length of the received data is shown in
RCVD_LEN.
7000
Block not ready to receive
7001
Block is ready to receive, receive job was activated.
7002
Follow-on call, receive job being processed: Data is written to the receive
area during this processing For this reason, an error could result in
inconsistent data in the receive area.
8085
The LEN parameter is greater than the largest permitted value, or you
changed the LEN or DATA parameter since the first call.
8086
The ID parameter is not in the permitted address range
8088
Receive area is too small: The ·Value LEN is greater than the receive area
specified by DATA.
80A1
Communications error:
The specified connection has not yet been established
The specified connection is currently being terminated. A receive job over
this connection is not possible.
The interface is receiving new parameters.
80C3
Internal lack of resources: A block with this ID is already being processed in a
different priority class.
80C4
Temporary communications error:
The connection to the partner cannot be established at the moment.
The interface is receiving new parameter settings or the connection is
currently being established.
S7-1200 Programmable controller
System Manual, 11/2009, A5E02486680-02