Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
● A soft characteristic can be selected for a parallel connection (for uniform load distribution of power supply units of the same type) ● Operating status is displayed using LED ● Signaling contact "24 V O.K" SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Page 4
Overview Ordering data Regulated power supply unit SITOP PSU2600 3ph Type Order number Input 3AC 400 - 500 V, 6EP4436-0SB00-0AY0 Output 24 V DC / 20 A Validity This manual provides information on the following products: ● SITOP PSU2600 basic device 24 V DC/20 A...
Protection and monitoring ....................... 31 MTBF ............................31 Mechanical system ......................... 31 Dimension drawing ......................... 32 Safety, approvals, EMC ........................... 33 Safety ............................33 Test voltage ..........................34 Approvals ..........................35 EMC ............................35 SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Page 6
Table of contents Environmental conditions ......................... 37 Applications ............................. 39 Parallel connection to increase the power rating ..............39 Series connection for increased voltage ................41 Environment ............................43 Service & Support ............................ 45 SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Page 8
Safety information SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Description, device design, dimension drawing Device description SITOP PSU2600 3ph is a primary-clocked power supply for connection to a 3-phase AC line supply. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof.
"+" ② 2 screw terminals output "–" ④ One screw terminal each Signaling contact ⑥ One screw terminal each Reset Do not subject the end stop to higher loads Figure 2-2 Terminal data SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
P is exceeded. rated Note It is only permissible to use an insulated screwdriver when actuating the potentiometer. For information on actuating the potentiometer (screwdriver, torque), see Figure 2-2 Terminal data (Page 10). SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Starting delay 3 – 5 s after 1/0 signal edge Input current, max. 10 mA Voltage strength (test voltage), 5 kV AC with respect to PE/ AC input / DC output. Figure 2-4 Potentiometer, signaling Figure 2-5 Signaling contact, reset SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Page 13
6EP4436-0SB00-0AY0 (24 V/20 A) Green LED lit Normal operation, output voltage > 20 V ± 0.5 V Signaling contact, contact closed LED off Output voltage < 20 V Signaling contact, contact open (quiescent position) SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
WARNING Installing the device in a housing or a control cabinet The SITOP PSU2600 3ph power supply is a built-in device. It must be installed in a housing or control cabinet, to which only qualified personnel have access. The device can be mounted in a control cabinet on standard mounting rails (see Chapter...
A clearance of at least 50 mm should be maintained above and below the device (maximum depth of the cable duct, 50 mm). No space is required at the side. Output current as a function of the ambient temperature Figure 4-1 Output current in the standard mounting position SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Particularly when installing on a vertically fastened standard mounting rail, additional measures may be required, e.g. to prevent the device from slipping on the rail. Figure 4-2 Mounting position 1 Figure 4-3 Mounting position 2 SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Page 21
Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-4 Mounting position 3 Figure 4-5 Mounting position 4 Figure 4-6 Mounting position 5 SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Line-side connection The SITOP PSU2600 3ph power supply is designed for connection to a 3-phase AC line supply (TN or TT system according to IEC 60364-1) with a rated voltage of 400 - 500 V, 50 - 60 Hz.
Page 24
Installation 5.1 Line-side connection The protective conductor of the line supply must be connected at the PE terminal. NOTICE Country-specific regulations must be observed when installing. SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
5.2 Output-side connection Output-side connection The SITOP PSU2600 3ph power supply provides at its output an isolated (= non-grounded) SELV output voltage (Safety Extra Low Voltage). The output of the power supply is no-load, overload and short-circuit proof. If an overload occurs, the electronic current limiting function limits the output current to a maximum value (see Section Technical data (Page 27)).
2.5 s Voltage rise, typ. 150 ms Rise time of the output voltage, max. 500 ms Rated current I 20 A out rated Current range 0 - 20 A Active power output, typ. 480 W SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Page 29
Figure 6-2 Starting delay/voltage rise Figure 6-3 Output characteristic single operation The device supplies a constant output voltage until the current limit is reached. In the event of an overload, the output current is reduced. SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Dyn. load regulation (I : 50/100/50 %), U ± typ. Load step regulation time 50 to 100 %, typ. 0.2 ms Load step regulation time 100 to 50 %, typ. 0.2 ms Regulation time, max. 10 ms SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Product feature of the housing: housing that can be lined up next to one another Type of mounting: Wall/panel mounting Type of mounting: Rail mounting Type of mounting: S7-300 rail mounting Mounting Can be snapped onto standard mounting rails TH 35-15/7.5 (EN 60715) SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Technical data 6.8 Dimension drawing Dimension drawing See Section Dimensions and weight (Page 15) CAD data that can be downloaded from the Internet: 6EP4436-0SB00-0AY0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01222) SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
SELV output voltage U according to EN 60950-1 Protection class Class I Degree of protection (EN 60529) IP20 Leakage current, typ. 1.7 mA Leakage current, max. 3.5 mA Test voltage see Test voltage (Page 34) SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
500 V DC 6000 V DC 1500 V AC 1500 V AC 350 V AC 4000 V AC Note: Tripping current for DC measurement: 0 mA Tripping current for AC measurement: < 100 mA SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Line harmonics limit EN 61000-3-2 Class A Generic standards EN 61000-6-2 Noise immunity for industrial environments EN 60601-1-2:2015 Medical sector (also refers to EN 61000-6-2 and EN 61000-6-3) EN 61000-6-3 Emission for residential areas SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Figure 9-1 Parallel connection Note It is not permissible to take into account simultaneous overload capability (Extra-Power 150% for 5 s/min) of several power supplies connected in parallel when configuring the power supply system. SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Page 40
For this purpose, a suitable protective circuit (e.g. decoupling diode or DC-capable circuit breaker) must be installed between each "+" terminal of the power supply and the common connection point. SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
When connecting two power supplies in series, the continuous, permissible SELV voltage of a maximum of 60 VDC according to EN 60950-1 cannot be guaranteed in the case of a fault. Figure 9-2 Series connection SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Page 42
Applications 9.2 Series connection for increased voltage SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
The devices are in conformance with RoHS. As a rule, only non-silicon precipitating materials are used. Disposal guidelines Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse. SITOP PSU2600 3ph Manual, 01.2018, A5E39263454-2-76...
Technical support for all IA/DT products can be accessed through the following communication channels: ● Telephone: + 49 (0) 911 895 7222 ● Internet: Web form for support request (http://www.siemens.de/automation/support-request) Technical documentation on the Internet Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (http://www.siemens.com/sitop/manuals)
Page 46
Service & Support Contact persons If you have any questions regarding the use of our products, then contact the Siemens contact person in your regional Siemens sales office. You can find these addresses as follows: ● On the Internet (http://www.automation.siemens.com/partner) ●...