Do not switch off the device during the firmware-setup!
If an error message is posted during the firmware setup, leave the device on and contact the SIEMENS-Hotline. It
may possible to continue the firmware-setup under the guidance of the Hotline using the following service program.
A message box will appear to notify you if and when the firmware-setup has been completed successfully.
9.4.6
Continuing the configuration
Once the interface has been configured successfully, the program attempts to set up a connection with the device and
to determine the device's hardware configuration. This process can last a few minutes.
Note
The File menu offers a function for working with the log-book.
Each action during the firmware setup and errors (if occurring) are
registered in a log book. This log book can be displayed with menu
command File Þ Show log book...
The Options menu offers the option to Update all components. This makes it
possible to earmark all the components of the selected device for an update.
The function is only to be used in compliance with instructions from the SIMEAS
Q80 7KG8080-Hotline.
If the PC is unable to connect with the device, switch the device off for about 10 seconds. Then
it should work without further problems.
Assembly, Commissioning, Parameterization
Power Quality Recorder SIMEAS Q80 7KG8080, Operating instruction
E50417-B1074-C419-A1, Release 07.05.2010
E-29