REFUspeed RS51
Parame-
Name
ter No.:
0871
On/off in TEST
0872
Setpoint in NORMAL
0873
Setpoint in TEST
0196
Mot. pot. mode
0195
Mot. pot. step value
0265.YY Fix value main s/p
DOK-RD500*-RS51*******-IB02-EN-P
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
Description / explanation
selectable options
Enters On/off for TEST operation.
As for parameter 0870.
Enters the setpoint for NORMAL operation
0
=
Motorized potentiometer
1
=
Fixed setpoint
2
=
Analog input 0..±10V
3
=
Analog input 0..+20mA
4
=
Analog input 4..+20mA
5
=
Opt. an. input 0..±10V (opt.
=
optional)
6
=
Opt. an. input 0..+20mA
7
=
Opt. an. input 4..+20mA
8
=
PC (PC with REFUwin via
service interface)
9
=
Bus SS1
10
=
Bus SS2
11
=
Bus SS4
12
=
Analog input 2..+10V
13
=
Bus SS6
Enters the setpoint for TEST operation
As for parameter 0872.
Supplementary parameter for "motorized potentiome-
ter".
For Start f set, the motorized potentiometer setpoint,
which was set the last after the off command, is ap-
proached.
For Start f min, the actual f min (P0180.XX) is ap-
proached.
Furthermore, the rate-of-change of the motorized po-
tentiometer can be set using the parameter:
linear
=
Uniform change
corresponding to the
selected step width
expon. =
The rate-of-change
increases the longer that
the button remains pressed
0
=
Start f set, linear
1
=
Start f min, linear
2
=
Start f set, exponential
3
=
Start f min, exponential
Supplementary parameter for "motorized potentiome-
ter".
The motorized potentiometer rate-of-change is set
using the step width.
Supplementary parameter for "fixed setpoint".
Parameter P0390 is the reference value for the fre-
quency setpoints and actual values.
P0390 is set to 50 Hz in the factory. This means that
to operate the motor with 50 Hz, a setpoint of 100%
must be entered.
YY =
The index which is displayed is determined by
the presently active setpoint memory.
Basic parameterization
Factory setting
Pass
wor
min ... max values
d
OP (Operator
1
panel) dynamic
0...11
Analog input
1
0..±10V
0...13
Motorized potenti-
1
ometer
0...13
Start f set, expon.
1
0 ... 3
0.01
1
0.01 ... 10.00 Hz
5.00 %
1
-199.99 ... 199.99
%
7-7