Item
Maximum number of link points per
network
Maximum
When the
number of
submaster
link points
function is
per station
not used
When the
submaster
function is
used
Local station
9 CONTROL NETWORK MODULE MIGRATION
322
9.2 Comparison of Control Network Module Specifications
Specifications
QJ71GF11-T2
RX
16384 points, 2K bytes
RY
16384 points, 2K bytes
RWr
8192 points, 16K bytes
RWw
8192 points, 16K bytes
Master
RX
16384 points, 2K bytes
station
RY
16384 points, 2K bytes
RWr
8192 points, 16K bytes
RWw
8192 points, 16K bytes
Master
RX
16384 points, 2K bytes
operating
RY
16384 points, 2K bytes
station
(2048 points and 256 bytes for the send range of an own
station)
RWr
8192 points, 16K bytes
RWw
8192 points, 16K bytes
(1024 points and 2048 bytes
for the send range of an own
station)
8192 points when
communication mode is
"High-Speed" (Own station
send range is 256 points.)
Submaster
RX
2048 points, 256 bytes (assigned for the station number 0 or
operating
submaster station)
station
RY
2048 points, 256 bytes (assigned for the station number 0 or
submaster station)
RWr
1024 points, 2048 bytes
(assigned for the station
number 0 or submaster
station)
256 points, 512 bytes when
communication mode is
"High-Speed"
RWw
1024 points, 2048 bytes
(assigned for the station
number 0 or submaster
station)
256 points, 512 bytes when
communication mode is
"High-Speed"
RX
2048 points, 256 bytes
RY
2048 points, 256 bytes
RWr
1024 points, 2048 bytes
256 points, 512 bytes when
communication mode is
"High-Speed"
RWw
1024 points, 2048 bytes
256 points, 512 bytes when
communication mode is
"High-Speed"
Compatibility
RJ71GF11-T2
8192 points, 16K bytes
(1024 points and 2048 bytes
for the send range of an own
station)
8192 points when
communication mode is
"High-Speed" (Own station
send range is 256 points.)
1024 points, 2048 bytes
(assigned for the station
number 0 or submaster
station)
256 points, 512 bytes when
communication mode is
"High-Speed"
1024 points, 2048 bytes
(assigned for the station
number 0 or submaster
station)
256 points, 512 bytes when
communication mode is
"High-Speed"
1024 points, 2048 bytes
256 points, 512 bytes when
communication mode is
"High-Speed"
1024 points, 2048 bytes
256 points, 512 bytes when
communication mode is
"High-Speed"
Precautions