Minimum Allowable Clearance and Service Access Requirements
Proper clearance for the outdoor unit coil is critical for proper operation. When installing the outdoor unit, consider service, inlet and outlet,
and minimum allowable space requirements as illustrated in the diagrams below.
• Include enough space for airflow and for service access. If installing multiple outdoor units, avoid placing the units where the discharge of
one unit will blow into the inlet side of an adjacent unit.
• If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that the discharge air of the outdoor unit isn't restricted.
No obstacles to air circulation around the unit; keep proper distances from ceilings, fences, floor, walls, etc. (Install a fence to prevent
pests from damaging the unit or unauthorized individuals from accessing it.)
Single Zone High Efficiency Standard Wall Mount Outdoor Unit (9,000, 12,000, 18,000 Capacities) Service Access and
Allowable Clearances
Specific clearance requirements in the diagram below are for 9,000, 12000, 18,000 Btu/h capacities. Figure 32 shows the overall minimum
clearances that must be observed for safe operation and adequate airflow around the outdoor unit.
When placing the outdoor unit under an overhang, awning, sunroof or other "roof-like structure", observe the clearance requirements (as
shown in Cases 1 and 2) for height in relation to the unit. To have successful service access to the outdoor unit, see Figure 32 for minimum
spacing. When installing multiple outdoor units, see Cases 4 and 5 for correct spacing requirements.
If the outdoor unit is installed between standard and minimum clearances, capacity decreases approximately 10%.
Figure 28: Single Zone High Efficiency Standard Wall Mount 9,000, 12,000, 18,000 Capacity Outdoor Unit Service Access and Allowable Clearances
Diagram.
Case 1
A
B
Case 4
Table 28: Single Zone High Efficiency Standard Wall Mount 9,000, 12,000, 18,000 Outdoor Unit Service Access and Allowable Clearances Diagram
Legend.
Unit: Inch
Standard
Case 1
Minimum
Standard
Case 2
Minimum
Standard
Case 3
Minimum
Standard
Case 4
Minimum
Standard
Case 5
Minimum
PLACEMENT CONSIDERATIONS
Case 2
G
D
D
F
E
A
B
12
24
4
10
-
-
-
-
-
-
-
-
-
-
-
-
-
24
-
10
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Case 3
G
C
Case 5
B
B
C
D
-
12
-
4
20
-
14
-
20
12
14
4
-
12
-
4
-
12
-
4
Outdoor Unit
D
C
Do not place the unit where animals
and/or plants will be in the path of the warm
air, or where the warm air and/or noise will
disturb neighbors.
D
E
F
-
-
-
-
-
-
-
-
-
-
-
-
24
-
8
79
-
-
-
-
APPLICATION | 51
G
-
40
-
40
-
-
-
-
-
-