WIRING
To connect external wiring
NOTES
1.
18AWG (1,5mm²) min.
2.
9.5A max. input current
per ZAM-180.
3.
Not power limited.
Figure 12
ZAM-180 Input Power Wiring
A24205-A334-B832 (Edition 1)
P/N 315-035600-2
Remove ELECTRICAL POWER prior to working on equipment.
All field wiring of the ZAM-180 is connected to the terminal blocks on the
upper side of the ZAM-180.
The screw terminals can accommodate one 12-24 AWG(Ø 0,5mm-2,5mm²)
or two 16-24 AWG, (Ø 0,5mm-1,0mm²).
Lift the white cover on the terminal block.
Loosen the screw of the terminal by turning it counterclockwise.
Insert the wire into the side of the terminal block.
Tighten the screw of the terminal block by turning it clockwise
Earth ground
Loc. Audio IN B
Loc. Audio IN A
1
2
3
4
5
6
9
10
11
12
13
Speaker Line 1A
Speaker Line 1B
Speaker Line 2A
Speaker Line 2B
ZAM-180
24V
0V
Power Input
24VDC @ 9.5A Max.
8
Earth ground
Loc. Switch A
Loc. Switch B
7
8
14
15
16
Back-Up Amp B
Back-Up Amp A
P5
TB3
P4
TB1
PSC-12
BATTERY
O —
0V
24V
Non-Power
Limited Output
24VDC @ 12A