Preparing for use
5.10 Converter operation
Immunity to interference
The machines fulfill the requirements of interference immunity in conformity with EN /
IEC 61000-6-2. For machines with integrated sensors, e.g. PTC thermistors, the operating
company must ensure sufficient interference immunity by selecting a suitable sensor signal
cable (possibly with shielding, connected in the same way as the machine feeder cable) and a
suitable evaluation unit.
When operating the machines from a converter at speeds higher than the rated speed, carefully
comply with the mechanical speed limits (safe operating speed EN / IEC 60034-1).
5.10

Converter operation

1FU9 motors are operated on the converter in the SYNCHRONOUS U/f operating mode.
5.10.1

Parameterizing the converter

• If the design of the motor requires connection to a particular converter type, the rating plate
will contain corresponding additional information.
• Correctly parameterize the converter. Parameterizing data can be taken from the machine
rating plates.
You can also find parameter data here:
– Operating instructions for the converter.
– SINAMICS Configuration Manuals.
• Do not exceed the specified limit rotational speed n
plate n
• Check that the machine is cooled sufficiently for commissioning purposes.
5.10.2

Converter input voltage

The insulation system of SIMOTICS machines complies with the requirements of stress category
C (IVIC C = high stress). If voltage peaks higher than those specified according to IVIC C can occur,
contact the Service Center.
• For a line supply voltage (converter input voltage) up to max. 480 V, and when controlled
from a SINAMICS converter with uncontrolled/controlled infeed: Comply with the guidelines
for configuring motor and converter.
• The insulation system of the machines is not suitable for a line voltage (converter input
voltage) greater than 480 V.
• Operation with a converter from another manufacturer: Comply with the permissible voltage
peaks according to IEC 60034-18-41 in accordance with stress category C, dependent on the
particular line voltage (converter input voltage) and the motor insulation system.
48
on the supplementary plate for converter operation as the highest speed.
max
. You can either find this on the rating
max
Operating Instructions, 10/2023, A5E46712792A