Technical specifications
A.3 Digital signal modules (SMs)
Technical Specifications
Model
Isolation groups
Current per common
Inductive clamp voltage
Switching delay
Lifetime mechanical (no load)
Lifetime contacts at rated load
Behavior on RUN to STOP
Number of outputs on simultaneously
Cable length (meters)
Wiring diagrams
SM 1223 DI 8 x 24 VDC, DQ 8 x Relay
6ES7 223-1PH30-0XB0
304
SM 1223 DI 8x24
SM 1223 DI 16x24
VDC, DQ 8xRelay
VDC, DQ
16xRelay
2
4
10A
8 A
--
10 ms max.
10,000,000 open/close cycles
100,000 open/close cycles
Last value or substitute value (default value 0)
8
16
500 shielded, 150 unshielded
SM 1223 DI 8x24
VDC, DQ 8x24
VDC
1
4 A
L+ minus 48 V, 1 W dissipation
50 μs max. off to on
200 μs max. on to off
--
--
8
SM1223 DI 16 x 24 VDC, DQ 16 x Relay
6ES7 223-1PL30-0XB0
S7-1200 Programmable controller
System Manual, 11/2009, A5E02486680-02
SM 1223 DI 16x24
VDC, DQ16x24
VDC
1
8 A
16