REFUspeed RS51
Drive setting
Parame-
Name
ter No.:
0071
Load factorySetting
0732
Copy from keypad
0733
Copy data to keypad
DOK-RD500*-RS51*******-IB02-EN-P
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Description / explanation
selectable options
0 =
no action
1 =
basic, standard values are loaded
Parameters, with a password level less than
or the same as the entered password level
are set to the standard value of the basic
parameterization.
P0064 0 = Basic parametrization
P0057 0 = not active
2 =
free standard values are loaded
Parameters with a password level less than
or equal to the entered password level are set
to the standard value of the free parameter
ization.
P0064 1 = Free parametrization
P0057 0 = not active
3 =
standard values for NAMUR applications are
loaded
Parameters, with a password level less than
or the same as the entered password level
are set to the standard value of the basic
parameterization with activated NAMUR func
tions.
P0064 0 = Basic parametrization
P0057 1 = active
4 =
standard values for Sercos applications are
loaded
Parameters, with a password level less than
or the same as the entered password level
are set to the standard value of the free
parameterization for Sercos applications.
P0064 1 = Free parametrization
P0057 0 = not active
The parameters with are relevant for
applications with Sercos option interface are
set.
Caution: Only those parameters are copied which are
enabled as a result of the selected password.
The data set, saved in the operator panel is copied
into the drive.
0 =
no
1 =
yes
2 =
designation (the saved data set designation
can be viewed here)
The complete drive converter data set is copied into
the operator panel.
0 =
no
1 =
yes
A data set name can be entered after the data trans-
fer.
You can scroll through the ASCII code using the + and
- keys (the system goes to the start of the following
ranges by simultaneously pressing the + and - keys: A,
a, 0 and the blank symbol).
You can move the cursor to the right or left using the <
or > key.
Basic parameterization
Factory setting
min ... max values
No action
0 ... 4
No
0 ... 2
No
0 / 1
7-21
Pass
wor
d
0
0