Siemens ZAM-180 Installation Instructions Manual page 3

Zone amplifier module 180w
Table of Contents

Advertisement

LED
COLOR
POWER
green
MODULE FAIL
yellow
CAN FAIL
yellow
ASI FAIL
yellow
ZONE ACTIVE
green
ZONE TRBL
yellow
ZONE GND
yellow
FAULT
OVERLOAD
Yellow
NORMAL
Green
LOW
yellow
A24205-A334-B832 (Edition 1)
P/N 315-035600-2
The LEDs functions are defined as follows:
NORMAL
OFF NORMAL
STATE
STATE
ON
OFF –external
voltages fail
OFF
ON –general
trouble at ZAM
OFF
ON –CAN interface
trouble
OFF
ON –ASI interface
trouble
OFF
ON –Speaker zone
active
OFF
ON –Speaker zone
trouble, open circuit
or short circuit
OFF
ON –unwanted
earth ground
connection on a
speaker line
OFF
ON
ON
OFF
OFF
ON
Terminal Connections:
Power Input:
3
ACTION IN OFF NORMAL STATE
Check for failure on PSC, CC-5, wiring
Failure on ZAM, ZAM-180 needs to be replaced
Failure on AIC, DAC-NET, CC-5, back plane or
other CAN cards/modules
Failure on "ASI OUT" and/or "ASI IN" at this
ZAM-180
Indicates normal operation on speaker zone
Check wires to the speakers, EOL resistor(s)
and de-coupling capacitors on every speaker
Check wires to the speakers for earth ground
connections
Refers to Local Audio input only: Press "DOWN"
push button until "OVERLOAD" LED turns off
and "NORMAL" LED turns on
Refers to Local Audio input only: No audio
signal or audio signal too high/low
Refers to Local Audio input only: Press "UP"
push button until "LOW" LED turns off and
"NORMAL" LED turns on
These terminals are used for field wiring as
shown in Figure 12
This terminal block is non power limited and
can supply up to 12A.
This Input is connected to the output terminal
TB4 of the PSC-12/PSX-12.