Siemens ST950 Handbook
Hide thumbs Also See for ST950:

Advertisement

THIS DOCUMENT IS ELECTRONICALLY APPROVED
AND HELD IN THE SIEMENS DOCUMENT CONTROL TOOL
All PAPER COPIES ARE DEEMED UNCONTROLLED COPIES
Prepared By
Division/BU
Mobility, Intelligent Traffic Systems
Department
Engineering
Name
C.Rabe & K.R.Napper
Function
Lead Engineer
Date
December 2018
COPYRIGHT STATEMENT
The information contained herein is the property of Siemens Mobility Limited. and is supplied
without liability for errors or omissions. No part may be reproduced or used except as
authorised by contract or other written permission. The copyright and the foregoing restriction
on reproduction and use extend to all media in which the information may be embodied.
Copyright  Siemens Mobility Limited 2018 All Rights Reserved
SAFETY INFORMATION
IT IS RECOMMENDED THAT DUE TO THE HAZARDS PRESENT WITHIN
THE CONTROLLER CABINET ALL POWER TO THE CABINET IS
DISCONNECTED BEFORE REMOVING OR INSTALLING ANY EQUIPMENT
INTO THE CABINET. WHERE A RISK ASSESSMENT AND METHOD
STATEMENT FOR THE WORKS TO BE COMPLETED AND / OR THE INSTRUCTIONS
Security classification
Version
Last Editor
Document Name
Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
ST950 ICM Handbook
667/HE/46950/000
ST950
Unrestricted
5
Neil Atkinson
ST950 ICM Handbook
Sopers Lane, Poole, Dorset, BH17 7ER
for
Checked and Released
Mobility, Intelligent Traffic Systems
Engineering
D.A.Martin
Engineering Manager
December 2018
Page
Status
Date
Document No.
Intelligent Traffic Systems
1 of 125
Issued
18-Dec-2018
667/HE/46950/000

Advertisement

Table of Contents
loading

Summary of Contents for Siemens ST950

  • Page 1 December 2018 COPYRIGHT STATEMENT The information contained herein is the property of Siemens Mobility Limited. and is supplied without liability for errors or omissions. No part may be reproduced or used except as authorised by contract or other written permission. The copyright and the foregoing restriction on reproduction and use extend to all media in which the information may be embodied.
  • Page 2 When re-commissioning signals, the following sequence is recommended to ensure that the correct signal startup sequence is followed: Security classification Unrestricted Page 2 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 3 There are various RJ45 connectors used to connect to peripheral cards within the ST950 family of controllers. Most are not Ethernet ports and should not be connected to other equipment, including PCs. Please note that the internal 24V DC supply should NOT be used for any equipment outside of the main controller cabinet.
  • Page 4 They must be recycled properly to protect the environment and to cut down on the waste of precious resources. Security classification Unrestricted Page 4 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 5: Table Of Contents

    Routine Inspection of Signal Equipment ............84 Security classification Unrestricted Page 5 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 6 May 2014 TS007425 K.R.Napper November 2018 TS008205 D.Martin December 2018 TS009064 N.Atkinson The electronic version of this handbook can be found on the Siemens website www.siemens.co.uk/traffic in the Handbooks section under Downloads. Security classification Unrestricted Page 6 of 125 Version Status...
  • Page 7: Introduction

    Purpose The purpose of this handbook is to describe the procedures for the Installation and Commissioning of the ST950 LV Controller and to provide guidance on routine maintenance and fault finding. This handbook has been created in accordance with the requirements of BS EN 12675:2001 and BS 7987:2001.
  • Page 8: Pre-Requisites

    667/HB/20168/000 IC4 Configurator Handbook Pre-Requisites Before reading this handbook, you should be familiar with the ST950 General Handbook 667/HB/46000/000. Anyone undertaking installation, commissioning and first line maintenance on the ST950 family of controllers will also need the ST950 User Interface Handbook (667/HU/46000/000) which provides details of how to connect to the controller and the different user interfaces which are available.
  • Page 9: Definitions

    Intelligent Traffic Systems Sopers Lane, Poole, Dorset, BH17 7ER Any personnel working on the ST950 family of controllers should have completed the following training courses: • HA Sector Scheme Sector 8 Modules 5XX • M609 – Junction Traffic Controller Maintenance for ST950 / ST950ELV Training requirements for non UK users may be different.
  • Page 10: Abbreviations

    Controller identification number (ElectroMatic). Configuration Identity Code (equivalent to EM above) Generic Versatile Platform - used by ST950 and other Siemens products to provide general services such as comms, user interface, etc. A scale drawing of the intersection including controller...
  • Page 11 Transport Layer Security User Datagram Protocol Urban Traffic Control Security classification Unrestricted Page 11 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 12: Third Party Information

    GNU General Public License, the GNU Lesser General Public License, the modified BSD license and the MIT license. In the event of conflicts between Siemens license conditions and the Open Source Software license conditions, the Open Source Software conditions shall prevail with respect to the Open Source Software portions of the software.
  • Page 13: System Overview

    Sopers Lane, Poole, Dorset, BH17 7ER YSTEM VERVIEW The Siemens ST950 Controller family is the latest in a long line of highly integrated traffic controllers. The ST950 family of controllers can be supplied either in a single-door outer case with a 6U logic rack and equipment mounting frame or as a free-standing logic rack housing the power supply, CPU Card and Lamp Switch cards.
  • Page 14: System Components

    An updated I/O card protocol improves system performance and adds functionality. This protocol is known as GSPI - Generic Serial Peripheral Interface. Older I/O cards will need to be updated to allow communication with the ST950. ST950 compatible I/O cards are easily recognized by the text 'I/O CARD 667/1/32990/95x' printed on the board cover.
  • Page 15 The ST950 CPU I/O card cannot be used in a standard ST950 cabinet, it can only be used in 3rd party cabinets.
  • Page 16 OR 4 OUTPUTS LOOPS Figure 1 – System Overview Security classification Unrestricted Page 16 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 17: Hardware Overview

    Sopers Lane, Poole, Dorset, BH17 7ER ARDWARE OVERVIEW The Controller Cabinet Figure 2 and Figure 3 show the ST950 controller fitted in an ST950 Controller Cabinet. CET bars are installed in the base of the cabinet. The Master Switch Panel is installed on the right hand side panel of the cabinet.
  • Page 18 Figure 3 – Controller Cabinet showing new equipment The Controller Rack Figure 4 and Error! Reference source not found. show the ST950 controller in a 6U 19" rack. The left-hand part of the rack contains the mains distribution unit (MDU) that contains the logic power supply, the lamp supply relays, the maintenance sockets and the controller’s power off/on switch.
  • Page 19 The standard controller items are used with these kits and are listed in the ST950 Family Tree. Refer to Siemens Poole for the latest copy. Figure 4 – ST950 19” Rack - Front Note that a LED UK MDU is shown.
  • Page 20: St950 Non Uk Controller Racks

    Figure 5 – ST950 19” Rack - Rear ST950 Non UK Controller Racks The ST950 Non UK variants provide a self contained controller providing all of the power supply and control functions located within a single rack. The rack variants contain the following: •...
  • Page 21 3.2.1 Rack Wiring Mains Supply Filtering for Export Rack Configurations The ST950 export rack is supplied without a mains input filter or Lightning Protection. We strongly recommend that a mains filter and/or Lightning Protection components are fitted to ensure maximum immunity to mains borne interference.
  • Page 22 Wire the Pink ‘TXL’ mains supply feed into the terminal that best matches the local mains supply voltage. Security classification Unrestricted Page 22 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 23 Wire the Blue Neutral Connection to the ‘0’ Terminal as shown above Security classification Unrestricted Page 23 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 24: St950 System Components

    ST950 S YSTEM OMPONENTS This section introduces the main components of the ST950 system. Mains Distribution Unit The MDU is not used to power the Loop Detector cards. MDU ConnectionsFigure 5 shows the rear of the MDU and details the connections on the connectors.
  • Page 25 The white wires should be joined together and connected to the ‘COMMON’ input (pin b16 of the connector). Security classification Unrestricted Page 25 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 26: Dimming Transformer

    Note: The ST950 LED controller only has one Dim output tap of 154V CPU Card Variants There are two variants of the ST950 CPU card which differ only in the amount of RAM available on the EFC module. • 667/1/46010/001 – 64M RAM •...
  • Page 27 LPU + HPU Relays Figure 7 – ST950 CPU Card (front and rear views) Figure 7 shows the CPU Cards interfaces on the front and rear in the orientation when installed in the logic rack (but without cables for clarity)
  • Page 28 Intelligent Traffic Systems Sopers Lane, Poole, Dorset, BH17 7ER The ST950 significant part positions are identified in Figure 8 below and detailed in Table 1. LICENCE HEART Smart RJ45 LSLS Card SD Card RJ45 SITE SPECIFIC RJ45 RJ45 Coin Serial...
  • Page 29 The function of each LED is described below. Security classification Unrestricted Page 29 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 30 Flashes to indicate status Slow flash Normal operation Security classification Unrestricted Page 30 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 31 Green flash, equal on and off Normal operation Security classification Unrestricted Page 31 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 32 Security classification Unrestricted Page 32 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 33 The maximum current that this output can pass is 25mA and suitable external devices must be employed to ensure that this figure is not exceeded otherwise damage to the ST950 board will occur. Digital External Supply Monitor (7,8) – For future use.
  • Page 34 S4 – Reset EFC push button. This push button is reserved for engineering use and should NOT be pressed. Security classification Unrestricted Page 34 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 35: Heart Of The Controller

    F2 – Aux RS232 Modem power supply output – 500mA Quick blow The replacement fuse for F1 and F2 is Siemens part number 518/4/97070/004. This part number calls up the holder and fuse. Remove the fuse and discard the holder.
  • Page 36: Gemini2

    Security classification Unrestricted Page 36 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 37 Figure 10 – I/O Card (Showing 16-output variant) Security classification Unrestricted Page 37 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 38 Works Specification. The valid address range is 1 Security classification Unrestricted Page 38 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 39: Cpu I/O Card

    CPU IO card has a fixed address: 1. Figure 12 – CPU I/O Card Security classification Unrestricted Page 39 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 40: Intelligent Detector Backplane Card

    Security classification Unrestricted Page 40 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 41 * - May flash so fast that it looks like Green Steady. Security classification Unrestricted Page 41 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 42: Loop Detector Cards

    They are not powered from 24V DC from the MDU. The maximum number of each type of each type of detector which can be supported by each type of transformer is given in the ST950 General Handbook. Loop Detector Cards The Loop Detector cards pick up the Loop Detector Power from SK7 on the Intelligent Detector Backplane Card.
  • Page 43: Lamp Switch Cards

    Figure 15 - Lamp Switch Card Switch Settings Security classification Unrestricted Page 43 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 44 ADC Test Failure (FLF 2:10) if cards are mixed. Security classification Unrestricted Page 44 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 45 Figure 16 – Lamp Switch Card Connections Security classification Unrestricted Page 45 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 46: Manual Panel

    SW 3 TEST Figure 17 – Manual Panel Security classification Unrestricted Page 46 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 47 These LEDs can be configured to display auxiliary functions active LEDs such as Dim Override. Security classification Unrestricted Page 47 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 48 (see MND command). Security classification Unrestricted Page 48 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 49: Pedestrian Audible/Tactile Indications

    Pedestrian Audible/Tactile Indications 4.12.1 Non-Switched Audibles/Tactiles The Audible power supplies on the ST950 are designed to provide a DC voltage between 10V and 24V, and typically provide 50mA at 18V DC. This is provided using the Audible Supply Kit. See the ST950 Installation, Commissioning and Maintenance Handbook for more details.
  • Page 50 Items required: Audio Switching Kit of Parts 667/1/21470/000 (Although this was designed for the T400 it may also be used for the ST950) In certain non UK markets the Pedestrian Audible units are powered from mains voltage, namely the pedestrian phase green man supply and red man supply. When...
  • Page 51 (See Figure 21 if the Tactiles are to be switched on/off by the controller) Security classification Unrestricted Page 51 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 52 (See Figure 18 if the Audibles do not need to be switched on/off by the controller) Security classification Unrestricted Page 52 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 53 (See Figure 19 if the tactiles do not need to be switched on/off by the controller) Security classification Unrestricted Page 53 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 54 Figure 21) or a mixture of tactiles and audibles up to a total of four. Security classification Unrestricted Page 54 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 55: Above Ground Detectors

    See the documentation relevant to the particular Above Ground Detector devices being used. Security classification Unrestricted Page 55 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 56: User Interface

    USB handset and network connections. Security classification Unrestricted Page 56 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 57 667/HH/46000/000 (controller handset) and 667/HB/31760/000 (GVP handset). Security classification Unrestricted Page 57 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 58: Fitting The Controller Into Alternative Cabinets

    The kits are listed on 667/DZ/46950/000 and contain the necessary installation instructions. The standard controller items are used with these kits and are listed in the ST950 Family Tree (667/DZ/46950/000). Refer to Siemens Poole for the latest copy.
  • Page 59: Installation And Commissioning Procedure

    • The MDU, LSC’s and Master switch panel are all of the correct variant for the type of ST950 in the Works specification LED or 20A. • All plugs and sockets are securely mated •...
  • Page 60: Checking Site Suitability

    900mm away from the main doors, extending the full width of the case, Security classification Unrestricted Page 60 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 61: Cabinet Installation

    Terminate the cable armouring to the CET bars Security classification Unrestricted Page 61 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 62 (20mm) with no excess water) and cover the flagstone to a height approximately Security classification Unrestricted Page 62 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 63 Electricity Supply Company cut out with any cabling. Security classification Unrestricted Page 63 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 64 667/HE/20664/000 – Installation and Commissioning Handbook – Installation Testing (General) Security classification Unrestricted Page 64 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 65 Apply a bead of silicone sealant around the edge of the stool. Security classification Unrestricted Page 65 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 66 Security classification Unrestricted Page 66 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 67: On Site Testing

    Cards, MDU, I/O card or Loop Termination Card connectors. Controller Commissioning The ST950 family of controllers support both the traditional RS232 handset port and now a USB handset port. The traditional handset commands are supported but the user will find that the web interface provides a more detailed view of the controller status to allow easier testing and commissioning.
  • Page 68 The optional battery backup kit for the RTC is provided with a lithium coin cell (CR2032 or equivalent) that is fitted into a socket on the ST950 CPU Card. Without this optional kit the RTC is maintained using supercaps which will provide 48hrs of backup in the event of a power failure.
  • Page 69 Affix the battery label in the space provided as shown below. Security classification Unrestricted Page 69 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 70 • using a USB memory stick and WIZ interface. Full details on how to load an IC4 configuration can be found in the ST950 User Interface Handbook 667/HU/46000/000. After loading an IC4 configuration which is significantly different from that previously in use, it will be necessary to own the Heart.
  • Page 71 Licences are distributed and held on the ST950 in Smart Cards. For distribution either a full size (credit card size) or SIM size Smart Card can be used. For storage on the ST950, a SIM size Smart Card is used and is fitted in the Smart Card holder on the CPU Card.
  • Page 72 Close the container and rotate locking ring. The fitted card should appear as shown below. Security classification Unrestricted Page 72 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 73 To view the licence information, press the 'Read Licences' button. Security classification Unrestricted Page 73 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 74 Card fitted in the external USB Smart Card Reader. This Licence Smart Card holds Security classification Unrestricted Page 74 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 75 Licence Smartcard fitted can be checked on the System – Settings – Comms – Stratos Security classification Unrestricted Page 75 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 76 Tenant Pass Phrase is not specified at the time of initial connection then the equipment will be allocated to the Siemens Support team who can then make the allocation when required based on the outstation name, unique site id and destination tenant.
  • Page 77 Security classification Unrestricted Page 77 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 78 Status and Configuration → System → Comms → DSL / Fibre web page • using the WIZ command Full details on how to configure then network interface can be found in the ST950 User Interface Handbook 667/HU/46000/000. 7.5.8 Setting the Date and Time There are two clocks within the system: •...
  • Page 79 • System Time - controller clock is synchronised to system clock. Use this mode where NTP or GPS is providing the source of time to the whole ST950 system and synchronisation to other controllers (e.g. mains synchronisation for CLF) is not required.
  • Page 80 To use this facility level 3 access is required and the signals on/off switch MUST be in the OFF position. Security classification Unrestricted Page 80 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 81 Security classification Unrestricted Page 81 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 82: Customer Acceptance

    Once downloaded the zip file can be unzipped into a folder. The user can navigate the downloaded file set by opening index.html in a web browser. 7.5.16 Loading New Firmware If new firmware is required refer to the ST950 User Interface Handbook 667/HU/46000/000 for how to load new firmware. Customer Acceptance Run through the commissioning with the customer.
  • Page 83: Leaving Site

    OUTINE AINTENANCE ROCEDURES This section contains a list of checks to be performed at an ST950 installation on a regular basis (normally annually). These instructions override any others that may exist. If a Site PI exists for the specific site, it may contain instructions that should be carried out in addition to those detailed below.
  • Page 84: Routine Inspection Of Signal Equipment

    Security classification Unrestricted Page 84 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 85 Re-test the cable to ensure that corrective action taken has removed the problem. Security classification Unrestricted Page 85 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 86: Routine Setup Check

    Export of site information - see section 7.5.15 Security classification Unrestricted Page 86 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 87: Fault Finding

    Security classification Unrestricted Page 87 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 88: Fault Finding Starting From The Fault Indications

    10.2 Fault Finding Starting from the Fault Indications The following is a list of indicators in the ST950 controller that assist in the location and diagnosis of a fault. The state of each of these indicators should be noted on arrival at a site before doing anything else.
  • Page 89 CPU Card. Security classification Unrestricted Page 89 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 90: Replacement Of Cards

    10.3 Replacement of Cards This section covers removal and fitting of PCBs in the ST950. Also described are procedures to ensure that the card functions correctly when fitted. 10.3.1 Safety Requirements Before replacing any fuses, cards etc., IT IS ESSENTIAL THAT THE POWER TO THE CONTROLLER IS ISOLATED.
  • Page 91 In order to gain access to the rear of the cards, first swing out the ST950 Rack Assembly. Release this by undoing the two screws at the right hand edge of the frame. Having done this there is room to reach the back of the cards to deal with the ribbon cables.
  • Page 92 SD card Write Enable switch position SD Card Orientation Security classification Unrestricted Page 92 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 93 Pressing the Program Button on the Processor Card within 30 seconds of the previous step. Security classification Unrestricted Page 93 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 94 Security classification Unrestricted Page 94 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 95 Switch signals off and press the PRG button. Security classification Unrestricted Page 95 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 96 WIZ. Owning the Heart Using Web Pages Security classification Unrestricted Page 96 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 97 In WIZ there are two options within the Heart menu: 1> Own Heart Security classification Unrestricted Page 97 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 98 If the Heart is already owned then the following is displayed. Security classification Unrestricted Page 98 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 99 Remove the three nuts holding the card in place and pull away from the passive backplane. Replace with the new card and tighten the nuts. Reassemble and return the kit including the defective card to Siemens Poole. 10.3.11 Replacement of the Manual Panel First unplug the cable connecting the panel to the CPU Card.
  • Page 100: Replacing Components Other Than Cards

    If desired the site log facility within the controller can be used as an alternative to the physical log book. Please see the ST950 User Interface Handbook (667/HU/46000/000) for further details. Security classification...
  • Page 101: The Self-Test Facility

    In previous controllers, LEDs on a lamp switch card were used to indicate the presence of up to three IO cards. The ST950 does not do this. Self-Test performs the checks detailed on the following pages and reports the error messages shown if faults have been detected.
  • Page 102 Full details on scenarios are given in the ST950 Facilities Handbook (667/HB/46000/001) but the scenarios most appropriate to installation and commissioning are ST950 System Test (the default which is used if no other choice is made) and ST950 System Test (no licence).
  • Page 103: Manual Panel Checks

    Sopers Lane, Poole, Dorset, BH17 7ER ST950 System Test (no licence) Scenario This scenario is similar to ST950 System Test but it does not include testing of the licence card so won’t report failures when run on controllers without a licence card fitted.
  • Page 104 Version Test: Primary Test ID Primary CPU Security classification Unrestricted Page 104 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 105 ‘unknown’ Iss:01 Serial:xxxxxxxx Security classification Unrestricted Page 105 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 106 (facilities) facility: x facility: y facility: z Security classification Unrestricted Page 106 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 107 TXD-RXD Security classification Unrestricted Page 107 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 108: Test Failures

    On power-up, the Self-Test facility checks the integrity of the Main CPU Card: RAM FAULT DPR RAM FAULT Security classification Unrestricted Page 108 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 109 ZXO wires are not connected to the back of the first Lamp Switch Security classification Unrestricted Page 109 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 110 P/Bus Init... LS/Card Fault (Lat) Bad L/S Cards Security classification Unrestricted Page 110 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 111: Self-Test Handset Output After Lamp Supply On

    LED Signals. Security classification Unrestricted Page 111 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 112 Measures and reports the dim lamp supply Security classification Unrestricted Page 112 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 113 (triacs still switched off): Security classification Unrestricted Page 113 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 114 If the Self-Test terminates and the controller starts up normally when it attempts to test the SSR*, the power supply may be overloaded. Check the number of detector cards for example. See Section 2 of the ST950 Controller General Handbook.
  • Page 115 Checking Lamp Supply Arrangement: RelayB;All Sigs Off Security classification Unrestricted Page 115 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 116 Security classification Unrestricted Page 116 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 117 After a few seconds, Self-Test repeats the tests from section 11.6, allowing the controller to be soak tested. Security classification Unrestricted Page 117 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 118 (on a phase on that card). Security classification Unrestricted Page 118 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 119 K green on the negative peak is stuck on. Security classification Unrestricted Page 119 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 120: Appendix A Part Numbers And Spares List

    Part Numbers Listed below are all the currently available main parts common to all ST950 Controllers. Sections A.1.1 and A.1.2 give part numbers for those parts that are exclusive to either UK only or non-UK Controllers. For an up to date list see the Family Tree (667/DZ/46950/000).
  • Page 121 ST950 Cabinet UK 2kVA 24PH Grey 667/1/46950/020 ST950 Cabinet UK 2kVA 24PH Black 667/1/46950/021 ST950 LED Cabinet UK 500VA 8PH Wired 8PH Grey 667/1/46950/018 ST950 LED Cabinet UK 500VA 8PH Wired 8PH Black 667/1/46950/019 ST950 LED Cabinet UK 500VA 24PH Grey...
  • Page 122 License Card Kit – UTMC OTU, MOVA 7 Streams 1,2 667/1/47566/000 License Card Kit – UTMC OTU, MOVA 7 Streams 1,2,3,4 667/1/47567/000 USB WiFi Dongle 667/1/45966/001 ST900 to ST950 Power Adaptor Cable Assy (Pink) 667/1/46961/000 Lightning Protection Kit – Ethernet 667/1/45972/001 Gemini 667/1/32600/000 A.1.4...
  • Page 123 PB815 Firmware (Latest issue – Phase Bus Processor) 667/1/12815/000 Security classification Unrestricted Page 123 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 124 5A cartridge fuse to BS1362 marked ‘MAINT’ on Mains Distribution card Security classification Unrestricted Page 124 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.
  • Page 125: Security Classification Unrestricted

    Two 3.15A fuses used for initial testing on a rewired junction for Self-Test (See section 11). Security classification Unrestricted Page 125 of 125 Version Status Issued Last Editor Neil Atkinson Date 18-Dec-2018 Document Name ST950 ICM Handbook Document No. 667/HE/46950/000 Copyright © Siemens Mobility Limited 2018. All Rights Reserved.

Table of Contents