GENERAL DATA

Electrical

Table 3: 208-230V, 60Hz, 1-Phase Single-Zone Mega System Electrical Data Table.
Nominal
Unit Model
Hertz Voltage
Tons
No.
3/4
LS090HEV2
1
LS120HEV2
60
1-1/2
LS180HEV2
2
LS240HEV2
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Table 4: 115V, 60Hz, 1-Phase Single Zone Single-Zone Mega 115V System Electrical Data Table.
Nominal
Unit Model
Hertz Voltage
Tons
No.
3/4
LS090HXV
60
1
LS120HXV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
12
Voltage
Range (Min.
MCA
to Max.)
10.0
10.0
208 - 230
187 - 253
15.0
15.0
Voltage
Range (Min.
MCA
to Max.)
13.5
115
104-127
13.5
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Compressor Motor
Com-
RLA
MOP
pressor
Cooling Heating
Quantity
15
1
7.0
15
1
7.0
20
1
10.0
20
1
10.0
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Compressor Motor
Com-
RLA
MOP
pressor
Cooling Heating
Quantity
20
1
10.0
20
1
10.0
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Outdoor Fan
Indoor Fan Motor
Motor
W
FLA
W
7.0
43
0.4
30
7.0
43
0.4
30
10.0
85
0.4
58
10.0
85
0.4
58
Outdoor Fan
Indoor Fan Motor
Motor
W
FLA
10.0
43
0.4
30
10.0
43
0.4
30
FLA
0.4
0.4
0.4
0.4
W
FLA
0.5
0.5

Advertisement