hit counter script

Mitsubishi Electric MELSEC Q Series User Manual page 262

Positioning module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Error
Error
code
category
(decimal)
125
Zero/gain
adjustment
error
126
260
Error
Error name
classification
Analog output
adjustment area
1 Outside the
setting range
ERR.1
Analog output
adjustment area
2 Outside the
setting range
Operation at the
Description
error occurrence
The set value in
"
Analog output
Cd.5
adjustment area 1" is
outside the setting
range.
The zero/gain
adjustment values
are not reflected.
The set value in
"
Analog output
Cd.9
adjustment area 2" is
outside the setting
range.
Action
Set a value within the
setting range.
[Setting range]
Depends on
"Accumulated pulse
setting" in the switch
setting. (Unit: pulse)
• Selection 1:
-3700 to 3700
• Selection 2:
-7400 to 7400
• Selection 3:
-11100 to 11100
• Default value,
selection 4:
-14800 to 14800
Set a value within the
setting range.
[Setting range]
Depends on
"Accumulated pulse
setting" in the switch
setting. (Unit: pulse)
• Selection 5:
-37000 to 37000
• Selection 6:
-74000 to 74000
• Selection 7:
-111000 to 111000
• Selection 8:
-148000 to 148000