List of related manuals in English Drive manuals and guides Code (English) ACQ580 pump control program firmware manual 3AXD50000035867 ACQ580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware 3AXD50000044862 manual ACQ580-01 frames R1 to R5 quick installation and start- 3AXD50000044864...
Table of contents 3 Table of contents List of related manuals in English Frames R1 to R4 Ratings and fuses IEC ratings at UN = 230 V, 400 V and 480 V ........9 UN = 230 V .
Page 4
4 Table of contents UN = 480 V ............28 gG fuses .
Page 5
Providing feedback on ABB Drives manuals ........
Type Min. short- Input gG (IEC 60269) circuit current ACQ580-01- current Nominal Voltage ABB type current rating 60269 size 3-phase U = 230 V 04A7-2 25.0 2500.0 OFAF000H25 06A7-2 25.0 2500.0 OFAF000H25 07A6-2 25.0 2500.0 OFAF000H25 012A-2 12.0 25.0...
uR or aR fuses Type Min. short- Input uR or aR (DIN 43620 blade style) circuit current ACQ580 Nominal Voltage Bussmann IEC 60269 current -01- current rating type size 3-phase U = 230 V 04A7-2 120.0 40.0 460.0 170M1563 06A7-2 120.0 40.0 460.0...
Page 13
Type Min. short- Input uR or aR (DIN 43653 bolted tags) circuit current ACQ580 Nominal Voltage Bussmann IEC 60269 current -01- current rating type size 3-phase U = 400 or 480 V 02A7-4 170M1311 03A4-4 170M1311 04A1-4 170M1311 05A7-4 170M1311 07A3-4 170M1311 09A5-4...
EN – R1…R4 Quick installation guide This guide briefly describes how to install the drive for IEC use. For complete information on installation, see ACQ580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000044862 [English]). For start-up instructions, see chapter EN –...
The allowed operating temperature range of the drive is -15 to +50 °C (+5 to +122 °F). No condensation or frost is allowed. For more information on the ambient temperature and derating, see chapter Technical data in ACQ580-01 (0.75 to 250 kW) hardware manual (3AXD50000044862 [English]).
TN-S system. If you install the drive to another system, you may need to disconnect the EMC filter. See section Checking the compatibility with IT (ungrounded), corner-grounded delta, midpoint-grounded delta, and TT systems (for IEC) in ACQ580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000044862 [English]).
TN-S system. If you install the drive to another system, you may need to disconnect the varistor. See section See section Checking the compatibility with IT (ungrounded), corner-grounded delta, midpoint-grounded delta, and TT systems (for IEC) in ACQ580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000044862 [English]).
EN – R1…R4 Quick installation guide 19 Connect the power cables See figures (page 51), C2, D, E1, E2, F, G1, R1…R4 Figures H (page 53). 1. Remove the rubber grommets from the cable entry. Use symmetrical shielded cable for motor cabling. If the cable shield is the sole PE conductor for drive or motor, make sure that is has sufficient conductivity for the PE.
20 EN – R1…R4 Quick installation guide Connect the control cables See figures on page 53. It shows an example with one analog signal cable and one digital signal cable. Make the connections according to the default configuration in use. The default connections of the Water default configuration are shown in section Default I/O connections on page 21.
OUT1 Safe torque off. Factory connection. Both circuits OUT2 must be closed for the drive to start. See chapter The Safe torque off function in ACQ580-01 (0.75 SGND to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000044862 [English]). Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
22 EN – R1…R4 Quick installation guide Install optional modules, if any See chapter Electrical installation in ACQ580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000044862 [English]). Reinstall cover See figure on page 54. 1. Put the tabs on the inside of the cover top in their counterparts on the housing (1a) and then press the cover at the bottom (1b).
Single EU Declaration of conformity 3AXD10000497692. Person authorized to compile the technical file Name and address: Risto Mynttinen, Hiomotie 13, 00380 Helsinki, Finland. Helsinki 07.06.2019 Manufacturer representative: Tuomo Tarula Vice President, ABB Oy Document number 3AXD10000486283 Page 1 of 1...
-01- current 3-phase U = 230 V 089A-2 115A-2 3AXD00000586715.xls L Type Input ratings Output ratings Frame size ACQ580-01- 1-phase U = 230 V 089A-2 115A-2 3AXD00000586715.xls L Continuous current, no overloadability = 400 V Type Input Output ratings...
Page 28
= 480 V Type Input Output ratings Heat Air flow Frame ACQ580 rating dissipation size Max. Nominal use -01- current 3-phase U = 480 V 088A-4 1240 106A-4 1510 3AXD00000586715.xls L...
Type Min. short- Input gG (IEC 60269) circuit current ACQ580-01- current Nominal Voltage ABB type current rating 60269 size 3-phase U = 230 V 089A-2 1300 89.0 125.0 103000 OFAF00H125 115A-2 1300 115.0 125.0 103000 OFAF00H125 3-phase U...
EN – R5 Quick installation guide This guide briefly describes how to install the drive for IEC use. For complete information on installation, see ACQ580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000044862 [English]). For start-up instructions, see chapter EN –...
The allowed operating temperature range of the drive is -15 to +50 °C (+5 to +122 °F). No condensation or frost is allowed. For more information on the ambient temperature and derating, see chapter Technical data in ACQ580-01 (0.75 to 250 kW) hardware manual (3AXD50000044862 [English]).
TN-S system. If you install the drive to another system, you may need to disconnect the varistor. See section See section Checking the compatibility with IT (ungrounded), corner-grounded delta, midpoint-grounded delta, and TT systems (for IEC) in ACQ580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000044862 [English]).
Page 34
34 EN – R5 Quick installation guide WARNING! Do not install a drive with the ground-to-phase varistor connected to a system that the varistor is not suitable for. If you do, the varistor circuit can be damaged.
EN – R5 Quick installation guide 35 Connect the power cables See figures (page 56), R5 Figures F (page 57). 1. Attach the residual voltage warning sticker in the local language next to the control board. 2. Remove the shroud on the power cable terminals by releasing the clips with a screwdriver and pulling the shroud out.
36 EN – R5 Quick installation guide Connect the control cables See figure on page 57. It shows an example with one analog signal cable and one digital signal cable. Make the connections according to the default configuration in use. The default connections of the Water default configuration are shown in section Default I/O connections on page 37.
OUT1 Safe torque off. Factory connection. Both circuits OUT2 must be closed for the drive to start. See chapter The Safe torque off function in ACQ580-01 (0.75 SGND to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000044862 [English]). Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
38 EN – R5 Quick installation guide Install optional modules, if any See chapter Electrical installation in ACQ580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual (3AXD50000044862 [English]). Reinstall cover See figure on page 58. 1. IP21, Reinstall the box cover: Slide the cover upwards (1a) and tighten the retaining screws (1b).
EN – Quick start-up guide 43 EN – Quick start-up guide This guide describes how to start-up the drive using the Set-up assistant on the HVAC control panel. For complete information on start-up, see ACQ580 pump control program firmware manual (3AXD50000035867 [English]). Before you start Ensure that the drive has been installed as described in chapter EN –...
Page 44
44 EN – Quick start-up guide The First start assistant guides you through the first start-up. The assistant begins automatically. Wait until the control panel enters the view shown on the right. Select the language you want to use by highlighting it (if not already highlighted) and pressing (OK).
Page 45
Refer to the motor or pump nameplate for the following nominal value settings of the motor. Enter the values exactly as shown on the motor or pump nameplate. Example of a nameplate of an induction (asynchronous) motor: ABB Motors motor M2AA 200 MLA 4 IEC 200 M/L 55 Ins.cl.
Page 46
46 EN – Quick start-up guide If you want to make a backup of the settings made so far, select Backup and press (Next). If you do not want to make a backup, select Not now and press (Next). The set-up is now complete and the drive is ready for use.
Page 47
EN – Quick start-up guide 47 3 – Hand/Off/Auto operation The drive can be in remote control or local control, and in local control there are additionally two different modes. Remote control: Drive is controlled from the I/O or the fieldbus. •...
— DRIVES FOR WATER ACQ580-01 drives Quick installation guide Frames R1 to R4 and R5 installation figures 3AXD50000044864 Rev B MUL EFFECTIVE: 2019-06-30...
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.