Bosch Rexroth REFUspeed RS51 Operating Instructions Manual page 69

Drive control devices for high-speed grinding spindles
Table of Contents

Advertisement

REFUspeed RS51
Parame-
Name
ter No.:
0778
0390.XX
Frequency normali-
zation
0374.XX
Current normalization Reference value for current setpoints and actual val-
0072.XX
Param. setting
0280.YY
Ramp-up time
0281.YY
Ramp-down time
DOK-RD500*-RS51*******-IB02-EN-P
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Description / explanation
selectable options
Reference value for frequency setpoints and actual
values.
This parameter is set to 50 Hz in the factory. To oper-
ate the motor with 50 Hz, a setpoint of 100% must be
entered.
ues.is set to the value of the drive current in the fac-
tory (P0024).
Enters from which source the parameter can be set.
0
=
Operator panel ,
1
=
Bus SS1 ,
2
=
Bus SS2 ,
3
=
Bus SS4 ,
4
=
All buses ,
5
=
Bus SS6
Refer to Fig. 5-3: Up and down ramp
Ramp-up time of the ramp-function generator. The
entered time is valid for a setpoint change from 0 % to
100 %.
XX=The index, in which a value can be saved, is se-
lected in parameters P0875, P0876; P0877; P0878,
P0879 or P0880 (function: Setpoint memory, bits 20 ...
23).
Refer to Fig. 5-3: Up and down ramp
Ramp-down time of the ramp-function generator. The
entered time is valid for a setpoint change normalized
for 100%.
XX=The index, in which a value can be saved, is se-
lected in parameters P0875, P0876; P0877; P0878,
P0879 or P0880 (function: Setpoint memory, bits 20 ...
23).
1:
The motor data of a typical motor are set as factory setting for each
drive output class.
2:
This menu item is only displayed, if an induction motor was selected
as motor type.
3:
This menu item is only displayed if a synchronous motor was se-
lected as motor type.
XX:
The index, shown in the display, is defined by the currently active pa-
rameter set.
YY:
The index, shown in the display, is determined by the currently active
setpoint memory.
Basic parameterization
Factory setting
Pass
wor
min ... max values
d
50.00 Hz
2
15.0 Hz ... P0027
P0024
2
0.5 ... 6553.5
Operator panel, PC
2
0...5
5.000 s
1
0.000 ... 3200.000
s
5.000 s
1
0.000 ... 3200.000
s
7-5