Miscellaneous; Backup And Restore; User Parameter Sets - ABB ACS280 Firmware Manual

Coldplate drives
Hide thumbs Also See for ACS280:
Table of Contents

Advertisement

Miscellaneous

Backup and restore

You can make backups of the settings manually to the assistant panel. The
panel also keeps one automatic backup. You can restore a backup to another
drive, or a new drive replacing a faulty one. You can make backups and restore
on the panel, or with the Drive composer PC tool.
See the relevant assistant control panel for more information on backing up and
settings.
Backup
Manual backup
Make a backup when necessary, for example, after you have started up the drive
or when you want to copy the settings to another drive.
Parameter changes from fieldbus interfaces are ignored unless you have forced
parameter saving.
Automatic backup
The assistant panel has space for one automatic backup. An automatic backup
is created two hours after the last parameter change. After completing the
backup, the panel waits for 24 hours before checking if there are additional
parameter changes. If there are, it creates a new backup overwriting the
previous one when two hours have passed after the latest change.
You cannot adjust the delay time or disable the automatic backup function.
Parameter changes from fieldbus interfaces are ignored unless you have forced
parameter saving.
Restore
The backups are shown on the panel. Automatic and manual backups are
separately marked.
Note: To restore a backup, the drive has to be in Local control.
Settings and diagnostics
96.07 Parameter save manually
Parameter
Events: -

User parameter sets

The drive supports four user parameter sets that can be saved to the
permanent memory and recalled using drive parameters. It is also possible to
Program features 83