5-4
Mains Filter
Technical Data NFE / NFD
Maximum
Nominal
connecting
mains
voltage of
current
mains
I
Netz
50..60 Hz
U
(1)
N
in V
in A
AC 480V+10%
7
AC 480V+10%
16
AC 480V+10%
30
AC 480V+10%
55
AC 480V+10%
75
AC 480V+10%
130
AC 480V+10%
180
AC 230V+10%
7,5
AC 230 V+10%
4,7
NFD = three-phase filter, NFE = single-phase filter
(1) = maximum continuous current on mains side at 45°C ambient temperature
(2) = to be used only for interference suppression of the NTM power supply unit
(3) = a conductor cross section of 10 mm
Operating frequency
Power dissipation
Temperature range
Overload
Effective attenuation
Saturation
Test voltage
Current reduced with
overtemperature
Leakage current at
50 Hz
Protection category
No. of
Type of mains
phases
filter
3
NFD 03.1-480-007
3
NFD 03.1-480-016
3
NFD 03.1-480-030
3
NFD 03.1-480-055
3
NFD 03.1-480-075
3
NFD 03.1-480-130
3
NFD 03.1-480-180
1
NFE 02.1-230-008
1
NFE 01.1-250-006
(2)
2
is to be connected for the ground wire by means of a plug connector or ring cable lug
Fig. 5-4: Technical Data
From 0 to 60 Hz at 45 °C
2
measured at 2 or 3 x R I
Nenn DC
-25 ...+ 85 °C
1.5 I
1 minute per hour or 4 I
Nenn
frequency range 150 kHz – 30 MHz
reduction of filter attenuation by 6 dB with 2.5-to 3-fold nominal current
L/N -> PE or L -> PE: 2700 V
N -> L
2100 V
see formula for calculating the reduction
symmetrical three-phase operation: typ. 30 mA,
single-phase operation or in the case of fuse failure of a phase: typ. 175 ... 190mA
IP20, except for NFE01.1-250-006: IP 10
Fig. 5-5: Technical Data
Terminals (3)
flexibel
starr
mm²
mm²
AWG
4 (3)
6 (3)
AWG 12
4 (3)
6 (3)
AWG 12
10
16
AWG 6
16
25
AWG 4
25
35
AWG 3
50
50
AWG 1/0
95
95
AWG 4/0
4 (3)
6 (3)
AWG 10
tab connectors
6,3 x 0,8 mm
für 10 s
Nenn
2 s at 25 °C
DC
2 s at 25 °C
DC
DOK-INDRV*-ADDCOMP****-PR02-EN-P
Rexroth IndraDrive
Power
Weight
Type
dissi-
pation
approx
W
kg
3,9
0,7
vertical
6,4
1,0
vertical
11,9
1,4
vertical
25,9
2,0
vertical
30,4
3,5
vertical
38
4,7
vertical
61
10
vertical
7,2
1,1
vertical
4
0,245
horizontal