GENERAL DATA
Multi F with LGRED Outdoor Unit Electrical Data
Table 2: Multi F with LGRED Electrical Data.
Nominal
Unit Model
Hertz Voltage
Tons
No.
1.5
LMU180HHV
2
LMU240HHV
60
2.5
LMU300HHV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as
follows: (Largest motor FLA x 2.25) + (Sum of other motor
FLA) rounded down to the nearest standard fuse size.
RFA = Recommended Fuse Amps.
10
Voltage Range
MCA MOP RFA
(Min. to Max.)
18.6
208 - 230
187 - 253
19
19.4
RLA = Rated Load Amps.
FLA = Full Load Amps.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Compressor
Compressor
Quantity
Motor RLA
30
25
1
30
25
1
30
25
1
Indoor Fan Motor (FLA) is based on the max. combination
of IDUs.
The maximum combination for each outdoor unit is:
- 18,000 ODU (LMU180HHV): 12,000 IDU x 2
- 24,000 ODU (LMU240HHV): 12,000 IDU x 2 + 9,000 IDU
x 1
- 30,000 ODU (LMU300HHV): 12,000 IDU x 3
F
MULTI
WITH
F
MULTI
MAX
Outdoor Unit Fan
Motor
kW
FLA
13
0.12
0.73
13
0.12
0.73
13
0.12
0.73
Indoor Unit
Fan Motor
FLA
1.6
2.0
2.4