Technical specifications
A.4 Analog signal modules (SMs)
Analog output representation for voltage
Decimal
32767
32512
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32513
-32768
1
Analog output representation for current
Decimal
32767
32512
32511
27649
27648
20736
1
0
-1
-32512
-32513
-32768
1. In an overflow or underflow condition, analog outputs will behave according to the device
310
System
Hexadecimal
7FFF
7F00
7EFF
6C01
6C00
5100
1
0
FFFF
AF00
9400
93FF
8100
80FF
8000
. In an overflow or underflow condition, analog outputs will behave according to the device
configuration properties set for the analog signal module. In the "Reaction to CPU STOP"
parameter, select either: Use substitute value or Keep last value.
System
Hexadecimal
7FFF
7F00
7EFF
6C01
6C00
5100
1
0
FFFF
8100
80FF
8000
configuration properties set for the analog signal module. In the "Reaction to CPU STOP"
parameter, select either: Use substitute value or Keep last value.
Voltage Output Range
± 10 V
See note 1
Overflow
See note 1
Overshoot range
11.76 V
10 V
Rated range
7.5 V
361.7 μ V
0 V
-361.7 μ V
-7.5 V
-10 V
Undershoot range
-11.76 V
See note 1
Underflow
See note 1
Current Output Range
± 20 mA
See note 1
Overflow
See note 1
23.52 mA
Overshoot range
20 mA
Rated range
15 mA
723.4 nA
0 mA
Undershoot range
See note 1
Underflow
See note 1
S7-1200 Programmable controller